MENGEMUKAKAN PELAN PINDAAN AS BUILT BAGI BLOK F, KOMPLEKS

JABATAN KERJA RAYA MALAYSIA ( JKR ), DI ATAS LOT NO 75, SEKSYEN 60


JALAN SULTAN SALAHUDDIN, BANDAR KUALA LUMPUR, 50480 WILAYAH
PERSEKUTUAN KUALA LUMPUR UNTUK :
TETUAN JABATAN KERJA RAYA MALAYSIA

WET CHEMICAL SYSTEM

Hood Gerai 2 - Gerai 6 Size, Total 5 Nos. Hood : (1.5m X 0.6m) per Hood
a) Hood (ADP) nozzle
Area coverage per nozzle is 1000mm x 1000mm
Therefore, no. of nozzle required = 2 nos. nozzle per hood

b) Exhaust duct (ADP) nozzle


Requirement is 1 nozzle per exhaust duct for duct's perimeter, x : x< 1200mm
Therefore, no. of nozzle required = 1 nos. nozzle per hood

c) Plenum nozzle
Plenum length (L) = 3000mm
Area coverage per nozzle = 3000mm(L) x 1200mm(W)
Therefore, no. of nozzle required = 1 nos. nozzle per hood

d) Flow number (Flow Factor) per hood

Total flow no required : 2 nos. of hood (ADP) nozzle x 1 set = 2


1 nos. of exhaust duct (ADP) nozzle x 1 set = 1
1 nos. of plenum nozzle x 1 set = 1
4 flow

e) Cylinder sizing

Selected 1 no. 1.25 gallon cylinder per hood

WC/1
WET CHEMICAL