Vitodens 300
Type WB3A, 6.6 to 35.0 kW
Gas fired wall mounted condensing boiler
natural gas and LPG version
VITODENS 300
Safety instructions
! Important information
This symbol warns against the
risk of material losses and
standards.
& Work on gas equipment must only & Shut down the system.
living space.
! Important information
Repairing components which
fulfil a safety function can com-
mann.
Index
Coding
Code 1........................................................................................................ 40
Code 2........................................................................................................ 43
Resetting the coding to the delivered condition ........................................... 63
Service scans
Service level summary ................................................................................ 64
Temperatures, boiler coding card and brief scans ....................................... 65
Checking outputs (relay test) ...................................................................... 69
Scanning operating conditions and sensors ................................................ 71
Troubleshooting
Calling up fault code history ........................................................................ 74
Calling up current fault codes ...................................................................... 74
Checking and acknowledging faults ............................................................ 76
Repairs ...................................................................................................... 85
Function description
Constant temperature control units ............................................................. 96
Weather-compensated control units ............................................................ 98
Extensions for external connections (accessory) ......................................... 100
Control functions ........................................................................................ 104
Designs
Connection and wiring diagrams – internal connections............................... 109
Connection and wiring diagrams – external connections .............................. 111
Certificates
Declaration of conformity ............................................................................ 127
Manufacturer's certificate according to the 1st BImSchV [Germany]............. 128
5692 537 GB
Commissioning steps
Inspection steps
Maintenance steps Page
! ! !
• 1. Filling the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
• 2. Venting the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
• 3. Venting the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• 4. Filling the siphon with water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• 5. Checking the electrical mains connection
• 6. Language selection (if required) - only for the
weather-compensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• • 7. Set the time and date (if required) - only for
weather-compensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
• • 8. Checking the gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
• 9. Gas type conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
• • • 10. Function sequence and possible faults . . . . . . . . . . . . . . . . . . . . . . . 12
• • • 11. Checking static and supply pressure ........................... 14
• • • 12. Checking the CO 2 settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
• 13. Setting the max. output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
• • • 14. Checking all connections on the primary and DHW
side for leaks
• • • 15. Checking the burner (recording values on
page 120 of commissioning report)
• 16. Checking the balanced flue system for soundness
(annular gap check) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
• • 17. Removing the burner and checking the burner
gasket (replace gasket every two years) . . . . . . . . . . . . . . . . . . . . . . 20
• • 18. Checking the burner gauze assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
• • 19. Checking and adjusting the ignition and ionisation
electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5692 537 GB
3.
! Important information
Unsuitable fill water
increases the level of
deposits and corrosion and
may lead to boiler damage.
& Thoroughly flush the
ble quality.
& Soften fill water harder
Note
The diverter valve actuator will be
in the central position, and the sys-
tem will be completely filled, if the
control unit has not been switched
ON before the system was filled.
4. If the control unit had already been 5. Close the boiler fill & drain valve
switched ON before filling began: A.
Start the control unit and in code 1,
set coding address 2F:2. 6. Set coding address 2F:0.
The diverter valve will then be in its
central position.
Note
To call up code 1 and for setting the
coding address, see page 40.
Whilst filling is in progress, the dis-
play shows bF (constant tempera-
ture control units) or "Filling"
(weather-compensated control
units).
5692 537 GB
1. Close the gas shut-off valve and 2. Activate the venting program via
start the control unit. coding address 2F:1.
Note
To call up code 1 and for setting the
coding address, see page 40.
For function and sequence of the
venting program, see page 105.
Whilst venting is in progress, the
display shows EL (constant tem-
perature control units) or "Venting"
(weather-compensated control
units).
1. Press c. 2. Press d.
5692 537 GB
10
Set the time and date (if required) - only for weather-compen-
sated control units
Note
During commissioning, or after prolonged time out of use, it may be necessary
to set the time and date.
1. Enquire about the gas type and 3. If these details do not match the
Wobbe index (Wo) from your local fuel provided, the burner must be
mains gas or LPG supplier. converted according to the details
provided by the mains gas or the
Note LPG supplier.
In its delivered condition, Vito-
dens 300 is set up for natural gas See separate conversion kit
E. installation instructions.
The boiler can be operated in the
Wobbe index range 12.0 to After conversion to
16.1 kWh/m 3 (43.2 to 58.0 MJ/m 3 ). & Natural gas LL
11
4. Set the gas type via coding 5. Record the gas type in the service
address 1E at the control unit. report on page 120.
