Site Test Report: Accuracy Testing of Energy Meter - Elster
Site Test Report: Accuracy Testing of Energy Meter - Elster
B. Function Test
NO FUNCTIONS
1 Physical /Visual Inspection.
2 Electrical check.
3 Metering Minimum Current
4 Current Measurement
5 Voltage Measurement
6 POWER(MW-MVAR) Measurement
7 Accuracy Test
8 Maximum Demand
2. Electrical Checks:
Item Description Remark
3. Metering
TEST PERFORMED BY TEST WITNESSED BY DATE
NAME
SIGNATURE
TEST EQUIPMENT Calibration Due:10 MAY, Serial No:
File : 505771613.doc
SITE TEST REPORT
APPLIED
APPLIED VOLTAGE REMARKS
CURRENT
69.28 0.0 A No Increment In Energy Values
4- Current Measurements:
5- Voltage Measurements:
90%
7.17 7.17 7.17 7.169 7.167 7.167
62.355 V
100%
7.967 7.967 7.967 7.965 7.963 7.964
69.28 V
110%
8.764 8.764 8.764 8.760 8.759 8.758
76.212 V
7. Accuracy Test