You are on page 1of 20

BY: SAB DATE: 04/2021 CLIENT: SANTA FE, NM SHEET:

CHKD: DESCRIPTION: MCC BUILDING FOOTING JOB NO: 11443A10

Overturning Calculation Based on a Given Geometry

Material properties

ρ_conc = 150 pcf Density of concrete.


σ_a = 2000 psf Allowable bearing stress of soil.
γ_dry = 53 pcf Equivalent fluid pressure for dry soil.
γ_sat = 0 pcf Equivalent fluid pressure for saturated soil.
γ_unit = 128 pcf Density of sampled soil.

Height and elevation information

Top of Structure = 7401.84 Elevation of tallest point of structure.


Top of Footing = 7384.5 Elevation of the top of the base slab.
Bottom of Footing = 7383 Elevation of the bottom of the base slab.
Top of Wall = 7401.84 Elevation of the top of foundation wall.
Grade = 7393.5 Elevation of grade or ground level.
Ground Water = 0 Elevation of ground water.

H_structure = 17.34 ft Total height of superstructure.


t_footing = 1.5 ft Thickness of the foundation slab.
H_wall = 17.3 ft Total height of the foundation wall.
H_soil = 9 ft Total depth of the soil column bearing on structure.
H_wind = 8.34 ft Total height of the wind column to load structure.

Geometry of structure/walls/base

B_foot = 7.33333 ft Width of footing


B_heel 4
B_toe 2.5
L_foot = 1 ft Length of slab or base (use 1' for unit analysis).
t_wall = 0.83333 ft Thickness of the wall.

Calculation of overturning and resisting moments

ID P e M_OT M_RES RES: Y/N LF


FOOTING = 0 0 Y 1
WALL = 0 0 Y 1
OVERBUDERN = 0 0 Y 1
WIND = 0 0 N 1
WIND PARAPET = 0 0 N 1
LATERAL SOIL = 0 0 N 1
SNOW = 0 0 Y 1 0 0
MANUAL INPUT = 0 0 N 1
0
TOTAL = 0 0 0 0
#DIV/0!
F.S. = #DIV/0! #DIV/0! Factor of safety against overturning.

W = 0 lbs Resisting weight.

Calculation of bearing pressure

x = #DIV/0! ft Distance from overturning point to equivalent force.


e = #DIV/0! ft Eccentric distance from centerline of slab.
#DIV/0!

σ_MAX = #DIV/0! psf #DIV/0! Maximum bearing pressure due to applied loads.
BY: SAB DATE: 04/2021 CLIENT: SANTA FE, NM SHEET:
CHKD: DESCRIPTION: MCC BUILDING FOOTING JOB NO: 11443A10

Overturning Calculation Based on a Given Geometry

σ_MIN = #DIV/0! psf #DIV/0! Minimum bearing pressure due to applied loads.
W 15.16666666667
L 15.16666666667
t 2

Load Type Full Tank Empty Tank


Tank Dead Load Axial (Down) 81400 21200
Slab Dead Load Axial (Down) 69008 69008
Wind Load Shear (Lateral) 3760 3760
Wind Load Axial (Uplift) 660 660
Seismic Load Shear (Lateral) 1750 460

Full Tank Empty Tank


Tank Dead Load Moment 20350 5300
Wind Load Moment 0 0
Wind Load Moment 60160 60160
Seismic Load Moment 56000 14720
Sai
Wi
R
Ie
Sac

Vi
Vc
BY: SAB DATE: 04/2021 CLIENT: GREELEY, CO SHEET:
CHKD: DESCRIPTION: METRON - Prefab Elec. Bldg. JOB NO: 10820B10

Overturning Calculation Based on a Given Geometry

Material properties

ρ_conc = 150 pcf Density of concrete.


σ_a = 1500 psf Allowable bearing stress of soil.
γ_dry = 63 pcf Equivalent fluid pressure for dry soil.
γ_sat = 94 pcf Equivalent fluid pressure for saturated soil.
γ_unit = 125 pcf Density of sampled soil.

Height and elevation information

Top of Structure = 4654 Elevation of tallest point of structure.


Top of Slab = 4632 Elevation of the top of the base slab.
Bottom of Slab = 4630.5 Elevation of the bottom of the base slab.
Top of Wall = 4640 Elevation of the top of foundation wall.
Grade = 4637 Elevation of grade or ground level.
Ground Water = 4641 Elevation of ground water.