Note
To call up code 1 and for setting the
coding address, see page 40.
Yes
12
Yes
Yes
Yes
Yes
Yes
pressure
13
Danger
Higher CO emissions can lead to poisoning.
Measure the CO value before and after any work on gas equipment to
prevent any health hazards and to ensure the perfect operational condi-
tion of the system.
5. Start up boiler.
Note
During commissioning, the boiler
can enter a fault state because of
airlocks in the gas pipe. After
approx. 5 seconds, press E to
reset the burner.
5692 537 GB
14
Note
Use suitable test equipment with a
resolution of at least 0.1 mbar to
measure the supply pressure.
8. Danger
Gas escaping from the test
nipple leads to a risk of
explosion.
Check for gas leaks.
5692 537 GB
15
Vitodens 300 is factory-set for natural gas E, and can be converted to natural
gas LL or LPG P using a conversion kit.
During commissioning or maintenance, check the CO 2 level at the boiler adap-
tor.
Note
The MatriX burner for Vitodens 300 is preset for the entire gas group. Therefore,
the burner requires no further setting or adjustment.
Compare the actual CO 2 value with the above CO 2 value ranges for the indivi-
dual gas groups (check the gas group with your mains gas or LPG supplier).
If the actual CO 2 value deviates by more than 1 % for natural gas or 0.5 % for
LPG, proceed as follows:
& Check whether the correct gas restrictor has been installed.
& Check the balanced flue system for soundness, see page 19.
5692 537 GB
16
Weather-compensated control
units:
& Press both keys 9 and d simul-
"Basic load".
2.
Weather-compensated control
units:
& With a/b in the display, select
5692 537 GB
"Full load".
17
Note
The max. output can be limited for heating operation. You can limit the output
via the modulation range.
2. Press both K and F simulta- 5. Record the settings for max. output
neously until 100 flashes on the on the additional type plate
display, (equals 100 % of the rated included with the technical docu-
output) and A appears. On mentation. Affix the type plate next
weather-compensated control to the original type plate on top of
units, the display additionally the boiler.
shows "Max. output".
Note
3. With a/b select the required The output can also be limited for
value in % of rated output as max. DHW loading. For this, change coding
output. address 6F in code 2.
5692 537 GB
18
19
1. Switch OFF the control unit ON/ 5. Release four nuts H and remove
OFF switch and the mains electri- the burner.
cal supply.
20
21
1. Check the electrodes for wear and 3. Check all clearances. If the gaps
contamination. are not as specified or the electro-
des are damaged, replace and
2. Clean the electrodes with a small align the electrodes together with
brush (not with a wire brush) or new gaskets A. Tighten the elec-
emery paper. trode fixing screws with 2 Nm.
! Important information
Wire mesh
do not damage.
5692 537 GB
22
! Important information
Scratches on parts which
are in contact with flue
gases, can lead to corrosion.
Only use plastic brushes and
NOT wire brushes.
Apply a solvent-/potassium-free
cleaning agent if residues remain:
& Remove soot deposits with alka-
discolouration (yellow-brown)
with slightly acidic, chloride-free
cleaning agents based on phos-
phoric acid (e.g. Antox 75 E).
& Thoroughly flush with water.
Note
Fauch 600 and Antox 75 E are sup-
plied by:
Hebro Chemie GmbH
Rostocker Straße 40
D 41199 Mönchengladbach
c: Intec Bassersdorf AG
Grindelstrasse 12
Postfach
CH-8303 Bassersdorf
23
Danger
Escaping gas leads to a risk
of explosion.
Check all fittings for sound-
ness.
24
Note
Residual water may escape during
dismantling.
Danger
Escaping gas leads to a risk of
explosion.
Check gas equipment for
soundness.
5692 537 GB
25
2.
Weather-compensated control
units:
& Press K and d simultaneously
"Full load".
Note
The minimum ionisation current
should be at least 4 µA as soon as
the flame is established (approx. 2 -
3 seconds after opening the gas
A Adaptor line (available as acces- train).
sory)
3. If the ionisation current is < 4 µA:
& Check the electrode gap, see
page 22.
& Check the control unit power sup-
ply.
26
Note
The control unit must be matched to the system equipment. Various system
components are automatically recognised by the control unit, and codes are
automatically set.
In the following system designs, DHW loading is illustrated with a separate
DHW cylinder. The designs also apply to systems where DHW is heated by an
integral instantaneous water heater. In that case, the cylinder temperature sen-
sor % is factory fitted to the boiler.
