You are on page 1of 28

Service instructions VIESMANN

for contractors

Vitoplex 100
Type PV1, 150 to 620 kW
Oil/gas boiler

For applicability, see the last page

VITOPLEX 100

5692 701 GB 10/2014 Please keep safe.


Safety instructions
Safety instructions

Please follow these safety instructions closely to If you smell gas


prevent accidents and material losses.
Danger
Safety instructions explained Escaping gas can lead to explosions which may
result in serious injury.
Danger ■ Do not smoke. Prevent naked flames and
This symbol warns against the risk of injury. sparks. Do not switch lights or electrical appli-
ances on or off.

! Please note
This symbol warns against the risk of material
■ Close the gas shut-off valve.
■ Open windows and doors.
losses and environmental pollution. ■ Evacuate any people from the danger zone.
■ Notify your gas or electricity supplier and your
Note local heating contractor from outside the build-
Details identified by the word "Note" contain additional ing.
information. ■ Shut off the electricity supply to the building
from a safe place (outside the building).
Target group
If you smell flue gas
These instructions are exclusively intended for quali-
fied contractors. Danger
■ Work on gas installations must only be carried out by Flue gas can lead to life threatening poisoning.
a registered gas fitter. ■ Shut down the heating system.
■ Work on electrical equipment must only be carried ■ Ventilate the installation site.
out by a qualified electrician. ■ Close all doors in the living space.
■ The system must be commissioned by the system
installer or a qualified person authorised by the Flue systems and combustion air
installer.
Ensure that flue systems are clear and cannot be
Regulations sealed, for instance due to accumulation of conden-
sate or other causes. Ensure a sufficient supply of
Observe the following when working on this system: combustion air.
■ Statutory regulations regarding the prevention of Instruct system users that subsequent modifications to
accidents the building characteristics are not permissible (e.g.
■ Statutory regulations regarding environmental pro- cable/pipework routing, cladding or partitions).
tection
■ The Code of Practice of relevant trade associations Danger
■ All current safety regulations as defined by DIN, EN, Leaking or blocked flue systems, or an insuffi-
DVGW, TRGI, TRF, VDE and all locally applicable cient supply of combustion air can cause life
standards, threatening poisoning from carbon monoxide in
Gas Safety (Installation & Use) Regulations the the flue gas.
appropriate Building Regulationeither the Building Ensure the flue system is in proper working
regulations, theBuilding Regulation (Scotland), Build- order. Apertures for supplying combustion air
ing Regulations (Northern Ireland), the Water Fittings must be non-closable.
Regulation or Water Bylaws in Scotland, the current
I.E.E. Wiring Regulations. Extractors

Operating appliances that extract air to the outside


(cooker hoods, extractors, air conditioning units, etc.)
can create negative pressure. If the boiler is operated
at the same time, this can lead to reverse flow of the
flue gas.

Danger
The simultaneous operation of the boiler and
appliances that extract air to the outside can
result in life threatening poisoning due to
reverse flow of the flue gas.
Fit an interlock circuit or take suitable steps to
5692 701 GB

ensure a sufficient supply of combustion air.

2
Safety instructions
Safety instructions (cont.)

Working on the system

■ Where gas is used as the fuel, close the main gas


shut-off valve and safeguard it against unintentional
reopening.
■ Isolate the system from the power supply (e.g. by
removing the separate fuse or by means of a mains
isolator) and check that it is no longer 'live'.
■ Safeguard the system against reconnection.

Danger
Hot surfaces can cause burns.
■ Before maintenance or service work, switch
OFF the appliance and let it cool down.
■ Never touch hot surfaces on the boiler, burner,
flue system or pipework.

! Please note
Electronic assemblies can be damaged by elec-
trostatic discharge.
Before beginning work, touch earthed objects,
such as heating or water pipes, to discharge
static loads.

Repair work

! Please note
Repairing components that fulfil a safety func-
tion can compromise the safe operation of the
system.
Faulty components must be replaced with origi-
nal Viessmann spare parts.

