You are on page 1of 20

DEAD LOAD CALCULATION FOR STRUCTURE

Selfweight of the structure


Dead load for roof including purlins = 0.80 Kn/m2
Dust Load = 0.2 Kn/m2
Total Dead Load = 1.00 Kn/m2
Façade Loads including Façade Purlins = 0.80 Kn/m2
Hoist Beam selfweight = 3.00 Kn
Hoist selfweight = 2.00 Kn
Total Hoist Dead Load = 5.00 Kn
Dead Load of RC roof slab (considering 200 mm) = 0.00 Kn/m2
Floor Finishing = 0.00 Kn/m2
Decking Sheet = 0.00 Kn/m2
False Ceiling = 0.60 Kn/m2
Cable tray load (2 levels) including support weight@ 1.5 m spacing = 350.00 Kg/m
Twisting Moment due to cable trays = 105.00 kg-m

DEAD LOAD CALCULATION FOR FOUNDATION


Dead load of slab (500 tk ) = 12.5 Kn/m2
Dead load of soil considering 0.5m depth = 9.00 Kn/m2
Ground floor wieght 5.8 kn/m2
ground live load considered in dead 15 kn/m2
E

(as per clause 8.1.1 Civil design criteria)


(as per clause 8.1.4 Civil design criteria)

42 kg/m
420 2.73
0.42

ON
LIVE LOAD CALCULATIONS
For non accessible roofs
Live Load on Roof = 1 Kn/m2 (As per clause 7.3 Civil Design Critera)
Hoist Load Calculation

Hoist capacity 10 KN
Hoist self weight 2 KN
Selfweight of hoist beam 1.8 KN
Dynamic coeffcient for vertical action 1.1
coeffcient for Horzontal action 0.05
Longitudinal Horizontal Load, HL 0.55 KN
Critical Load applied on each beam
Vertical Load 11 KN
Longitudinal Horizontal Load, HL 0.55 KN

Selfweight of Hoist 3 KN
Hoist capacity 10 KN
ɸ1 1.1
Class HC1
Hoisting speed,Vh 0.1 m/s
ɸ2 min 1.05
β2 0.17
ɸ2 1.07
ɸ4 Not Applicable
ɸ5 1
ɸ6 1.035 (for 1
ɸ6 1 (for 1
Longitudinal Horizontal Load, HL 1.3 KN
Transverse Horizontal Load, HT 1.3 KN
Dynamic Test Load 11 KN
Static Test Load 12.5 KN
Critical Load Combination applied on each beam
Vertical Load 16 KN
Longitudinal Horizontal Load, HL 1.3 KN
Transverse Horizontal Load, HT 1.3 KN
alculation

(as per input data)

considering IPE 240 for 6 m span


(as per Table 2.4, EN 1991-3)
(as per clause 8.9 Civil design criteria)
(as per 2.5.1.2 of Eurocode 1 - Part-3)

(as per input data)


(as per input data)
(as per Table 2.4, Eurocode 1 - Part -3)
(as per 7.13 of Civil Design Criteria )
(assumed)
(as per Table 2.5, Eurocode 1 - Part-3)
(as per Table 2.5, Eurocode 1 - Part-3)
(as per Table 2.4, Eurocode 1 - Part-3)

(as per Table 2.6, Eurocode 1 - Part-3)


(as per 2.10 of Eurocode 1 - Part-3)
(as per 2.10 of Eurocode 1 - Part -3)
(as per 7.13 of Civil Design Criteria)
(as per 7.13 of Civil Design Criteria)
( as per 2.10 of Eurocode 1 - Part-3)
( as per 2.10 of Eurocode 1 - Part-3)
(as per Table 2.2 of Eurocode 1 - Part-3)
(Static Test Load case)
NF EN 1991-1-4:2005 & NA EUROCODE EXPRESSIONS
EC
Basic wind velocity Vb (m/s) 24
Fundamental value of the basic wind velocity Vb,0 (m/s) 24
Directional factor c dir 1 recommended value NA
Seasonal factor c season 1 recommended value NA