& For selection of an appropriate design, see the following diagrams.
System design 1
27
System design 2
Note
The volume flow of the heating circuit without mixer must be at least 30 %
greater than the volume flow of the heating circuit with mixer.
28
System design 3
29
System design 4
or
Operation with LPG 1E:1
30
System design 5
With/without DHW heating with 1 heating circuit with mixer M2 (with exten-
sion kit), 1 heating circuit with mixer (Vitotronic 050) and low loss header
or
Operation with LPG 1E:1
31
System design 6
With 1 heating circuit without mixer A1, solar panels and Vitocell-W 100
DHW cylinder (type CVB) installed adjacent to the boiler
*1 High
limit safety cut-out required only for:
DHW volume smaller than 30 litres/m 2 absorber surface when using Vitosol 100.
DHW volume smaller than 100 litres/m 2 absorber surface when using Vitosol 200 or 300.
32
Installation instructions
LON communication module
Note
Data transfer via the LON system can take 2 to 3 minutes.
Adjust the user number via coding In a LON system, the same number
address 77 (see below). cannot be allocated twice.
Only possible, if all users are connected, and the control unit is encoded as fault
manager (code 79:1).
33
The communication with the system devices connected to the fault manager is
tested with a user check.
Preconditions:
& The control unit must be encoded as fault manager (code 79:1).
& The LON user number must be encoded in all control units (see page 33).
& The fault manager user list must be up to date (see page 33).
5692 537 GB
*1 In each heating system, only one Vitotronic may be encoded as fault manager.
34
is no communication between
both devices. Check LON con-
nection.
The heating curves illustrate the rela- Settings in the delivered condition:
tionship between the outside tem- & Slope = 1.4
35
36
37
38
The system installer must hand the operating instructions to the system user
and instruct them in the operation of the system.
The red fault indicator flashes when the limits set via coding address 21 and 23
have been reached. As regards the operating interface display:
& For constant temperature control units, the hours run (subject to setting) or
Note
Set code 24:1 and then code 24:0, if maintenance is implemented before main-
tenance is displayed; the set maintenance parameters for hours run and interval
are then reset to 0.
39
Code 1
Call up code 1
5692 537 GB
40
Code 1 (cont.)
Summary
Codes
41
Code 1 (cont.)
Note
Allocate each number
only once.
Summer econ. A1
A5:5 * 1With heating circuit A5:0 Without heating circuit
pump logic function pump logic function
Summer econ. M2
A5:5 * 1With heating circuit A5:0 Without heating circuit
pump logic function pump logic function
Min. flow temp. A1
C5:20 Electronic limit of the C5:1 Minimum limit adjustable
minimum flow tempera- to from 1 to 127 °C
ture: 20 °C C5:127
Min. flow temp. M2
C5:20 Electronic limit of the C5:1 Minimum limit adjustable
minimum flow tempera- to from 1 to 127 °C
ture: 20 °C C5:127
Max. flow temp. A1
C6:75 * 1Electronic maximum C6:1 Maximum limit adjustable
flow temperature limit at to from 1 to 127 °C
75 °C C6:127
Max. flow. temp. M2
C6:75 * 1Electronic maximum C6:1 Maximum limit adjustable
flow temperature limit at to from 1 to 127 °C
75 °C C6:127
5692 537 GB
Code 1 (cont.)
Code 2
Calling up code 2
Code 2 (cont.)
Overall summary
The coding addresses are grouped in accordance with the following function
ranges. The respective function range is displayed.
Scroll through the ranges in the following sequence with a or b.
5692 537 GB
44
Code 2 (cont.)
Codes
100 hours)
45
Code 2 (cont.)
Code 2 (cont.)
47
Code 2 (cont.)
funct.
20 ON OFF Control funct. Control funct.
48
Code 2 (cont.)
49
Code 2 (cont.)
Code 2 (cont.)
Code 2 (cont.)
Note
Allocate each number
only once.
Code 2 (cont.)
Code 2 (cont.)
Code 2 (cont.)
Note
When selecting a value
below 1 °C there will be
a risk of pipes outside
the thermal insulation
envelope of the house
freezing-up. The
standby mode, in parti-
cular, should be
observed, e.g. during
holidays.
2 1 °C 3 °C
to to
*1 Only for weather-compensated control units.
55
Code 2 (cont.)
Note
When selecting a value
below 1 °C there will be a
risk of pipes outside the
thermal insulation envel-
ope of the house freez-
ing-up. The standby
mode, in particular,
should be observed, e.g.
during holidays.