Auxiliary components, spare and wearing parts

! Please note
Spare and wearing parts that have not been tes-
ted together with the system can compromise its
function. Installing non-authorised components
and making non-approved modifications or con-
versions can compromise safety and may inva-
lidate the warranty.
For replacements, use only original spare parts
supplied or approved by Viessmann.
5692 701 GB

3
Index
Index

1. Product information Symbols ................................................................................................. 5


Intended use .......................................................................................... 5

2. Commissioning, inspec- Steps - commissioning, inspection and maintenance ............................ 6


tion, maintenance

3. Parts lists Ordering parts ........................................................................................ 14


Parts ...................................................................................................... 16
Parts ...................................................................................................... 18

4. Water quality Water quality requirements .................................................................... 20


■Prevention of damage due to scaling ................................................. 20
■Prevention of damage due to corrosion on the water side ................. 21
Using antifreeze in boilers ..................................................................... 21

5. Commissioning/service .................................................................................................................. 23
reports

6. Specification .................................................................................................................. 24

7. Certificates Declaration of conformity ....................................................................... 25

8. Keyword index .................................................................................................................. 26

5692 701 GB

4
Product information
Symbols

Symbol Meaning The work sequences for commissioning, inspection


and maintenance are summarised in the chapter
Reference to other document containing
"Commissioning, inspection and maintenance "and are
further information
marked as follows:

Information
Additional information, not safety relevant
Symbol Meaning
Step:
1. Work sequences required during commis-
The numbering corresponds to the se-
quence of work. sioning
Not required during commissioning

Work sequences required during inspec-


tion
Not required during inspection

Work sequences required during mainte-


nance
Not required during maintenance

Intended use

The appliance is only intended to be installed and


operated in sealed unvented heating systems that
comply with EN 12828, with due attention paid to the
associated installation, service and operating instruc-
tions as well as the details in the datasheet.
It is only designed for the heating up of heating water.

Commercial or industrial usage for a purpose other


than the heating up of heating water shall be deemed
inappropriate.

Intended use presupposes that a fixed installation in


conjunction with permissible components designed for
this purpose has been carried out.
Every other use will be deemed to be inappropriate.
Any resulting losses are excluded from the manufac-
turer's liability.

Any usage beyond this must be approved by the man-


ufacturer for the individual case.

Intended use also includes the adherence to mainte-


nance and inspection intervals.
5692 701 GB

5
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance

Commissioning steps
Inspection steps
Maintenance steps Page

• • • 1. Commissioning the system............................................................................................... 7


• • 2. Shutting down the system................................................................................................. 7
• • 3. Closing the Vitoair draught stabiliser (if installed)......................................................... 7
• • 4. Opening the boiler door and cleaning cover................................................................... 8
• 5. Cleaning the turbulators, heating surface, flue outlet and flue pipe............................. 8
• • • 6. Checking all gaskets and packing cords on the flue gas side
• • • 7. Checking the thermal insulation components on the boiler door
• 8. Inserting turbulators.......................................................................................................... 9
• • 9. Securing the boiler door and cleaning cover.................................................................. 9
• • • 10. Checking connections and sensor well on the heating water side for tightness
• • • 11. Checking the function of the safety equipment.............................................................. 10
• • • 12. Checking the expansion vessel and system pressure................................................... 10
• • • 13. Checking the firm seating of electrical plug connections and cable grommets
• • • 14. Checking the thermal insulation
• • 15. Checking the water quality................................................................................................ 11
• • 16. Cleaning the sight glass in the boiler door...................................................................... 12
• • • 17. Checking the mixer for ease of operation and tightness............................................... 12
• • • 18. Checking the function of the return temperature raising facility (if installed)
• • • 19. Checking the installation room ventilation
• • • 20. Checking the flue pipe for tightness
• • • 21. Checking the Vitoair draught stabiliser (if installed)...................................................... 12
• • 22. Adjusting the burner.......................................................................................................... 12
• 23. Instructing the system user.............................................................................................. 13
• 24. Operating and service documents................................................................................... 13 5692 701 GB

6
Commissioning, inspection, maintenance
Commissioning the system

Operating and service instructions for the control 11. The dew point range must be cleared as quickly
unit and the burner as possible. To do so, prevent any heat supply to
the consumers when heating the system from
01. Check that the turbulators are fully inserted into cold. This also applies when restarting after main-
the hot gas flues (see page 9); open the boiler tenance and cleaning work.
door for this.