Mean wind velocity Vm (m/s) 27.52


Roughness factor Cr 1.147
orography factor Co 1
Building top height z (m) 6
Roughness length kr 0.162

Terrain factor depending on the roughness length z0 (m) 0.005


(acc. table 4.1 (NA))
minimum height (acc table 4.1 (NA)) zmin (m) 1 Terrain category 0

Basic velocity pressure qb (kN/m2) 0.353


Air density (acc. 4.5 (1) (NA)) ρ (kg/m3) 1.225
Turbulence density Iv(z) 0.14
Turbulence factor (acc. 4.4 (1) (NA)) ki 0.999976677
Peak velocity pressure qp(z) ( kN/m2) 0.922
WIND LOADS - NF EN 1991 1-4

All exposed structures or parts of structure shall be designed to resist the pressures due to wind in any direction in accordance
with the applicable provisions according to Eurocode NF EN 1991 1-4 2005 & NA.

1 WIND DESIGN PARAMETERS

qp(b) = 0.920 kN/m2

2 BUILDING DESIGN PARAMETERS

- Short side: b= 12.0 m

- Long side: d= 18.5 m

- Height: h= 5.50 m

- Roof slope: q= 8.0 º

3 WIND FORCES ON FACADES AND ROOF

WIND FORCES IN X DIRECTION

External pressure coefficient:

Walls:

Cpe,A = -1.2 e= 11.0 m e=min(b,2h)


Cpe,B = -0.8 e/5 = 2.2 m b= 18.5 m
Cpe,C = -0.5 e/4 = 2.8 m
Cpe,D = +0.75 e/2 = 5.5 m
Cpe,E = -0.4 e/10 = 1.1 m
Roof:
q = 8º: q = 90º:
Cpe,F = -1.50 0.0 Cpe,F = -1.50
Cpe,G = -1.10 0.0 Cpe,G = -1.30
Cpe,H = -0.45 0.0 Cpe,H = -0.65
Cpe,I = -0.50 -0.4 Cpe,I = -0.55
Cpe,J = -0.50 -0.4
Internal pressure coefficient:

= 29.00 m2
0.906 Cpi = 0.30
= 32.00 m2

WL+X_A:

Considering a negative value of Cpi applied to all internal surfaces

Walls:
Wind pressure where 0 < Z < b

qpe,A = -0.83 kN/m2


qpe,B = -0.46 kN/m2
qpe,C = -0.18 kN/m2
qpe,D = 0.97 kN/m2
qpe,E = -0.09 kN/m2
Roof: F G H
q = 8º: 3.25 -3.588 -2.392 -0.4485
qpe,F = -1.10 0.28 kN/m2 7.25 -8.004 -5.336 -1.0005
qpe,G = -0.74 0.28 kN/m2 4 -4.416 -2.944 -0.552
qpe,H = -0.14 0.28 kN/m2 6 -6.624 -4.416 -0.828
qpe,I = -0.18 -0.09 kN/m 2
2 -2.208 -1.472 -0.276
qpe,J = -0.18 -0.09 kN/m2

WL+X_B:

Considering a positive value of Cpi applied to all internal surfaces

Walls:
Wind pressure from 0 < Z < b

qp,A1 = -1.38 kN/m2


qp,B1 = -1.01 kN/m2
qp,C1 = -0.74 kN/m2
qp,D1 = 0.41 kN/m2
qp,E1 = -0.64 kN/m2

Roof:
q =8º: F G H
qp,F = -1.66 -0.28 kN/m2 3.25 -5.382 -4.186 -2.2425
qp,G = -1.29 -0.28 kN/m2 7.25 -12.006 -9.338 -5.0025
qp,H = -0.69 -0.28 kN/m2 4 -6.624 -5.152 -2.76
qp,I = -0.74 -0.64 kN/m 2
6 -9.936 -7.728 -4.14
qpe,J = -0.74 -0.64 kN/m2 2 -3.312 -2.576 -1.38
WIND FORCES IN Y DIRECTION