2 AT > RTSet + 4 K
*1 Only for weather-compensated control units.
56
Code 2 (cont.)
Code 2 (cont.)
control mode
or
& after cylinder loading
(for 20 min.)
or
& if there is a risk of frost.
Code 2 (cont.)
*1 Only
for weather-compensated control units.
*2 Changethe coding for the heating circuit without mixer A1 or for mixer circuit M2, if the
remote control unit affects that heating circuit.
59
Code 2 (cont.)
Code 2 (cont.)
Note
Observe the screed dry-
ing supplier's instruc-
tions.
Code 2 (cont.)
achieved
& Operating condition
*4 Inheating program rw, the party mode ends automatically when changing over to
operation with standard room temperature.
*5 Only for constant temperature control units.
62
Code 2 (cont.)
64
3. Press d.
The following values can be scanned, subject to the actual equipment level:
to
Brief scan 8
Display screen
Brief
scan
65
Display screen
Brief
scan
66
Display screen
Brief
scan
67
Display screen
Brief scan
68
Display screen
Brief scan
d Variable Software
speed version
pump Variable
0: excl. speed pump
1: Wilo
2: Grund-
fos
Subject to the actual equipment level, the following relay outputs can be con-
trolled:
Display Description
Basic load Burner modulation lower output
Full load Burner modulation upper output
Heating valve Diverter valve set to heating mode
Valve central pos. Changeover valve in central position (fill)
DHW valve Diverter valve set to DHW mode
Int. pump ON Int. pump/output 20 ON
Close mixer Mixer extension
Open mixer Mixer extension
Heating circ. pump M2 ON Mixer extension
Output int. Internal extension
Heating circ. pump A1 ON Ext. extension
Cylinder loading pump ON Ext. extension
5692 537 GB
69
Display Description
Solar pump ON Vitosolic
Subject to the actual equipment level, the following relay outputs can be con-
trolled:
Display Description
1 Burner modulation lower output
2 Burner modulation upper output
3 Diverter valve set to heating mode
4 Valve in central position
5 Valve set to DHW mode
6 Internal pump/output 20 ON
10 Output sK internal extension
11 Heating circuit pump A1 external extension
12 Cylinder loading pump external extension
13 DHW circulation pump external extension
14 Central fault external extension 5692 537 GB
70
*1 Reset
hours run and burner starts after maintenance has been completed. You can reset
the hours run to 0 by pressing e.
71
1. Press c. 3. Press c.
*1 Displayed in °F if the relevant code has been selected and with the fourth display digit.
72
*1 Displayedin °F if the relevant code has been selected and with the fourth display digit.
*2 Reset
hours run and burner starts after maintenance has been completed. You can reset
the hours run to 0 by pressing e.
73
The most recent 10 faults are saved and may be called up.
3. Press d.
74
3. Acknowledge fault.
3. Acknowledge fault.
75
weather-compensated control
units)
C Fault number
D Fault code
76
Note
The fault can be acknowledged
with d. The fault message in the dis-
play will be hidden, but the red fault
indicator U continues to flash. A new
fault message will be displayed if an
Constant temperature control units acknowledged fault is not removed by
the following morning.
header)
77
78
circuit
79
80
extension 2E settings
81
sor.
Press E.
82
83
84
Repairs
85
Repairs (cont.)
5692 537 GB
86
Repairs (cont.)
87
Repairs (cont.)
Danger
The boiler temperature sen-
sor is immersed in the heat-
ing water (risk of scalding).
Drain the boiler before repla-
cing the sensor.
88
Repairs (cont.)
Note
Water can leak out when replacing
the outlet sensor. Close the cold
water shut-off valve. Drain DHW
pipe and plate heat exchanger
(secondary side).
The flue gas temperature sensor locks out the boiler when the permissible flue
gas temperature is exceeded. The lockout can be reset no sooner than after
20 minutes by pressing the reset button E.
Note
The equipment will also be locked out again for 20 minutes if the mains power
supply is switched OFF.
5692 537 GB
89
Repairs (cont.)
90
Repairs (cont.)
1. Shut off and drain the boiler on 7. Release screws F and pull plate
the primary and the secondary heat exchanger G forward out of
side. the assembly.
4. Remove the retaining clip and 8. Check the secondary side for
siphon C. scaling and, if necessary, clean or
replace the plate heat exchanger.
5. Remove gas supply pipe D.
9. Check the primary side for con-
6. Remove thermal insulation E. tamination and, if necessary,
5692 537 GB
91
Repairs (cont.)
iter A.