02. Check that the installation room supply air vent is ! Please note
During boiler heat-up, unpleasant fumes
open. and odours can result from outgassing from
the thermal insulation, the thermal block and
03. Fill the heating system with water and vent the the paint.
system. Vent the room during commissioning.
Permissible operating pressure: 5 bar (0.5 MPa)
12. Once the flow temperature has been reached,

! Please note
Scaling and boiler damage may result if the
successively switch on the heat consumers.
Switch the burner over to automatic mode.
system is not operated with fully softened
heating water.
Operate boilers only with softened water. ! Please note
When testing the flue gas for CO, internal
Observe the instructions in chapter "Water gases being expelled from the thermal block
quality requirements". can result in higher values.
Continue to operate the boiler until a decline
04. Enter the amount of fill water and water hardness can be clearly recognised.
into the table in chapter "Checking the water qual-
ity". 13. Check all gaskets and plugs, and retighten if nec-
essary.
05. Check the system pressure.
14. Check the boiler door and cleaning cover after
06. Check the oil level or the gas supply pressure. approx. 50 hours run and retighten all screws.

07. Open the flue gas damper (if installed). Danger


Opening the connections on the heating water
08. Check that the cleaning aperture on the flue outlet side whilst the boiler is under pressure can
is closed. result in injuries.
First depressurise the boiler.
09. Open the shut-off valves in the oil or gas line. Only drain the boiler with a suction pump when
the air vent valve is open.
10. Switch ON the mains isolator, the switch for the
heating circuit pump and the burner ON/OFF
switch, in that order. Observe the burner manufac-
turer’s operating instructions.

Shutting down the system

Danger
Only open the connections on the heating water
side after the boiler has been depressurised.
Only drain the boiler with a suction pump when
the air vent valve is open.

Closing the Vitoair draught stabiliser (if installed)

1. Start the burner. 2. When pre-purge is active, switch off the system; the
control disc is then closed.
5692 701 GB

7
Commissioning, inspection, maintenance
Opening the boiler door and cleaning cover

Note
On gas burners, disconnect the gas supply pipe.

4x

Fig. 1

Cleaning the turbulators, heating surface, flue outlet and flue pipe

1. Remove turbulators A without applying force.

2. Clean flues B and combustion chamber C with


the brush.
Remove combustion residues with a vacuum
cleaner.

A BC
Fig. 2

3. Remove combustion residues from the flue and the


flue outlet through the cleaning aperture in flue out-
let D using a vacuum cleaner.

Fig. 3
5692 701 GB

8
Commissioning, inspection, maintenance
Checking all gaskets and packing cords on the flue gas side

Checking the thermal insulation components on the boiler door

Inserting turbulators

! Please note
Burner adjustments and specific system condi-
tions can cause the turbulators to move forward,
which may result in them being burnt. This can
also lead to damage to the thermal insulation on
the boiler door.
Before insertion, the turbulators must be slightly
bent (see steps).

A B 1. Push turbulators A approx. ¼ of their length into


hot gas flues B.

2. Bend turbulators approx. 10 to 15°.

3. Push the turbulators into the hot gas flues as far as


they will go. When doing this, check the pre-stress-
10-15° ing.

Note
Ensure that turbulators cannot easily be pulled out
Fig. 4 of the hot gas flues.

Securing the boiler door and cleaning cover

Note Danger
On gas burners, mount the gas supply pipe. Escaping gas leads to a risk of explosion.
Check all gas connections for tightness.

A
4x

Fig. 5
5692 701 GB

9
Commissioning, inspection, maintenance
Securing the boiler door and cleaning cover (cont.)

Tighten screws A crosswise (torque 25 Nm).

Danger
Leaks can result in a risk of poisoning through
escaping gas.
Check gaskets carefully.