H_structure = 14 ft Total height of superstructure.


t_slab = 1.5 ft Thickness of the foundation slab.
H_wall = 8.0 ft Total height of the foundation wall.
H_soil = 6.5 ft Total depth of the soil column bearing on structure.
H_wind = 17.00 ft Total height of the wind column to load structure.

Geometry of structure/walls/base

B_slab = 12.5833 ft Width of base slab.


B_foot = 1 ft Width of any extension beyond slab.
L_slab = 1 ft Length of slab or base (use 1' for unit analysis).
t_wall = 1.5 ft Thickness of the wall.

Calculation of overturning and resisting moments

ID P e M_OT M_RES RES: Y/N LF


SLAB = 3281 7 0 23926 Y 1
WALL 1 = 1800 2 0 3150 Y 1
WALL 2 = 1800 13 0 23100 Y 1
WT = 1300 7 0 9476 Y 1
SURCHARGE = 200 3 650 0 N 1
WIND = 680 15 6120 0 N 1
SOIL = 1986 2 4302 0 N 1

TOTAL = 11072 59651

F.S. = 5.4 OK Factor of safety against overturning.

W = 8181 lbs Resisting weight.

Calculation of bearing pressure

x = 5.94 ft Distance from overturning point to equivalent force.


e = 1.35 ft Eccentric distance from centerline of slab.
Base is in compression everywhere.
BY: SAB DATE: 04/2021 CLIENT: GREELEY, CO SHEET:
CHKD: DESCRIPTION: METRON - Prefab Elec. Bldg. JOB NO: 10820B10

Overturning Calculation Based on a Given Geometry

σ_MAX = 873 psf OK Maximum bearing pressure due to applied loads.


σ_MIN = 249 psf OK Minimum bearing pressure due to applied loads.
BY: SAB DATE: 04/2021 CLIENT: GREELEY, CO SHEET:
CHKD: DESCRIPTION: SELECTOR BASINS JOB NO: 10820B10

Overturning Calculation Based on a Given Geometry

Material properties

ρ_conc = 150 pcf Density of concrete.


σ_a = 1500 psf Allowable bearing stress of soil.
γ_dry = 63 pcf Equivalent fluid pressure for dry soil.
γ_sat = 94 pcf Equivalent fluid pressure for saturated soil.
γ_unit = 125 pcf Density of sampled soil.

Height and elevation information

Top of Structure = 4646.6 Elevation of tallest point of structure.


Top of Slab = 4624 Elevation of the top of the base slab.
Bottom of Slab = 4621 Elevation of the bottom of the base slab.
Top of Wall = 4646.6 Elevation of the top of foundation wall.
Grade = 4642 Elevation of grade or ground level.
Ground Water = 4641 Elevation of ground water.

H_structure = 0 ft Total height of superstructure.


t_slab = 3 ft Thickness of the foundation slab.
H_wall = 22.6 ft Total height of the foundation wall.
H_soil = 21.00 ft Total depth of the soil column bearing on structure.
H_wind = 4.60 ft Total height of the wind column to load structure.

Geometry of structure/walls/base

B_slab = 150.667 ft Width of base slab.


B_foot = 0 ft Width of any extension beyond slab.
L_slab = 1 ft Length of slab or base (use 1' for unit analysis).
t_wall = 2.33333 ft Thickness of the wall.

Calculation of overturning and resisting moments

ID P e M_OT M_RES RES: Y/N LF


SLAB = 67800 75 0 5107600 Y 1
WALL 1 = 7910 1.17 0 9228 Y 1
WALL 2 = 7910 150 0 1182545 Y 1
WT = 0 0 0 0 Y 1
SURCHARGE = 0 0 0 0 N 1
WIND = 0 0 0 0 N 1
SOIL = 21894 7 153261 0 N 1
OVERBURDEN 1 = 0 0 0 0 N 1
OVERBURDEN 2 = 0 0 0 0 N 1

TOTAL = 153261 6299373

F.S. = 41.1 OK Factor of safety against overturning.

W = 83620 lbs Resisting weight.


BY: SAB DATE: 04/2021 CLIENT: GREELEY, CO SHEET:
CHKD: DESCRIPTION: SELECTOR BASINS JOB NO: 10820B10

Overturning Calculation Based on a Given Geometry

Calculation of bearing pressure

x = 73.50 ft Distance from overturning point to equivalent force.


e = 1.83 ft Eccentric distance from centerline of slab.
Base is in compression everywhere.