& Check the continuity of the tempera-
Check the sensor in case of fault messages concerning the differential pressure
sensor:
& Correct installation
92
Repairs (cont.)
93
Repairs (cont.)
94
Repairs (cont.)
Note
The flow temperature sensor must
now sense a higher temperature. If
the temperature falls, either the
motor is turning in the wrong direc-
tion or the mixer set is incorrectly
fitted.
Vitotronic 050 is connected with the control unit via the LON system. To test the
5692 537 GB
connection, implement a user check on the boiler control unit (see page 34).
95
96
97
Heating mode
The control unit determines a set boi- DHW loading with a gas fired boiler
ler water temperature subject to out- The DHW heating will be activated if
side temperature or room temperature the cylinder temperature falls 2.5 K
(if a room temperature-dependent below the set cylinder temperature.
remote control is connected) and the The burner and the cylinder loading
slope/level of the heating curve. The pump are switched ON. In the deliv-
determined set boiler water tempera- ered condition, the set boiler water
ture is then transferred to the burner temperature lies 20 K above the set
control unit. From the set and actual cylinder temperature. If the actual
boiler water temperatures, the burner cylinder temperature rises 2.5 K
control unit calculates the modulation above the set cylinder temperature,
level and controls the burner accord- the burner will be switched OFF and
ingly. The burner control unit limits the the cylinder loading pump run-on time
boiler water temperature: through the will be activated.
control thermostat to 74 °C, and
through the electronic temperature Supplementary DHW heating
limiter to 82 °C. The temperature lim- The backup heating function is acti-
iter in the safety chain locks out the vated, if a switching period is selected
burner control unit at a boiler water for the fourth time phase. This period
temperature of 100 °C. must lie outside the switching times
for standard DHW heating to enable
DHW loading with gas fired combi- the control unit to recognise the sig-
nation boilers nal. The set temperature value for
If the flow switch recognises that backup heating is adjustable in coding
DHW is drawn off (> 3 l/min), the bur- address 58.
ner and circulation pump are switched
ON, and the three-way valve changes
over to DHW loading. The burner
modulates to reach the DHW outlet
temperature and is limited on the boi-
ler side by the temperature limiter
(82 ºC). With activated comfort opera-
tion, the plate heat exchanger will be
held to a standby temperature of
42 °C ON and 46 °C OFF.
5692 537 GB
98
99
Internal extension H1
The internal extension is integrated & Central fault message (code 53:0)
into the control unit housing. As alter- & Cylinder loading pump (code 53:3)
native, the following functions can be & DHW circulation pump (code 53:1)
connected to relay output sK. The & Heating circuit pump for heating cir-
100
Internal extension H2
The internal extension is integrated & Central fault message (code 53:0)
into the control unit housing. As alter- & Cylinder loading pump (code 53:3)
native, the following functions can be & DHW circulation pump (code 53:1)
connected to relay output sK. The & Heating circuit pump for heating cir-
101
External extension H1
102
External extension H2
103
Control functions
104
External blocking
External demand
The function "External demand" is In coding address 9b, you can select
connected via input aVD of the exter- the minimum set boiler water tem-
nal extension. perature in case of external demand.
In coding address 34 you can select
the influence the signal "Ext. demand"
should have on the connected circula-
tion pumps.
Venting program
Filling program
105
Screed function
Temperature profile: Diagram 1 (DIN 4725 part 4) code F1:1 5692 537 GB
106
107
5692 537 GB
108
109
5692 537 GB
110
111
5692 537 GB
112
Parts lists
095 Locking clips (10 pieces) 098 Cable harness 100/35/34 (aux-
110 Outside temperature sensor iliary earth)
099 Step motor connecting cable
Wearing parts 100 Cable harness ionisation/KM
050 Burner gasket BUS (internal)
053 Ignition electrode with gasket 101 Internal ionisation lead
054 Ionisation electrode with gasket 104 Adaptor - ionisation current test
062 Burner maintenance set cable
063 Set of small burner parts 150 Installation instructions
065 Insulation ring 151 Service instructions
153 Operating instructions for con-
Parts not shown stant temperature operation
016 Special grease 154 Operating instructions for
017 Heat conducting paste weather-compensated operation
039 Fixing parts (set) 156 Touch-up paint stick, Vitowhite
097 Cable harness X8/X9 157 Touch-up spray paint, Vitowhite
A Type plate
5692 537 GB
114
115
5692 537 GB
116
117
5692 537 GB
118
119
Commissioning/service reports
Date:
By:
Static pressure mbar max. 57.5 mbar
Oxygen content O 2
& at lower rated output % by
vol.