Checking connections and sensor well on the heating water side for tight-
ness

Checking the function of the safety equipment

Check safety valves, water level and pressure limiter in


accordance with manufacturer's details.

Checking the expansion vessel and system pressure

Expansion vessel manufacturer's documentation Note


Carry out this test on a cold system.

Expansion vessel

1. Drain the system until the pressure gauge indicates 2. If the pre-charge pressure of the expansion vessel
"0" or close the cap valve on the expansion vessel is lower than the static system pressure, top up with
and reduce the pressure in the expansion vessel. nitrogen until the pre-charge pressure is 0.1 to
0.2 bar (0.01 to 0.02 MPa) higher.
Note The static pressure corresponds to the static head.
The pre-charge pressure of the expansion vessel
(p0) is made up of the static system pressure (pSt) 3. Top up with softened water*1 until the charge pres-
(= static head) and a supplement (p0 = pSt + supple- sure of the cooled system is 0.1 to 0.2 bar (0.01 to
ment). 0.02 MPa) higher than the pre-charge pressure of
The supplement depends on the high limit safety the expansion vessel.
cut-out setting. The following applies for the respec- Permiss. operating pressure: 5 bar (0.5 MPa)
tive high limit safety cut-out settings
■ 100 °C: 0.2 bar (0.02 MPa)
■ 110 °C: 0.7 bar (0.07 MPa).

Pump controlled pressure maintaining systems

! Please note
Pressure fluctuations may cause damage to the
Boiler out-
put
kW up to
300
up to
500
up to
1000
boiler or to other system components.
Expansion litre 50 80 140
In heating systems with automatic pressure
vessel
maintaining systems, and in particular pump-
controlled systems with integral deaeration, we
recommend the installation of an expansion ves-
sel for each boiler as individual boiler protection.
This reduces the frequency and level of pres-
sure fluctuations. This contributes considerably
to improved operational reliability and a longer
service life of the system components.
5692 701 GB

*1 For water quality requirements, see page 20.


10
Commissioning, inspection, maintenance
Checking the expansion vessel and system… (cont.)

! Please note
The ingress of oxygen can result in system dam-
Carry out all checks in accordance with the manufac-
turer's instructions. Limit pressure fluctuations to the
age as a consequence of oxygen corrosion. lowest possible differential. Cyclical pressure fluctua-
Only use pump controlled pressure maintaining tions and more significant pressure differentials point
systems that are sealed against corrosion. The towards a system fault. Immediately remedy such
pressure maintaining systems must be protected faults or other heating system components may be
against oxygen ingress into the heating water. damaged.
Pump controlled pressure maintaining systems
with atmospheric deaeration through cyclical
pressure release bring about central post-venti-
lation of the heating system. They do not pro-
vide oxygen removal in the sense of corrosion
protection as described in Directive VDI 2035
Part 2.

Checking the firm seating of electrical plug connections and cable grom-
mets

Checking the thermal insulation

Checking the water quality

Observe the instructions in chapter "Water quality Enter the amount of top-up water and the total hard-
requirements". ness of the feed and boiler water into the table.

Meter reading Fill and top-up water Total water volume Total hardness pH value Date
Feedwater Boiler water
m3 m3 m3 °dH °dH
5692 701 GB

11
Commissioning, inspection, maintenance
Checking the water quality (cont.)

The total hardness of the feed and top-up water must The pH value should be between 9 and 10.5.
not exceed 0.11 °dH (total value of alkaline earths
≤ 0.02 mol/m3).

Cleaning the sight glass in the boiler door

Fig. 6

Check the gaskets and hose connection for tightness.

Checking the mixer for ease of operation and tightness

1. Remove the motorised lever from the mixer handle. 3. Check the mixer for tightness. Replace the O-ring
gaskets if the mixer is leaking.

2. Check the mixer for ease of operation. 4. Snap the motorised lever into place.

Checking the function of the return temperature raising facility (if


installed)

Checking the installation room ventilation

Checking the flue pipe for tightness

Checking the Vitoair draught stabiliser (if installed)

Release the latch on the control disc. The control disc must swing freely during burner oper-
ation.