σ_MAX = 596 psf OK Maximum bearing pressure due to applied loads.


σ_MIN = 514 psf OK Minimum bearing pressure due to applied loads.

Consider bearing pressure due to concentric dead load only.

σ_MAX_DL = 555 psf OK Maximum bearing pressure due to dead load.

Calculation of sliding resistance due to soil only.

cA = 0 Adhesion value for soil underneath slab.


δ = 24.2 deg Degree of friction

tan(δ) = 0.44942 Coefficient of friction.

R_SL = 37580.3 lbs

F.S. = 1.72 OK Factor of safety against sliding.


BY: SAB DATE: 04/2021 CLIENT: GREELEY, CO SHEET:
CHKD: DESCRIPTION: METRON - Prefab Elec. Bldg. JOB NO: 10820B10

Overturning Calculation Based on a Given Geometry

Material properties

ρ_conc = 150 pcf Density of concrete.


σ_a = 2000 psf Allowable bearing stress of soil.
γ_dry = 63 pcf Equivalent fluid pressure for dry soil.
γ_sat = 94 pcf Equivalent fluid pressure for saturated soil.
γ_unit = 125 pcf Density of sampled soil.

Height and elevation information

Top of Structure = 4646 Elevation of tallest point of structure.


Top of Slab = 4629.33 Elevation of the top of the base slab.
Bottom of Slab = 4627.83 Elevation of the bottom of the base slab.
Top of Wall = 4646 Elevation of the top of foundation wall.
Grade = 4642 Elevation of grade or ground level.
Ground Water = 4630 Elevation of ground water.

H_structure = 0 ft Total height of superstructure.


t_slab = 1.5 ft Thickness of the foundation slab.
H_wall = 16.7 ft Total height of the foundation wall.
H_soil = 14.17 ft Total depth of the soil column bearing on structure.
H_wind = 0.00 ft Total height of the wind column to load structure.

Geometry of structure/walls/base

B_slab = 11 ft Width of base slab.


B_foot = 1 ft Width of any extension beyond slab.
L_slab = 1 ft Length of slab or base (use 1' for unit analysis).
t_wall = 1 ft Thickness of the wall.

Calculation of overturning and resisting moments

ID P e M_OT M_RES RES: Y/N LF


SLAB = 2700 6 0 16200 Y 1
WALL 1 = 2501 11 0 26255 Y 1
WT = 0 0 0 0 Y 0
SURCHARGE = 200 7 0 0 N 0
WIND = 0 0 0 0 N 0
SOIL = 9437 5 0 0 N 0
OVERBURDEN 1 = 1584 11 0 17421 Y 1
OVERBURDEN 2 = 0 0 0 0 N 1
MANUAL INPUT = 14150 1 14150 0 N 1

TOTAL = 14150 59877

F.S. = 4.2 OK Factor of safety against overturning.

W = 6784 lbs Resisting weight.

Calculation of bearing pressure

x = 6.74 ft Distance from overturning point to equivalent force.


e = -0.74 ft Eccentric distance from centerline of slab.
BY: SAB DATE: 04/2021 CLIENT: GREELEY, CO SHEET:
CHKD: DESCRIPTION: METRON - Prefab Elec. Bldg. JOB NO: 10820B10

Overturning Calculation Based on a Given Geometry

Base is in compression everywhere.

σ_MAX = 344 psf OK Maximum bearing pressure due to applied loads.


σ_MIN = 700 psf OK Minimum bearing pressure due to applied loads.
BY: SAB DATE: 04/2021 CLIENT: GREELEY, CO SHEET:
CHKD: DESCRIPTION: METRON - Prefab Elec. Bldg. JOB NO: 10820B10

Overturning Calculation Based on a Given Geometry

Material properties

ρ_conc = 150 pcf Density of concrete.


σ_a = 3000 psf Allowable bearing stress of soil.
γ_dry = 72 pcf Equivalent fluid pressure for dry soil.
γ_sat = 98 pcf Equivalent fluid pressure for saturated soil.
γ_unit = 120 pcf Density of sampled soil.

Height and elevation information

Top of Structure = 4646 Elevation of tallest point of structure.


Top of Slab = 4629.33 Elevation of the top of the base slab.
Bottom of Slab = 4627.83 Elevation of the bottom of the base slab.
Top of Wall = 4646 Elevation of the top of foundation wall.
Grade = 4642 Elevation of grade or ground level.
Ground Water = 4630 Elevation of ground water.