& at upper rated output % by
vol.
120
121
Oxygen content O 2
& at lower rated output % by
vol.
& at upper rated output % by
vol.
122
123
Oxygen content O 2
& at lower rated output % by
vol.
& at upper rated output % by
vol.
124
125
Specification
*1 The supply values are only for reference (e.g. in the gas contract application) or to esti-
5692 537 GB
mate the supplementary volumetric settings. Because of factory settings, the gas pres-
sure must not be altered from these values. Reference: 15 °C, 1013 mbar.
*2 Max. limit to EnEV.
126
Declaration of conformity
We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, declare as sole
responsible body, that the product
Vitodens 300
127
We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, confirm that the fol-
lowing product meets the NO x limits specified by 1st BImSchV Paragraph 7 (2)
[Germany]:
Vitodens 300
5692 537 GB
128
Keyword index
A F
Adjusting the room temperature . . . . 37 Fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Fault messages . . . . . . . . . . . . . . . . . . . . . 74, 76
B Filling function . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Boiler temperature sensor . . . . . . . . . . . . . 87 Filling the system . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Brief scans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Finding faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Burner gauze assembly . . . . . . . . . . . . . . . . 21 Flow limiter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Burner installation . . . . . . . . . . . . . . . . . . . . . . . . 23 Flue gas temperature sensor . . . . . . . . . 90
Burner removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Function descriptions . . . . . . . . . . . . . . . . . . . 96
Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
C
Checking the differential pressure G
sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Gas combination valve . . . . . . . . . . . . . . . . . 14
Cleaning agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Gas supply pressure . . . . . . . . . . . . . . . . . . . . 15
Cleaning the combustion chamber . 23 Gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Code 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 H
Code 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Coding during commissioning . . . . . . . 27 Heating curve slope . . . . . . . . . . . . . . . . . . . . . 36
Comfort sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Heating surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Condensate drain . . . . . . . . . . . . . . . . . . . . . . . . . 24 I
Cylinder temperature sensor . . . . . . . . . 87 Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Ignition electrodes . . . . . . . . . . . . . . . . . . . . . . . . 22
D Ionisation current . . . . . . . . . . . . . . . . . . . . . . . . . 26
Declaration of conformity . . . . . . . . . . . . 127 Ionisation electrode . . . . . . . . . . . . . . . . . . . . . . 22
Deleting codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
L
E Language selection . . . . . . . . . . . . . . . . . . . . . . 10
Extension kit for heating circuit with Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
mixer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Level heating curve . . . . . . . . . . . . . . . . . . . . . . 36
Extension LON communication module . . . . . . . . . 33
& external . . . . . . . . . . . . . . . . . . . . . . . . . . 102, 103 LON system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
& internal . . . . . . . . . . . . . . . . . . . . . . . . . . . 100, 101 LON user check . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
External blocking . . . . . . . . . . . . . . . . . . . . . . . 105
External demand . . . . . . . . . . . . . . . . . . . . . . . . 105 M
Manufacturer's Declaration . . . . . . . . . 128
O
Operating mode changeover . . . . . . . 104
5692 537 GB
129
P T
Parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Temperature limiter
Plate heat exchanger . . . . . . . . . . . . . . . . . . . 91 & Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Product characteristics . . . . . . . . . . . . . . . 126 Temperature scans . . . . . . . . . . . . . . . . . . . . . . . 65
Testing functions . . . . . . . . . . . . . . . . . . . . . . . . . . 69
R Testing outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Relay test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Resetting the coding to the delivered V
condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Venting program . . . . . . . . . . . . . . . . . . . . . . . . 105
S Vitotronic 050 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Safety chain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Scanning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 W
Scanning operating conditions . . . . . . 71 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . 109
Scanning sensors . . . . . . . . . . . . . . . . . . . . . . . . 71
Screed drying . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Screed function . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Service level summary . . . . . . . . . . . . . . . . . 64
Service report . . . . . . . . . . . . . 120, 122, 124
Setting the date . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Setting the output . . . . . . . . . . . . . . . . . . . . . . . . . 18
Setting the time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Setting up LON user numbers . . . . . . . 33
Siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10, 24
Slope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Soundness test, balanced flue
system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Static pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Supply pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
System designs . . . . . . . . . . . . . . . . . . . . . 27, 41
System pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 7