External pressure coefficient:

Walls:

Cpe,A = -1.2 e= 11.0 m e=min(d,2h)


Cpe,B = -0.8 e/5 = 2.2 m b= 12.0 m
Cpe,C = -0.5 e/4 = 2.8 m
Cpe,D = +0.8 e/2 = 5.5 m
Cpe,E = -0.5 e/10 = 1.1 m

Roof:

Cpe,F = -1.5
Cpe,G = -1.3
Cpe,H = -0.7
Cpe,I = -0.6

Internal pressure coefficient:

= 9.00 m2
0.333 Cpi = 0.30
= 27.00 m2

WL+Y_A:

Considering a negative value of Cpi applied to all internal surfaces

Walls:
qp,A = -0.83 kN/m2
qp,B = -0.46 kN/m2
qp,C = -0.18 kN/m2
qp,D = 1.01 kN/m2
qp,E = -0.74 kN/m2
Roof:

q = 90º:
qp,F = -1.10 kN/m2
qp,G = -0.92 kN/m2
qp,H = -0.34 kN/m2
qp,I = -0.25 kN/m2
WL+Y_B:

Considering a positive value of Cpi applied to all internal surfaces

Walls:
qpe,A = -1.38 kN/m2
qpe,B = -1.01 kN/m2
qpe,C = -0.74 kN/m2
qpe,D = 0.46 kN/m2
qpe,E = -0.74 kN/m2
Roof:

q = 90º:
qpe,F = -1.66 kN/m2
qpe,G = -1.47 kN/m2
qpe,H = -0.89 kN/m2
qpe,I = -0.80 kN/m2
Wind load for roof Purlins
q = 0.922
Cpe,1 (F) = -2.35
Cpe,1 (G) = -1.85
cpi = 0.3
wind load (F) = -2.442536 kn/m2
wind load (F) = -1.889509 kn/m2
wind load (G) = -1.98168 kn/m2
wind load (G) = -1.428653 kn/m2

Wind load forfacade Purlins


q = 0.922
Cpe,1 (A) = -1.4
Cpe,1 (B) = -1.1
Cpe,1 (C) = -0.5
Cpe,1 (D) 1
cpi = 0.3
wind load (A) = -1.57 kn/m2
wind load (A) = -1.01 kn/m2
wind load (B) = -1.29 kn/m2
wind load (B) = -0.74 kn/m2
wind load (C) = -0.74 kn/m2
wind load (C) = -0.18 kn/m2
wind load (D) = 0.65 kn/m2
wind load (D) = 1.20 kn/m2
SEISMIC LOAD CALCULATIONS

Region = 1
Ocuupancy Category = IV
Importance factor = 1.5
Site Class = C
Seismic design category = D
Ss (%g) = 0.55
S1(%g) = 0.25
g= 9.8
Sms = Fa Ss
Sm1 = Fv S1
SDS = 2/3 Sms
SD1 = 2/3 Sm1
Fa = 1.4
Fv = 1.9
Sms = 0.77
Sm1 = 0.48
SDS = 0.51
SD1 = 0.32

weight(kn) = 85
SDS = 0.55
Ie = 1.5
Hi = 3
Hn = 13.5
fe/me = 0.238
fe (kn) = 20.258

weight 5.4
SDS 0.55
Ie 1.5
Hi 3
Hn 13.5
Fa/Wp 0.238

Fa = 1.287
SEISMIC LOAD CALCULATIONS AUX TRANSFORMER

Region = 1
Ocuupancy Category = IV
Importance factor = 1.5
Site Class = C
Seismic design category = D
Ss (%g) = 0.55
S1(%g) = 0.25
g= 9.8
Sms = Fa Ss
Sm1 = Fv S1
SDS = 2/3 Sms
SD1 = 2/3 Sm1
Fa = 1.4
Fv = 1.9
Sms = 0.77
Sm1 = 0.48
SDS = 0.51
SD1 = 0.32

You might also like