H_structure = 0 ft Total height of superstructure.


t_slab = 2.67 ft Thickness of the foundation slab.
H_wall = 0.0 ft Total height of the foundation wall.
H_soil = 21.9 ft Total depth of the soil column bearing on structure.
H_wind = 0.00 ft Total height of the wind column to load structure.

Geometry of structure/walls/base

B_slab = 16.67 ft Width of base slab.


B_foot = 3 ft Width of any extension beyond slab.
L_slab = 1 ft Length of slab or base (use 1' for unit analysis).
t_wall = 1 ft Thickness of the wall.

Calculation of overturning and resisting moments

ID P e M_OT M_RES RES: Y/N LF


SLAB = 7878 10 0 77479 Y 1
WALL 2.67' = 4806 15 0 73700 Y 1
WALL 2' = 4101 17 0 68364 Y 1
OVERBUDERN = 7884 18 0 143252 Y 1
LIVE = 2800 7 0 19600 Y 1
SOIL = 17266 7 126042 0 N 1
DT = 2937 14 0 41118 Y 1
SNOW = 1140 14 0 15960 Y 1
MANUAL INPUT = 1 0 0 N 1

TOTAL = 126042 439472

F.S. = 3.5 OK Factor of safety against overturning.

W = 31546 lbs Resisting weight.

Calculation of bearing pressure

x = 9.94 ft Distance from overturning point to equivalent force.


e = -0.10 ft Eccentric distance from centerline of slab.
Base is in compression everywhere.

σ_MAX = 1354 psf OK Maximum bearing pressure due to applied loads.


BY: SAB DATE: 04/2021 CLIENT: GREELEY, CO SHEET:
CHKD: DESCRIPTION: METRON - Prefab Elec. Bldg. JOB NO: 10820B10

Overturning Calculation Based on a Given Geometry

σ_MIN = 1429 psf OK Minimum bearing pressure due to applied loads.


BY: SAB DATE: 04/2021 CLIENT: GREELEY, CO SHEET:
CHKD: DESCRIPTION: METRON - Prefab Elec. Bldg. JOB NO: 10820B10

Overturning Calculation Based on a Given Geometry

Material properties

ρ_conc = 150 pcf Density of concrete.


σ_a = 3000 psf Allowable bearing stress of soil.
γ_dry = 72 pcf Equivalent fluid pressure for dry soil.
γ_sat = 98 pcf Equivalent fluid pressure for saturated soil.
γ_unit = 120 pcf Density of sampled soil.

Height and elevation information

Top of Structure = 4646 Elevation of tallest point of structure.


Top of Slab = 4629.33 Elevation of the top of the base slab.
Bottom of Slab = 4627.83 Elevation of the bottom of the base slab.
Top of Wall = 4646 Elevation of the top of foundation wall.
Grade = 4642 Elevation of grade or ground level.
Ground Water = 4630 Elevation of ground water.

H_structure = 0 ft Total height of superstructure.


t_slab = 2.67 ft Thickness of the foundation slab.
H_wall = 0.0 ft Total height of the foundation wall.
H_soil = 21.9 ft Total depth of the soil column bearing on structure.
H_wind = 0.00 ft Total height of the wind column to load structure.

Geometry of structure/walls/base

B_slab = 16.67 ft Width of base slab.


B_foot = 3 ft Width of any extension beyond slab.
L_slab = 1 ft Length of slab or base (use 1' for unit analysis).
t_wall = 1 ft Thickness of the wall.

Calculation of overturning and resisting moments

ID P e M_OT M_RES RES: Y/N LF


SLAB = 7878 10 0 77479 Y 1
WALL 2.67' = 4806 15 0 73700 Y 1
WALL 2' = 4101 17 0 68364 Y 1
OVERBUDERN = 7884 18 0 143252 Y 1
LIVE = 2800 7 0 0 Y 0
SOIL = 17266 7 126042 0 N 1
DT = 2937 14 0 41118 Y 1
SNOW = 1140 14 0 0 Y 0
MANUAL INPUT = 1 0 0 N 1

TOTAL = 126042 403912

F.S. = 3.2 OK Factor of safety against overturning.

W = 31546 lbs Resisting weight.

Calculation of bearing pressure

x = 8.81 ft Distance from overturning point to equivalent force.


e = 1.03 ft Eccentric distance from centerline of slab.
Base is in compression everywhere.

σ_MAX = 1770 psf OK Maximum bearing pressure due to applied loads.


