Professional Documents
Culture Documents
Test Device: Excitation Curve
Test Device: Excitation Curve
Overall assessement OK
Asset
Ipn 800.0 A Object Location
Isn 1.0 A Manufacturer RITZ Company SEC
Rated burden 30.0 VA /0.80 Type ASG36-70 Country KSA
Operating burden 30.0 VA /0.80 Serial number 19/80325435 Station MOBILE SS
Standard IEC 61869-2 Core 1 Feeder M04
Application Protection Tap 2 Phase B
Class 5P Optional IEC-ID
Frequency 60.0 Hz Comment
Rct max 5.255 Ω ?
ALF 20.0
Ts
Burden
Burden cos φ: Z
V-meas I-meas
Excitation
Ls 0.006819 H Lm 122.1246 H Results at rated burden (30.00 VA) Results at operating burden (30.00 VA)
Kr 78.15 % ALF > 24.98 ALFi 24.05 ALF > 24.98 ALFi 24.05
Standard IEC 61869-2 εci (@ ALF=20) 0.114 % εci (@ ALF=20) 0.114 %
V-kn 628.03 V I-kn 0.0179 A Ts 4.174 s Ts 4.174 s
Ratio
Turns ratio 799.9594 Results at rated burden (30.00 VA) Results at operating burden (30.00 VA)
εt -0.0051 % Ratio 800.0 : 0.9989 Ratio 800.0 : 0.9989
Polarity OK ε -0.1055 % ∆φ 0.46 min ε -0.1055 % ∆φ 0.46 min
εc 0.1063 % εc 0.1063 %
Residual magnetism
Residual flux
Residual magnetism
Excitation curve
900.00
800.00
700.00
600.00
Voltage [V]
500.00 X1-X2
400.00
300.00
200.00
100.00
0.00
0.00 0.500 1.00 1.50 2.00 2.50 3.00
Ie [A]
1/2
Current ratio error in % at % of rated current at rated burden (30.00 VA)
VA/cos φ 1.00 % 5.00 % 10.00 % 20.00 % 50.00 % 100.00 % 120.00 % 200.00 %
30/0.8 -0.4779 -0.2378 -0.1881 -0.1525 -0.1214 -0.1055 -0.1008 -0.0904
15/0.8 -0.3442 -0.1564 -0.1218 -0.0966 -0.0742 -0.0629 -0.0604 -0.0548
7.5/0.8 -0.2424 -0.1084 -0.0810 -0.0639 -0.0476 -0.0394 -0.0377 -0.0336
3.75/1 -0.0719 -0.0496 -0.0393 -0.0318 -0.0249 -0.0209 -0.0200 -0.0180
20.0000
7.50 VA
0.0000
-20.0000 3.75 VA
-40.0000
Limits
-60.0000
-80.0000
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]
2/2