Professional Documents
Culture Documents
Page
1 of 11
MASONRY
0 16/05/01 A. KHALIK SHIREEN EL TAKI ABDUL AZIZ AL AMERI ISSUED FOR IMPLEMENTATION
Sections changed in last revision are identified by a vertical line in the right margin
DGS-2020-001/FH
Rev.
Page
2 of 11
CONTENTS
1. GENERAL .............................................................................................................................................. 3
1.1 INTRODUCTION........................................................................................................................................ 3
1.2 P URPOSE.............................................................................................................................................. 3
1.3 DEFINITIONS ........................................................................................................................................... 3
2. CODES AND STANDARDS...................................................................................................................... 3
2.1 B RITISH STANDARDS (BS)........................................................................................................................ 4
2.2 NATIONAL CONCRETE M ASONRY ASSOCIATION (NCMA)................................ ................................ ................. 4
2.3 A MERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) ................................ ................................ ............. 4
2.4 UNIFORM B UILDING CODE (UBC-94)............................................................................................................ 4
3. REFERENCE DOCUMENTS................................ ................................ ................................ ..................... 5
8. SUBCONTRACTORS/SUBVENDORS ....................................................................................................... 5
DGS-2020-001/FH
Rev.
Page
3 of 11
1. GENERAL
1.1 Introduction
This Design General Specification defines the technical requirements for the furnishing and
installation of all masonry and accessories.
1.2 Purpose
This Design General Specification is to provide criteria for the furnishing of all materials, equipment
and installation of all masonry and accessories as outlined on the DRAWINGS, in the contract and
this specification.
1.3 Definitions
Where used in this specification, the following terms shall have the meanings indicated below unless
otherwise clearly indicated by context of their use.
1.3.2 CONCESSION REQUEST - A deviation requested by the CONTRACTOR or VENDOR, usually after
receiving the contract documents or purchase order. Often, it refers to an authorization to use,
repair, recondition, reclaim, or release materials, components or equipment already in progress or
completely manufactured but which does not meet or comply with the COMPANY requirements. A
CONCESSION REQUEST is subject to COMPANY approval.
1.3.3 CONTRACTOR - The party which carries out all or part of the design engineering, procurement
,construction and commissioning or management of the project
1.3.5 PROJECT MANAGEMENT TEAM (PMT) - The COMPANY authorized party responsible for the
overall day -to-day execution of the Project. The PMT is to serve as the liaison between the
COMPANY and the CONTRACTOR(S) on the PROJECT.
DGS-2020-001/FH
Rev.
Page
4 of 11
BS 6073 Part 2, Precast Concrete Masonry Units: Method for Specifying Precast
Concrete Masonry Units
DGS-2020-001/FH
Rev.
Page
5 of 11
3. REFERENCE DOCUMENTS
The following reference documents, to the extent specified herein, form a part of this specification.
When an edition date is not indicated for a document, the latest edition in force at the time of
contract award shall apply.
DGS 2020-004 Specification for Thermal and Moisture Protection
4. DOCUMENT PRECEDENCE
It shall be the CONTRACTOR’S responsibility to be, or to become, knowledgeable of the
requirements of the referenced Codes and Standards.
The CONTRACTOR shall notify the PMT of any apparent conflict between this specification, the
related data sheets, the Codes and Standards and any other Design General Specifications noted
herein. Resolution and/or interpretation precedence shall be obtained from the PMT in writing before
proceeding with the design / manufacture.
In case of conflict, most stringent criteria shall apply.
Requirements as specified in MANUFACTURER’S instructions shall be followed where applicable.
7. DOCUMENTATION
The construction drawings shall be issued by CONTRACTOR (or a SUBCONTRACTOR) and
“approved for CONSTRUCTION” before the work commence.
The procedures for tittle block, issuing of the documentation shall be strictly followed.
8. SUBCONTRACTORS/SUBVENDORS
(NOT APPLICABLE).
9. HANDLING
DGS-2020-001/FH
Rev.
Page
6 of 11
10. MATERIALS
The CONTRACTOR shall submit an “Affidavit of Compliance” before beginning construction. The
Affidavit shall confirm that all material meets the requirements of this specification.
11.1 General
11.2 Materials
11.3 Execution
DGS-2020-001/FH
Rev.
Page
7 of 11
Where joints reinforcements are necessary, lime shall be replaced by a mortar plasticiser meeting
the requirements of BS 4887.
All mortar shall contain the recommended amount of integral water-repellent admixture for mortar for
water repellency and to assure proper bond strength. The required amount of admixture per bag of
cement shall be per MANUFACTURER’s instructions. Mortar preparation and composition shall
comply with ASTM C207, Type S.