BY: SAB DATE: 04/2021 CLIENT: GREELEY, CO SHEET:
CHKD: DESCRIPTION: METRON - Prefab Elec. Bldg. JOB NO: 10820B10

Overturning Calculation Based on a Given Geometry

σ_MIN = 1013 psf OK Minimum bearing pressure due to applied loads.


BY: SAB DATE: 04/2021 CLIENT: SANTA FE, NM SHEET:
CHKD: DESCRIPTION: MCC BUILDING FOOTING JOB NO: 11443A10

Overturning Calculation Based on a Given Geometry

Material properties

ρ_conc = 150 pcf Density of concrete.


σ_a = 2000 psf Allowable bearing stress of soil.
γ_dry = 53 pcf Equivalent fluid pressure for dry soil.
γ_sat = 0 pcf Equivalent fluid pressure for saturated soil.
γ_unit = 128 pcf Density of sampled soil.

Height and elevation information

Top of Structure = 7401.84 Elevation of tallest point of structure.


Top of Footing = 7384.5 Elevation of the top of the base slab.
Bottom of Footing = 7383 Elevation of the bottom of the base slab.
Top of Wall = 7401.84 Elevation of the top of foundation wall.
Grade = 7393.5 Elevation of grade or ground level.
Ground Water = 0 Elevation of ground water.

H_structure = 17.34 ft Total height of superstructure.


t_footing = 1.5 ft Thickness of the foundation slab.
H_wall = 17.3 ft Total height of the foundation wall.
H_soil = 9 ft Total depth of the soil column bearing on structure.
H_wind = 8.34 ft Total height of the wind column to load structure.

Geometry of structure/walls/base

B_foot = 7.33333 ft Width of footing


B_heel 4
B_toe 2.5
L_foot = 1 ft Length of slab or base (use 1' for unit analysis).
t_wall = 0.83333 ft Thickness of the wall.

Calculation of overturning and resisting moments

ID P e M_OT M_RES RES: Y/N LF


FOOTING = 1650 4 0 6050 Y 1
WALL = 2168 4 0 9573 Y 1
OVERBUDERN = 2880 6 0 17520 Y 1
WIND = 170 13 2268 0 N 1
WIND PARAPET = 125 18 2197 0 N 1
LATERAL SOIL = 2922 4 10226 0 N 1
SNOW = 0 0 Y 1 4465 1488.329
MANUAL INPUT = 0 0 N 1
1010.94
TOTAL = 9915 14691 33143 4465
4.416667
F.S. = 2.3 OK Factor of safety against overturning.

W = 6698 lbs Resisting weight.

Calculation of bearing pressure

x = 2.76 ft Distance from overturning point to equivalent force.


e = 0.91 ft Eccentric distance from centerline of slab.
Base is in compression everywhere.

σ_MAX = 1594 psf OK Maximum bearing pressure due to applied loads.


BY: SAB DATE: 04/2021 CLIENT: SANTA FE, NM SHEET:
CHKD: DESCRIPTION: MCC BUILDING FOOTING JOB NO: 11443A10

Overturning Calculation Based on a Given Geometry

σ_MIN = 232 psf OK Minimum bearing pressure due to applied loads.


BY: SAB DATE: 04/2021 CLIENT: SANTA FE, NM SHEET:
CHKD: DESCRIPTION: MCC BUILDING FOOTING JOB NO: 11443A10

Overturning Calculation Based on a Given Geometry

Material properties

ρ_conc = 150 pcf Density of concrete.


σ_a = 2000 psf Allowable bearing stress of soil.
γ_dry = 53 pcf Equivalent fluid pressure for dry soil.
γ_sat = 0 pcf Equivalent fluid pressure for saturated soil.
γ_unit = 128 pcf Density of sampled soil.

Height and elevation information

Top of Structure = 7401.84 Elevation of tallest point of structure.


Top of Footing = 7384.5 Elevation of the top of the base slab.
Bottom of Footing = 7382.5 Elevation of the bottom of the base slab.
Top of Wall = 7401.84 Elevation of the top of foundation wall.
Grade = 7393.5 Elevation of grade or ground level.
Ground Water = 0 Elevation of ground water.

H_structure = 17.34 ft Total height of superstructure.


t_footing = 2 ft Thickness of the foundation slab.
H_wall = 17.3 ft Total height of the foundation wall.
H_soil = 9 ft Total depth of the soil column bearing on structure.
H_wind = 8.34 ft Total height of the wind column to load structure.

