Professional Documents
Culture Documents
42 kg/m
420 2.73
0.42
ON
LIVE LOAD CALCULATIONS
For non accessible roofs
Live Load on Roof = 1 Kn/m2 (As per clause 7.3 Civil Design Critera)
Hoist Load Calculation
Hoist capacity 10 KN
Hoist self weight 2 KN
Selfweight of hoist beam 1.8 KN
Dynamic coeffcient for vertical action 1.1
coeffcient for Horzontal action 0.05
Longitudinal Horizontal Load, HL 0.55 KN
Critical Load applied on each beam
Vertical Load 11 KN
Longitudinal Horizontal Load, HL 0.55 KN
Selfweight of Hoist 3 KN
Hoist capacity 10 KN
ɸ1 1.1
Class HC1
Hoisting speed,Vh 0.1 m/s
ɸ2 min 1.05
β2 0.17
ɸ2 1.07
ɸ4 Not Applicable
ɸ5 1
ɸ6 1.035 (for 1
ɸ6 1 (for 1
Longitudinal Horizontal Load, HL 1.3 KN
Transverse Horizontal Load, HT 1.3 KN
Dynamic Test Load 11 KN
Static Test Load 12.5 KN
Critical Load Combination applied on each beam
Vertical Load 16 KN
Longitudinal Horizontal Load, HL 1.3 KN
Transverse Horizontal Load, HT 1.3 KN
alculation
All exposed structures or parts of structure shall be designed to resist the pressures due to wind in any direction in accordance
with the applicable provisions according to Eurocode NF EN 1991 1-4 2005 & NA.
- Height: h= 5.50 m
Walls:
= 29.00 m2
0.906 Cpi = 0.30
= 32.00 m2
WL+X_A:
Walls:
Wind pressure where 0 < Z < b
WL+X_B:
Walls:
Wind pressure from 0 < Z < b
Roof:
q =8º: F G H
qp,F = -1.66 -0.28 kN/m2 3.25 -5.382 -4.186 -2.2425
qp,G = -1.29 -0.28 kN/m2 7.25 -12.006 -9.338 -5.0025
qp,H = -0.69 -0.28 kN/m2 4 -6.624 -5.152 -2.76
qp,I = -0.74 -0.64 kN/m 2
6 -9.936 -7.728 -4.14
qpe,J = -0.74 -0.64 kN/m2 2 -3.312 -2.576 -1.38
WIND FORCES IN Y DIRECTION
Walls:
Roof:
Cpe,F = -1.5
Cpe,G = -1.3
Cpe,H = -0.7
Cpe,I = -0.6
= 9.00 m2
0.333 Cpi = 0.30
= 27.00 m2
WL+Y_A:
Walls:
qp,A = -0.83 kN/m2
qp,B = -0.46 kN/m2
qp,C = -0.18 kN/m2
qp,D = 1.01 kN/m2
qp,E = -0.74 kN/m2
Roof:
q = 90º:
qp,F = -1.10 kN/m2
qp,G = -0.92 kN/m2
qp,H = -0.34 kN/m2
qp,I = -0.25 kN/m2
WL+Y_B:
Walls:
qpe,A = -1.38 kN/m2
qpe,B = -1.01 kN/m2
qpe,C = -0.74 kN/m2
qpe,D = 0.46 kN/m2
qpe,E = -0.74 kN/m2
Roof:
q = 90º:
qpe,F = -1.66 kN/m2
qpe,G = -1.47 kN/m2
qpe,H = -0.89 kN/m2
qpe,I = -0.80 kN/m2
Wind load for roof Purlins
q = 0.922
Cpe,1 (F) = -2.35
Cpe,1 (G) = -1.85
cpi = 0.3
wind load (F) = -2.442536 kn/m2
wind load (F) = -1.889509 kn/m2
wind load (G) = -1.98168 kn/m2
wind load (G) = -1.428653 kn/m2
Region = 1
Ocuupancy Category = IV
Importance factor = 1.5
Site Class = C
Seismic design category = D
Ss (%g) = 0.55
S1(%g) = 0.25
g= 9.8
Sms = Fa Ss
Sm1 = Fv S1
SDS = 2/3 Sms
SD1 = 2/3 Sm1
Fa = 1.4
Fv = 1.9
Sms = 0.77
Sm1 = 0.48
SDS = 0.51
SD1 = 0.32
weight(kn) = 85
SDS = 0.55
Ie = 1.5
Hi = 3
Hn = 13.5
fe/me = 0.238
fe (kn) = 20.258
weight 5.4
SDS 0.55
Ie 1.5
Hi 3
Hn 13.5
Fa/Wp 0.238
Fa = 1.287
SEISMIC LOAD CALCULATIONS AUX TRANSFORMER
Region = 1
Ocuupancy Category = IV
Importance factor = 1.5
Site Class = C
Seismic design category = D
Ss (%g) = 0.55
S1(%g) = 0.25
g= 9.8
Sms = Fa Ss
Sm1 = Fv S1
SDS = 2/3 Sms
SD1 = 2/3 Sm1
Fa = 1.4
Fv = 1.9
Sms = 0.77
Sm1 = 0.48
SDS = 0.51
SD1 = 0.32