You are on page 1of 2

 

Sub‐Contractor:  Saudi  Binladin 


Date Issued:  26/12/2019 
Group 
Title: Design Calculations: False work at 3rd floor open court
DESIGNED BY:     Engr.Shoeb 

 
Design Criteria:‐

 All design are based on American code ( AISC360-16)


 All Structural members, plates and connections are
made of stain less steel Grade A304
 Structural analysis and design made by SAP 2000 V
20.2 software
 Connection in IDEA STATICA with link BIM with
SAP200 v20.2.
 Connection designs of weld made as per AISC in
Limcon.
 Base plate connection designed in Hilti Achors.

Synopsis:-

 Considering SHS section TUBE 60x60x3.with stainless


steel Gr.304
 Assuming 30mm thick marble to be fixed to this
frame.
 
Sub‐Contractor:  Saudi  Binladin 
Date Issued:  26/12/2019 
Group 
Title: Design Calculations: False work at 3rd floor open court
DESIGNED BY:     Engr.Shoeb 

Loads:
 
 Dead load – Self weight of steel Structural members
calculated by SAP program
 Self-weight of Marble = 0.03M (thick.) x 28 KN/M3 = 0.84KN/m2

 Assuming Self-weight of halfen channel 50x25x3 per 1 meter +


marble fixing to the channel on one side as per available
drawing dim of marble assuming 1m length x0.5m depth =
0.0215 + (28x0.5x0.03) = 0.42 KN/m2

 Total dead load = 0.8615 (Marble weight at middle) + 0.42


(Weight of marble on both sides) = 1.28KN/m2

 Wind loads as per project specification as per code SBC 301/


ASCE 7-05
 V (basic wind speed) = 152 Km/h = 94 m/h
 Exposer category =C
 G (gust factor) = 1.79
 Cp pressure Coefficient = +/-0.8 & +/-0.5 applied for one
side wind Y direction based on 3 axis directions.
 Values input in SAP model on frame with none value
cladding.

 Earth quake loads as per project specification as per code


SBC 301/ ASCE 7-05 Ss=0.25g, S1=0.111g, for 2sec spectral
acceleration. Values input in SAP.

You might also like