Adjusting the burner

Burner service instructions or separate docu- Adjust the maximum oil or gas throughput of the
mentation by the burner manufacturer burner to the rated boiler heating output.
5692 701 GB

12
Commissioning, inspection, maintenance
Adjusting the burner (cont.)

Rated heating Pressure drop on the hot gas Safeguard the boiler return temperature (minimum
output side temperature) of 65 °C.
kW Pa mbar Set the minimum heating output for the base load
stage according to the conditions of the flue system.
150 60 0.6 Note that the flue system must be suitable for the low
200 120 1.2 flue gas temperatures that may occur.
250 130 1.3
310 230 2.3 In the event of frequent cycling in standby mode and
for partial loads below 40 %, we recommend the fol-
400 250 2.5 lowing:
410 250 2.5 ■ Insulate the flue gas collector
500 230 2.3 ■ Install a motorised flue gas damper
■ Set the minimum boiler runtime to 10 min
620 310 3.1

This extends the service life and reduces running


The minimum boiler water temperature for oil and gas
costs.
operation is 75 °C.

Instructing the system user

The installer should instruct the user in the operation of


the system.

Operating and service documents

1. Complete and detach the customer registration


card:
■ Hand system users their section for safekeeping.
■ Retain the heating contractor's section.

2. File all parts lists, operating and service instructions


in the folder and hand this over to the system user.
The installation instructions are no longer required
after the installation is complete and therefore do
not need to be retained.
5692 701 GB

13
Parts lists
Ordering parts

The following details are required when ordering parts:


■ Serial no. (see type plate)
■ Position number of the part (from this parts list)

Pos. Part not shown


300 Installation instructions
301 Service instructions
302 Thermal insulation, small parts
303 Touch-up spray paint, Vitosilver
304 Touch-up paint stick, Vitosilver
305 Flame tube gasket
Components

5692 701 GB

14
Parts lists
Ordering parts

Components
5692 701 GB

15
Parts lists
Parts

206 211 205

210

013
200
009

010
Components

011
002 001

007

005
019
008

021
006
004

020

008 022

Fig. 7

B Boiler control unit, see parts list in the service


instructions of the boiler control unit
5692 701 GB

16
Parts lists
Parts (cont.)

Pos. Part
001 Boiler door
002 Studs
003 Sight glass set, comprising: pos. 004 to 008
004 Hose
005 Sight glass closure
006 Sight glass with pos. 007
007 Seal ring
008 Hose nozzle
009 Gasket Ø 18 mm
010 Thermal insulation block
011 Thermal insulation mat
013 Gasket 20 x 15 mm
019 Cleaning brush (wearing part)
020 Brush handle (accessory)

Components
021 Extension piece (accessory)
022 Turbulator extractor (accessory)
200 Front panel, top
205 Top panel, right
206 Top panel, left
210 Control unit fascia
211 Edge protector
5692 701 GB

17
Parts lists
Parts

204 203 018

016
015 208 201 017

015

202

014
Components

209

207
C

212 204

Fig. 8

A Type plate, optionally left or right


C Burner cable, see parts list in the service instruc-
tions of the boiler control unit
5692 701 GB

18
Parts lists
Parts (cont.)

Pos. Part
014 Turbulator
015 Gasket
016 Cleaning cover
017 Gasket 10 x 10 mm
018 Sensor well
201 Back panel, top
202 Back panel, bottom
203 Side panel, back left
204 Side panel, front left and back right
207 Thermal insulation jacket
208 Thermal insulation mat, back
209 Vitoplex 100 logo
212 Side panel, front right with pos. 209

Components
Information on pos. 014
Rated heating output kW 150 200 250 310 400 410 500 620
Number 20 22 26 26 30 30 40 45
5692 701 GB

19
Water quality
Water quality requirements

Note
Observing the following requirements is necessary to
safeguard your warranty rights.
The warranty excludes damage due to corrosion and
scaling.