Geometry of structure/walls/base

B_foot = 6.83333 ft Width of footing


B_heel 4
B_toe 2
L_foot = 1 ft Length of slab or base (use 1' for unit analysis).
t_wall = 0.83333 ft Thickness of the wall.

Calculation of overturning and resisting moments

ID P e M_OT M_RES RES: Y/N LF


FOOTING = 2050 3 0 7004 Y 1
WALL = 2168 4 0 9573 Y 1
OVERBUDERN = 2304 6 0 13440 Y 1
WIND = 170 14 2353 0 N 1
WIND PARAPET = 125 18 2259 0 N 1
LATERAL SOIL = 3207 4 11757 0 N 1
SNOW = 0 0 Y 1 4613 1537.594
MANUAL INPUT = 0 0 N 1
1044.403
TOTAL = 10024 16370 30017 4613
4.416667
F.S. = 1.8 OK Factor of safety against overturning.

W = 6522 lbs Resisting weight.

Calculation of bearing pressure

x = 2.09 ft Distance from overturning point to equivalent force.


e = 1.32 ft Eccentric distance from centerline of slab.
Base is in tension and compression.

σ_MAX = 2078 psf FAIL Maximum bearing pressure due to applied loads.
BY: SAB DATE: 04/2021 CLIENT: SANTA FE, NM SHEET:
CHKD: DESCRIPTION: MCC BUILDING FOOTING JOB NO: 11443A10

Overturning Calculation Based on a Given Geometry

σ_MIN = 0 psf OK Minimum bearing pressure due to applied loads.


BY: SAB DATE: 04/2021 CLIENT: SANTA FE, NM SHEET:
CHKD: DESCRIPTION: MCC BUILDING FOOTING JOB NO: 11443A10

Overturning Calculation Based on a Given Geometry

Material properties

ρ_conc = 150 pcf Density of concrete.


σ_a = 2000 psf Allowable bearing stress of soil.
γ_dry = 53 pcf Equivalent fluid pressure for dry soil.
γ_sat = 0 pcf Equivalent fluid pressure for saturated soil.
γ_unit = 128 pcf Density of sampled soil.

Height and elevation information

Top of Structure = 7401.84 Elevation of tallest point of structure.


Top of Footing = 7384.5 Elevation of the top of the base slab.
Bottom of Footing = 7382.5 Elevation of the bottom of the base slab.
Top of Wall = 7401.84 Elevation of the top of foundation wall.
Grade = 7393.5 Elevation of grade or ground level.
Ground Water = 0 Elevation of ground water.

H_structure = 17.34 ft Total height of superstructure.


t_footing = 2 ft Thickness of the foundation slab.
H_wall = 17.3 ft Total height of the foundation wall.
H_soil = 9 ft Total depth of the soil column bearing on structure.
H_wind = 8.34 ft Total height of the wind column to load structure.

Geometry of structure/walls/base

B_foot = 2.83333 ft Width of footing


B_heel 1
B_toe 1
L_foot = 1 ft Length of slab or base (use 1' for unit analysis).
t_wall = 0.83333 ft Thickness of the wall.

Calculation of overturning and resisting moments

ID P e M_OT M_RES RES: Y/N LF


FOOTING = 850 1 0 1204 Y 1
WALL = 2168 1 0 3071 Y 1
OVERBUDERN = 1152 2 0 2688 Y 1
WIND = 170 14 2353 0 N 1
WIND PARAPET = 125 18 2259 0 N 1
LATERAL SOIL = 3207 4 11757 0 N 1
SNOW = 0 0 Y 1 4613 1537.594
MANUAL INPUT = 0 0 N 1
1044.403
TOTAL = 7672 16370 6963 4613
4.416667
F.S. = 0.4 FAIL - F.S. < 1.5 Factor of safety against overturning.

W = 4170 lbs Resisting weight.

Calculation of bearing pressure

x = -2.26 ft Distance from overturning point to equivalent force.


e = 3.67 ft Eccentric distance from centerline of slab.
Base is in tension and compression.

σ_MAX = -1232 psf OK Maximum bearing pressure due to applied loads.


BY: SAB DATE: 04/2021 CLIENT: SANTA FE, NM SHEET:
CHKD: DESCRIPTION: MCC BUILDING FOOTING JOB NO: 11443A10

Overturning Calculation Based on a Given Geometry

σ_MIN = 0 psf OK Minimum bearing pressure due to applied loads.

You might also like