Professional Documents
Culture Documents
Criteria For Selection of Resistors in Trip Circuit Supervision Relays PDF
Criteria For Selection of Resistors in Trip Circuit Supervision Relays PDF
Supervision Relays:
In Trip Circuit Supervision Relays, the Selection of Resistors should met the Following Criteria,
Requirement:
1) During PreClose , two coils should be picked up . while Post Close , only one coil should be
Picked.
2) According to TCS Relay (Areva) ,Maximum Trip circuit Supervision current should not Exceed
20mA.
3) Minimum Pickup Voltage For TCS Relay coils(RL2 , RL3) = 16.80 V (From SAT Values)
Suppose,.
i) if we Select very less Resistance it will exceed the maximum Trip Circuit
supervision Current
ii) if we select very High resistance, During preclose Condition, Relay coil will
not pick up and thus Supervision is not possible.
Results:
Conclusion:
Selection of the Resistor Values should be in such a way that it should balance the above two
criterias. Thus 4000 ohms resistor is a better value.
Example:
Default condition:
We are selecting 4000 ohms resistor across each coil of TCS relay,
=110/15645
= 7mA
In this Condition,
= 25 Volts
ii) voltage developed across EXt . Resist for RL2 coil = 7mA * 4000 ohms
= 28 Volts
= 24.85 Volts
iv) voltage developed across EXt . Resist for RL3 coil = 7mA * 4000 ohms
= 28 Volts
V) voltage developed across the Breaker Trip Coil is = 7mA * 525 ohms
= 3.675 Volts
2) During Post close condition ,
=110/8075
= 13.62mA
In this situation,
= 48.62 Volts
ii) voltage developed across EXt . Resist for RL2 coil = 13.62 mA * 4000 ohms
= 54.48 Volts
iii) voltage developed across the Breaker Trip Coil is = 13.62mA * 525 ohms
= 7.15 Volts
Condition 1:
Suppose, instead of 4000 ohms , if We select 8000 ohms resistor across each coil of TCS relay:
=110/23645
= 4.65 mA
In this Condition,
= 16.60 Volts
ii) voltage developed across EXt . Resist for RL2 coil = 4.65mA * 8000 ohms
= 37.2 Volts
= 16.5 Volts
iv) voltage developed across EXt . Resist for RL3 coil = 4.65mA * 8000 ohms
= 37.2 Volts
V) voltage developed across the Breaker Trip Coil is = 4.65 mA * 525 ohms
= 2.4 Volts
=110/12075
= 9.1mA
In this Condition,
= 32.52 Volts
ii) voltage developed across EXt . Resist for RL2 coil = 9.1 mA * 8000 ohms
= 72.8 Volts
V) voltage developed across the Breaker Trip Coil is = 9.1mA * 525 ohms
= 4.7 Volts
In this situation
During Preclose Condition the developed voltage across the Relay coil is not sufficient to pick up the
relay.
since the Minimum required volage to pick up the relay is 16.8 Volts
Whereas, Developed voltage across the coil during preclose condition is only 16.5V
Condition 2:
Suppose , if We select 500 ohms resistor across each coil of TCS relay:
=110/8645
= 12.72 mA
In this Condition,
= 45.41 Volts
ii) voltage developed across EXt . Resist for RL2 coil = 12.72mA * 500 ohms
= 6.36Volts
= 45.15 Volts
iv) voltage developed across EXt . Resist for RL3 coil = 12.72mA * 500 ohms
= 6.36 Volts
V) voltage developed across the Breaker Trip Coil is = 12.72 mA * 525 ohms
= 6.678 Volts
2) During Postclose condition ,
=110/4575
= 24 mA
In this situation,
= 85.68 Volts
ii) voltage developed across EXt . Resist for RL2 coil = 24 mA * 500 ohms
= 12 Volts
iii) voltage developed across the Breaker Trip Coil is = 24mA * 525 ohms
= 12.6 Volts
According to TCS Relay (Areva), Maximum Trip circuit Supervision current should be less than 20mA.
Whereas, During Post Close Condition we are exceeding the Maximum Limit.