Prevention of damage due to scaling

Prevent excessive scale build-up (calcium carbonate)


on the heating surfaces. For heating systems with
operating temperatures up to 100 °C, Directive
VDI 2035 Part 1 "Prevention of damage in water heat-
ing installations - Scale formation in domestic hot
water supply installations and water heating installa-
tions" applies together with the following standard val-
ues. See also the explanations in the original text of
the Directive.

Total heating output Total alkaline earths Total hardness


kW mol/m3 °dH
> 50 to ≤ 200 ≤ 2.0 ≤ 11.2
> 200 to ≤ 600 ≤ 1.5 ≤ 8.4
> 600 < 0.02 < 0.11

The standard values assume the following: Operating information:


Appendix

■ The total volume of fill and top-up water will not ■ During expansion or repair work, only drain the nec-
exceed three times the water content of the heating essary pipework sections.
system during its service life. ■ Check, clean and activate filters, dirt traps and other
■ The specific system volume is less than 20 l/kW blow-down or separating facilities in the heating
heating output. In multi boiler systems, apply the out- water circuit more frequently after commissioning or
put of the smallest boiler. in case of new installations, later on subject to the
■ All measures to prevent corrosion on the water side water treatment applied (e.g. water softening).
in accordance with Directive VDI 2035 Part 2 have ■ No further steps are required during commissioning
been implemented. if you fill the heating system with fully softened
water.
Soften the fill and top-up water in heating systems If the heating system is not filled with fully soft-
operating under the following conditions: ened water, but with water that meets the require-
■ The total of alkaline earths in the fill and top-up water ments in the above table, also observe the follow-
exceeds the standard value. ing during commissioning:
■ Higher fill and top-up water volumes are expected. ■ Commission the system step by step, starting with
■ The specific system volume is greater than 20 l/kW the lowest boiler output and a high heating water
heating output. In multi boiler systems, apply the out- flow rate. This prevents localised concentration of
put of the smallest boiler. limescale deposits on the boiler heating surfaces.
■ In multi boiler systems, start all boilers simultane-
■ In systems > 50 kW, install a water meter to capture ously to prevent the entire limescale deposit settling
the amount of fill and top-up water. Enter the volume in the heat exchanger of just one boiler.
of fill water and the water hardness into the boiler ■ Where water treatment is required, treat even the
maintenance checklists. first fill of the heating system prior to commissioning.
■ For systems with a specific system volume in excess This also applies to any subsequent filling, e.g. when
of 20 l/kW heating output (in multi boiler systems adding top-up water or after a repair, or for any sys-
apply the output of the smallest boiler), apply the tem expansion.
requirements of the next higher category of total out-
put (in accordance with the table). In the case of seri- The build-up of limescale deposits on the heating sur-
ous deviations (> 50 l/kW) soften down to a total of faces will be minimised if these instructions are
alkaline earths ≤ 0.02 mol/m3. observed.
5692 701 GB

20
Water quality
Water quality requirements (cont.)

If limescale deposits have formed because of a failure It is essential that the faulty operating parameters are
to observe the requirements of Directive VDI 2035 the corrected to prevent renewed formation of excessive
service life of the installed heating appliances will, in scale deposits.
most cases, already have been reduced.
Removing the limescale deposits is one option for
restoring operational viability. This measure must be
carried out by a qualified contractor. Inspect the heat-
ing system for possible damage prior to returning it into
use.

Prevention of damage due to corrosion on the water side

The corrosion resistance of ferrous materials on the The use of gas-permeable components, e.g. permea-
heating water side of heating systems and heat gener- ble plastic pipes in underfloor heating systems, should
ators depends on the absence of oxygen in the heating be avoided. Provide system separation if such compo-
water. The oxygen introduced into the heating system nents are nevertheless used. This must separate the
with the first fill and subsequent top-ups reacts with the water flowing through the plastic pipes from other heat-
system materials without causing damage. ing circuits, e.g. from the boiler, by the provision of a
The characteristic blackening of the water after a cer- corrosion-resistant heat exchanger.
tain time in operation indicates that there is no more No further anti-corrosion measures are required for
free oxygen present. The technical rules and in partic- sealed hot water heating systems, subject to the above
ular Directive VDI 2035-2 therefore recommend that points being observed. However, take additional pre-
heating systems are designed and operated so that a cautions where there is a risk of oxygen ingress, for
constant ingress of oxygen into the heating water is example by adding oxygen binder sodium sulphite (5 -
prevented. 10 mg/l into the excess). The pH value of the heating
During operation, oxygen can normally only enter due water should be between 9 and 10.5.

