Proposal for improved

voltage source converter


model – an update
Deepak Ramasubramanian, EPRI
dramasubramanian@epri.com
Evangelos Farantatos, EPRI
Anish Gaikwad, EPRI
Wenzong Wang, Texas A&M University
WECC REMTF
May 10th 2018
Salt Lake City, UT

© 2018 Electric Power Research Institute, Inc. All rights reserved.


DISCLAIMERS
 This model is neither expected to nor can it accurately represent
the complete all encompassing behavior of a converter.

 It is not expected that this model will replace existing second


generation generic models. It is however intended for use as a
screening model in an additional step before performing a
PSCAD type of simulation.

2
© 2018 Electric Power Research Institute, Inc. All rights reserved.
Questions and comments from March 2018 WebEx
meeting
 Is the inner current control loop required?
– Can only the PLL model be represented in detail and represent the inner
current control loop by single time constant.
 Should the PLL interface be added to the current source
REGC_A model?
 Are limits required in the PLL model for frequency calculation?
– Depending on the vendor, this may or may not be a feature in the model.
 Addition of rate limits on the current commands.
– And LVPL? (may not be required if VDL blocks are present?)
 A switch to allow bypass of PLL and inner current control loop.
3
© 2018 Electric Power Research Institute, Inc. All rights reserved.
Draft block diagram
1 N
1 + 𝑠𝑇𝑖 s0 𝑉𝑡
𝑉𝑡
Y 𝑟𝑒 𝑥𝑒
𝐼𝑞𝑐𝑚𝑑 + 𝐾𝐼𝑖
N
𝑖𝑞′

𝐸𝑑 = 𝑉𝑡𝑑0 + 𝑖𝑝 𝑟𝑒 − 𝑖𝑞′ 𝑥𝑒
𝐸𝑞 = 𝑉𝑡𝑞0 + 𝑖𝑞 𝑟𝑒 + 𝑖𝑝′ 𝑥𝑒
𝐾𝐼𝑝 +
𝑠 Y 1 Iterate +
- s0 𝑗 ∑ 𝐸෨
1 + 𝑠𝑇𝑒 with
𝑖𝑞 s2 network +
1 solution
to enforce
1 + 𝑠𝑇𝑖 1 current
𝑑𝐼𝑝𝑚𝑎𝑥 s1
N
𝑖𝑝′ 1 + 𝑠𝑇𝑒 limit
𝐼𝑝𝑐𝑚𝑑 + 𝐾𝐼𝑖 s3
∑ 𝐾𝐼𝑝 + Y
𝑠
- s1 N

𝑖𝑝 Y
𝑖𝑝 𝐼𝑟𝑒𝑎𝑙 𝑦
Y tan−1 𝑥
N
𝑖𝑞 𝐼𝑖𝑚𝑎𝑔 y x

Δ𝜔𝑚𝑎𝑥 𝑉𝑡𝑑 𝑉𝑡𝑟𝑒𝑎𝑙


Y – Use PLL and PI Loop
N – Do not use 1 Δ𝜔 𝐾𝑃𝐿𝐿𝑖
𝐾𝑃𝐿𝐿𝑝 +
Note: The LVPL block is not represented 𝜃 𝑠 s4 𝑠 𝑉𝑡𝑞 𝑉𝑡𝑖𝑚𝑎𝑔
s5
as REEC_A (with VDL blocks) was used Δ𝜔𝑚𝑖𝑛
to generate current commands
4
© 2018 Electric Power Research Institute, Inc. All rights reserved.
Three versions of the model created
 Version 1:
– Inner current control PI loop,
– Representation of the PLL,
– Voltage source interface,
– Iteration with network solution.
 Version 2:
– Inner current control PI loop, Replaced by first order time constant
– Representation of the PLL,
– Voltage source interface,
– Iteration with network solution.
 Version 3: Same as Version 1 but with inclusion of ramp rate limit
5
© 2018 Electric Power Research Institute, Inc. All rights reserved.
Preliminary validation results – requirement for inner current control
loop
Version 1 – with PLL and inner current control loop • PLL control gains:
Version 2 – with PLL without inner current control loop
• Kp = 20.0
• Ki = 2400.0
• Inner current control gains:
• Version 1:
• Kp = 5.0
• Ki = 70.0
• Version 2:
• T = 0.07s
• 7 cycle fault solid fault (X =
0.005pu) applied in both
cases
• Current commands provided
by REEC_A
• SCR ≈ 2.48

6
© 2018 Electric Power Research Institute, Inc. All rights reserved.
PLL frequency limits?
Positive sequence simulation 3 phase point on wave simulation

6.81 cycle fault 5.52 cycle fault

6.80 cycle fault


5.46 cycle fault

• Open PLL limits in both positive sequence and 3 phase simulation • ‘Pole-slip’ effect occurs in 3 phase simulation under certain circumstances
• Relative angle in positive sequence is against swing generator • Positive sequence angle always stabilizes at a larger value
• PLL Gain: Kp = 20.0; Ki = 2400.0
7
© 2018 Electric Power Research Institute, Inc. All rights reserved.
6.81 cycle fault
5.52 cycle fault
6.80 cycle fault

5.46 cycle fault

Limitation of the positive sequence model in that the angle would probably always settle at the higher value

8
© 2018 Electric Power Research Institute, Inc. All rights reserved.
Version 3 of model – ramp rate limit
10000 pu/s
0.1 pu/s

• PLL Gain: Kp = 20.0; Ki = 2400.0 • PLL Limits: ± 12 Hz


• Presently ramp rate only on Ipcmd

9
© 2018 Electric Power Research Institute, Inc. All rights reserved.
Can such a behavior be represented by the model?

• Actual measurement data of a


bulk power system connected
PV plant presented by First
Solar.
• No large scale disturbance in the
immediate vicinity of the plant.
• Most probably a small
signal stability issue.
• Occurs only for certain levels of
active power output.

Source: “Deploying Utility-Scale PV Power Plants in Weak Grids”, First Solar, 2017 PES General Meeting, Chicago, IL, July 2017
10
© 2018 Electric Power Research Institute, Inc. All rights reserved.
System setup

R=
X=

 Source at Bus 1 represented by classical machine with large MVA and


H.
 Source at Bus 20004 represented by REEC_A and:
– Version 2 of REGC_B with KpPLL = 20.0; KiPLL = 1500.0; T = 0.07
– Version 3 of REGC_B with KpPLL = 20.0; KiPLL = 1500.0; KpICC = 5.0; KiICC =
70.0; Ramp rate = 100.0 pu/s
– Elliptical change in Pgen
 Two values of X to represent different system strengths:
– X = 0.01 pu
– X = 0.505 pu
11
© 2018 Electric Power Research Institute, Inc. All rights reserved.
Low/high grid strength – X = 0.505/0.01 pu
X = 0.505 pu Version 3 ~5.35 Hz Oscillation

Version 2

X = 0.01 pu

12
© 2018 Electric Power Research Institute, Inc. All rights reserved.
Discussion

 The positive sequence model with the added features is able


to replicate the trend observed in PSCAD simulations.
 It is however not yet a one-to-one comparison both from a
performance and control gain point of view.
 Blocking of PLL for low voltage, ramp rate on reactive
current, freezing of states have not been implemented in the
models.
 Is this model worth pursuing?

13
© 2018 Electric Power Research Institute, Inc. All rights reserved.
Together…Shaping the Future of Electricity

14