See Unit Masonry Section 13.0 herein for a list of acceptable admixture manufacturers.
All exterior block walls shall be laid with full mortar coverage on horizontal and vertical face shells,
and mortar shall contain the integral mortar admix as per label instructions. All joints shall be well
tooled. No raked joints shall be permitted. Attention shall be given to NCMA TEK 53 for joint and
crack control.
Grout for all unit masonry work shall attain a minimum compressive strength of 13.8 N/mm2 shall
conform to ASTM C476, and be proportioned by volume as follows:
♦ 1 part Portland cement
♦ 1/10 part hydrated lime
♦ 2-1/4 to 3 parts sand
♦ 1 to 2 parts coarse aggregate
11.3.3 Grouting
Place reinforcement before grouting. Place before or after laying masonry units, as required by job
conditions.
Prior to grouting, inspect and clean grout spaces. Remove dust, dirt, mortar droppings, loose
pieces of masonry and other foreign materials from grout spaces. After final cleaning and
inspection, close cleanout holes and brace closures to resist grout pressures.
Do not place grout until entire height of masonry to be grouted has attained sufficient strength to
resist displacement of masonry units and breaking of mortar bond. Install shores and bracing, if
required, before starting grouting operations.
Limit grout pours to sections that can be completed in one working day with not more than one hour
interruption of pouring operation. Place grout in lifts that do not exceed 1500 mm. Allow not less
than 30 minutes, nor more than one hour between lifts of a given pour. Rod or vibrate each grout lift
during pouring operation. When more than one pour is required to complete a given section of
DGS-2020-001/FH
Rev.
Page
8 of 11
12.1 General
12.1.3 Manufacturers
Local manufacturers (precast vendors) in UAE shall be approved by Contractor and Company for the
proposed application.
12.2 Materials
DGS-2020-001/FH
Rev.
Page
9 of 11
13.1 General
DGS-2020-001/FH
Rev.
Page
10 of 11
13.2.2 Manufacturers
Acceptable manufacturers or suppliers shall be approved by CONTRACTOR and COMPANY.
13.3 Execution
13.3.1 Installation
All walls shall be built true to dimensions, plumb, and square. All work shall be laid to line, in level
courses and all individual face units shall be kept “in plane.”
All unit masonry shall be laid using running bond. Joints shall run straight and plumb. Block cores
shall be reinforced as indicated on the DRAWINGS.
All masonry units shall be laid in a full bed of mortar with full head joints. All such mortar shall
contain the recommended amount of integral water-repellent admixture mortar admix for water
repellency and to assure proper bond strength.
All required cutting of masonry units shall be done with power equipment which will produce true
edges free of chipping and undamaged surfaces.
Where fresh masonry joins masonry that is partially or totally set, the exposed surface of the set
masonry shall be cleaned and wet lightly so as to obtain the best possible bond with the new work.
All loose masonry and mortar shall be removed. If it is necessary to “stop off” a run of masonry, this
shall be done by raking back one-half unit length of each course. No toothing will be permitted.
Joints in all exposed masonry work shall be firmly and neatly tooled, when mortar is thumbprint
hard, to a slightly concave profile, unless indicated otherwise. All concealed joints shall be cut off
flush and surplus mortar shall be brushed off as work progresses.
DGS-2020-001/FH
Rev.
Page
11 of 11
b. The maximum height which is to be built in one day is 1.5 M. In the case of walls built using
retarder mortars, the maximum height which is to be built in one day shall be 1.0 M.
c. Walls built using retarder mortar shall be adequately cured for a period of not less than 24 hours
before any further work on the wall can take place.
d. The mortar beds and vertical joints shall be 10 MM nominal thickness and shall not exceed
15 MM.
Other trades shall be consulted and provisions made to permit installation of their work in a manner
which will avoid cutting and patching as the work progresses.
Tapping of units shall not be permitted after mortar has taken its initial set. Irregular work shall be
replaced with fresh mortar.
Masonry wall intersections shall be bonded with joint reinforcing, except at control joints.
Masonry joints shown to be caulked shall be raked back 12 mm. Sides of caulking recess shall be
free of mortar.
All loose lintels (steel, precast concrete, etc.) shall be installed by the SUBCONTRACTOR.
All bond beams shall be built in as indicated on the DRAWINGS. They shall be reinforced and filled
as detailed.
All masonry reinforcement, control joints, and flashings shall be installed as specified in Masonry
Accessories section.
13.3.2 Protection
All masonry work shall be properly protected from staining, the elements, and from damage at all
times. Top of all walls shall be covered at end of each work day.
13.3.4 Cleaning Up
Upon completion of the work all surplus materials, debris, tools, and equipment shall be removed
from the site.
DGS-2020-001/FH