Appendix
to: Different conditions apply to systems that contain alu-
■ Open expansion vessels receiving a flow minium components.
■ Negative pressure in the system Where chemicals are used as part of the corrosion
■ Gas-permeable components protection, we recommend that the manufacturer of the
Sealed unvented systems – e.g. with an expansion chemicals issues a certificate of suitability of the addi-
vessel – offer good protection against the ingress of tives with regard to the boiler materials and the materi-
airborne oxygen into the system, if correctly sized and als of the other heating system components. We rec-
operating at the correct pressure. ommend you refer questions regarding water treat-
In all operating states and at all points in the heating ment to a qualified contractor.
system, including the intake side of the pump, the For further details, see Directives VDI 2035-2 and
pressure must be higher than atmospheric pressure. EN 14868.
Check the pre-charge pressure of the expansion ves-
sel at least during the annual service. For pressure
maintaining systems, see page 10.

Using antifreeze in boilers

Viessmann boilers are designed and built for water as ■ Check the compatibility with sealing materials. If
a heat transfer medium. To protect boiler systems from other sealing materials are used, take this into
frost, it may be necessary to treat the boiler water or account when designing the system.
circulating water with antifreeze. ■ Antifreeze developed especially for heating systems
contains inhibitors and buffer substances for corro-
When doing so, observe the following: sion protection as well as glycol. When using anti-
■ In general, follow the specifications given by the anti- freeze, always observe the manufacturer's instruc-
freeze manufacturer. tions regarding minimum and maximum concentra-
■ The properties of antifreeze and water are very dif- tions.
ferent.
■ The temperature stability of the antifreeze must be
sufficient for the particular application.
5692 701 GB

21
Water quality
Using antifreeze in boilers (cont.)

■ The concentration must never fall below the prescri-


bed minimum level, subject to the required frost pro-
tection temperature. Check and adjust the pH value
and frost protection (measure the density) regularly,
at least once a year, according to the manufacturer's
instructions.
■ Check with the relevant supplier whether antifreeze
may affect system components that are not part of
the boiler, such as pumps, electrically and pneumati-
cally driven valves, other types of valves, gaskets,
etc.
■ If the system is filled with antifreeze, it must be
marked accordingly.
■ If a boiler system is changed to operate without anti-
freeze, flush the system in order to remove all traces
of the antifreeze.
■ The quality of the boiler water and feedwater must
meet the requirements of Directive VDI 2035.
■ The systems must be designed as sealed unvented
systems, as the antifreeze inhibitors decrease rapidly
if airborne oxygen is allowed to enter.
■ Diaphragm expansion vessels must comply with
DIN 4807 [or local regulations].
■ Solder connections should preferably be made with
Ag or Cu hard solder. If liquids containing chlorides
are used for soft soldering, any deposits must be
removed from the circuit afterwards through thor-
Appendix

ough flushing. A higher chloride content in the heat


transfer medium can cause corrosion damage.
■ Only use oxygen diffusion-resistant hoses or metal
hoses for flexible connections.
■ Never equip the system on the primary side with
zinc-plated heat exchangers, containers or pipes as
zinc can be corroded by glycol/water mixtures.
■ To avoid the risk of corrosion, ensure that there is no
difference in electrical potential between system
components that are in contact with antifreeze.
■ Route all pipes in such a way that circulation cannot
be interrupted by gas cushions or deposits.
■ The water circuit must always be filled up to the high-
est point with the heat transfer medium.
■ After filling, ensure there are no more air cushions in
the system. When the temperature falls, gas cush-
ions form negative pressure and this can draw air
into the system.
■ After initial filling and commissioning, but after 14
days at the latest, clean the integral dirt trap so the
heat transfer medium can flow freely.
■ Following any losses through leaks or drawing off,
top up the antifreeze solution according to the con-
centration already in place. Establish the volume of
antifreeze as a check.
5692 701 GB

