The document is a magnetic particle inspection report for welds on carbon steel plates at an FMC dockyard in Bangladesh. It summarizes that 8 welds by 4 welders on 8mm thick plates were tested using wet magnetic particle inspection and found to have no apparent defects, meeting ASME standards. The inspection was performed by an ASNT Level II inspector and witnessed by another party.
The document is a magnetic particle inspection report for welds on carbon steel plates at an FMC dockyard in Bangladesh. It summarizes that 8 welds by 4 welders on 8mm thick plates were tested using wet magnetic particle inspection and found to have no apparent defects, meeting ASME standards. The inspection was performed by an ASNT Level II inspector and witnessed by another party.
The document is a magnetic particle inspection report for welds on carbon steel plates at an FMC dockyard in Bangladesh. It summarizes that 8 welds by 4 welders on 8mm thick plates were tested using wet magnetic particle inspection and found to have no apparent defects, meeting ASME standards. The inspection was performed by an ASNT Level II inspector and witnessed by another party.
Name of Project: FMC- DL-WPT-2021-01 Report No. :-MT-001 client : FMC- DOCKYARD LTD. tnspection Date : 04-08-2021. Location : FMC- Dockyard, West Domdondi,Boalkhali, Ctg. Test Procedure : MT-001/2021 Surface Condition : Clean Material : Carbon Steel Machine Type : Yoke Type Acceptable crietria : ASME-Sec-lX Machine Made : Magnaflux lndia Classification of Test : VisualWet Surface Condition : Clean ChemicalType : Wet & Spray 10lb Lift Check Result : Accepted Chemical Colour : White Contrast & Black lnk
sl. Welding Test
Welder Name Welder lD Thickness Evaluation Comments No. Position Specimen 1 Mohiuddin 3 2G Plate 08 mm NAD Accept 2 Mohiuddin 3 3G Plate 08 mm NAD Accept
3 Nur-Amin 1 2G Plate 08 mm NAD Accept
4 Nur-Amin 1 3G Plate 08 mm NAD Accept
5 Akter 4 2G Plate 08 mm NAD Accept
6 Akter 4 3G Plate 08 mm NAD Accept
7 Borhan 2 2G Plate 08 mm NAD Accept
8 Borhan 2 3G Plate 08 mm NAD Accept
INSPECTOR : LEVEL il (ASNr) Witness By: Approved By
Md. Zabed AIi Et 'r Name Approved By ature: &i I Signature Signature :
Dated 04-08- \\. Date Date :
Note: NAD : No Apparent Defect
+ Thisreportshall notbereproducedexceptinfull ,withoutthewrittenapproval of ideal NDTService&Trainingcentre.