22
Commissioning/service reports
Commissioning/service reports

Commissioning Service Service

date:

by:

Service Service Service

date:

by:

Service Service Service

date:

by:

Appendix
Service Service Service

date:

by:

Service Service Service

date:

by:
5692 701 GB

23
Specification
Specification

Rated heating output kW 150 200 250 310 400 410 500 620
Flue gas parameters *2

Temperature at boiler water


temp. 80 °C
■ At rated heating output °C 215
■ At partial load (60 %) °C 155
Product ID CE-0085BP0365
Efficiency η at
■ 100 % of the rated heating % 90.8 91.0 90.9 91.0 90.9 90.9 91.0 91.1
output (80/65 °C)
■ 30 % of the rated heating % 94.5 94.9 94.7 95.0 94.7 94.7 95.0 95.2
output (80/65 °C)
Appendix

5692 701 GB

*2 Values for sizing the flue system to EN 13384 relative to 13 % CO2 for fuel oil EL and 10 % CO2 for natural gas.
24
Certificates
Declaration of conformity

We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, declare as sole responsible body, that the following
product complies with the listed standards:

Vitoplex 100, type PV1, 150 to 620 kW


■ with the Vitotronic boiler control unit

EN 267 EN 60335-1
EN 303 EN 60335-2-102
EN 676 EN 61000-3-2
EN 14394 EN 61000-3-3
EN 50090-2-2 EN 62233
EN 55014-1 TRD 702
EN 55014-2

In accordance with the following Directives, this product is designated _-0085:

92/42/EEC 2006/95/EC
2004/108/EC 2009/142/EC

This product meets the requirements of the Efficiency Directive (92/42/EEC) for standard boilers (boilers
< 400 kW).

The boiler meets the requirements of all current TRD regulations.

Appendix
Allendorf, 01 October 2014 Viessmann Werke GmbH & Co KG

Authorised signatory Manfred Sommer


5692 701 GB

25
Keyword index
Keyword index

A H
Adjusting the burner................................................... 12 Heating surface cleaning..............................................8

B I
Boiler door Instructing the system user........................................ 13
– Opening.....................................................................8
– Securing.................................................................... 9 O
Boiler water total hardness......................................... 11 Operating and service documents............................. 13

C P
Checking the diaphragm expansion vessel................10 Parts...........................................................................16
Checking the mixer for ease of operation and tight-
ness............................................................................12 S
Checking the system pressure...................................10 Safety equipment function, checking......................... 10
Checking the water quality......................................... 11 System
Cleaning cover – Commissioning..........................................................7
– Opening.....................................................................8 – Filling with water........................................................7
– Securing.................................................................... 9 – Shutting down........................................................... 7
Cleaning the sight glass in the boiler door................. 12 – Venting...................................................................... 7

D T
Draught stabiliser Vitoair Turbulators
– Checking................................................................. 12 – Cleaning.................................................................... 8
– Closing...................................................................... 7 – Inserting.................................................................... 9

F W
Fill and top-up water................................................... 11 Water quality requirements........................................ 20
Flue outlet cleaning...................................................... 8
Flue pipe cleaning........................................................ 8

5692 701 GB

26
5692 701 GB

27
Subject to technical modifications.

Applicability

Serial No.:
7184508 7184509 7184510 7184511
7184512 7184513 7184649 7553287

Viessmann Werke GmbH&Co KG Viessmann Limited


D-35107 Allendorf Hortonwood 30, Telford
Telephone: +49 6452 70-0 Shropshire, TF1 7YP, GB
5692 701 GB

Fax: +49 6452 70-2780 Telephone: +44 1952 675000


www.viessmann.com Fax: +44 1952 675040
E-mail: info-uk@viessmann.com
28

You might also like