Professional Documents
Culture Documents
for contractors
Vitoplex 100
Type PV1, 150 to 620 kW
Oil/gas boiler
VITOPLEX 100
! Please note
This symbol warns against the risk of material
■ Close the gas shut-off valve.
■ Open windows and doors.
losses and environmental pollution. ■ Evacuate any people from the danger zone.
■ Notify your gas or electricity supplier and your
Note local heating contractor from outside the build-
Details identified by the word "Note" contain additional ing.
information. ■ Shut off the electricity supply to the building
from a safe place (outside the building).
Target group
If you smell flue gas
These instructions are exclusively intended for quali-
fied contractors. Danger
■ Work on gas installations must only be carried out by Flue gas can lead to life threatening poisoning.
a registered gas fitter. ■ Shut down the heating system.
■ Work on electrical equipment must only be carried ■ Ventilate the installation site.
out by a qualified electrician. ■ Close all doors in the living space.
■ The system must be commissioned by the system
installer or a qualified person authorised by the Flue systems and combustion air
installer.
Ensure that flue systems are clear and cannot be
Regulations sealed, for instance due to accumulation of conden-
sate or other causes. Ensure a sufficient supply of
Observe the following when working on this system: combustion air.
■ Statutory regulations regarding the prevention of Instruct system users that subsequent modifications to
accidents the building characteristics are not permissible (e.g.
■ Statutory regulations regarding environmental pro- cable/pipework routing, cladding or partitions).
tection
■ The Code of Practice of relevant trade associations Danger
■ All current safety regulations as defined by DIN, EN, Leaking or blocked flue systems, or an insuffi-
DVGW, TRGI, TRF, VDE and all locally applicable cient supply of combustion air can cause life
standards, threatening poisoning from carbon monoxide in
Gas Safety (Installation & Use) Regulations the the flue gas.
appropriate Building Regulationeither the Building Ensure the flue system is in proper working
regulations, theBuilding Regulation (Scotland), Build- order. Apertures for supplying combustion air
ing Regulations (Northern Ireland), the Water Fittings must be non-closable.
Regulation or Water Bylaws in Scotland, the current
I.E.E. Wiring Regulations. Extractors
Danger
The simultaneous operation of the boiler and
appliances that extract air to the outside can
result in life threatening poisoning due to
reverse flow of the flue gas.
Fit an interlock circuit or take suitable steps to
5692 701 GB
2
Safety instructions
Safety instructions (cont.)
Danger
Hot surfaces can cause burns.
■ Before maintenance or service work, switch
OFF the appliance and let it cool down.
■ Never touch hot surfaces on the boiler, burner,
flue system or pipework.
! Please note
Electronic assemblies can be damaged by elec-
trostatic discharge.
Before beginning work, touch earthed objects,
such as heating or water pipes, to discharge
static loads.
Repair work
! Please note
Repairing components that fulfil a safety func-
tion can compromise the safe operation of the
system.
Faulty components must be replaced with origi-
nal Viessmann spare parts.
! Please note
Spare and wearing parts that have not been tes-
ted together with the system can compromise its
function. Installing non-authorised components
and making non-approved modifications or con-
versions can compromise safety and may inva-
lidate the warranty.
For replacements, use only original spare parts
supplied or approved by Viessmann.
5692 701 GB
3
Index
Index
5. Commissioning/service .................................................................................................................. 23
reports
6. Specification .................................................................................................................. 24
5692 701 GB
4
Product information
Symbols
Information
Additional information, not safety relevant
Symbol Meaning
Step:
1. Work sequences required during commis-
The numbering corresponds to the se-
quence of work. sioning
Not required during commissioning
Intended use
5
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance
Commissioning steps
Inspection steps
Maintenance steps Page
6
Commissioning, inspection, maintenance
Commissioning the system
Operating and service instructions for the control 11. The dew point range must be cleared as quickly
unit and the burner as possible. To do so, prevent any heat supply to
the consumers when heating the system from
01. Check that the turbulators are fully inserted into cold. This also applies when restarting after main-
the hot gas flues (see page 9); open the boiler tenance and cleaning work.
door for this.
02. Check that the installation room supply air vent is ! Please note
During boiler heat-up, unpleasant fumes
open. and odours can result from outgassing from
the thermal insulation, the thermal block and
03. Fill the heating system with water and vent the the paint.
system. Vent the room during commissioning.
Permissible operating pressure: 5 bar (0.5 MPa)
12. Once the flow temperature has been reached,
! Please note
Scaling and boiler damage may result if the
successively switch on the heat consumers.
Switch the burner over to automatic mode.
system is not operated with fully softened
heating water.
Operate boilers only with softened water. ! Please note
When testing the flue gas for CO, internal
Observe the instructions in chapter "Water gases being expelled from the thermal block
quality requirements". can result in higher values.
Continue to operate the boiler until a decline
04. Enter the amount of fill water and water hardness can be clearly recognised.
into the table in chapter "Checking the water qual-
ity". 13. Check all gaskets and plugs, and retighten if nec-
essary.
05. Check the system pressure.
14. Check the boiler door and cleaning cover after
06. Check the oil level or the gas supply pressure. approx. 50 hours run and retighten all screws.
Danger
Only open the connections on the heating water
side after the boiler has been depressurised.
Only drain the boiler with a suction pump when
the air vent valve is open.
1. Start the burner. 2. When pre-purge is active, switch off the system; the
control disc is then closed.
5692 701 GB
7
Commissioning, inspection, maintenance
Opening the boiler door and cleaning cover
Note
On gas burners, disconnect the gas supply pipe.
4x
Fig. 1
Cleaning the turbulators, heating surface, flue outlet and flue pipe
A BC
Fig. 2
Fig. 3
5692 701 GB
8
Commissioning, inspection, maintenance
Checking all gaskets and packing cords on the flue gas side
Inserting turbulators
! Please note
Burner adjustments and specific system condi-
tions can cause the turbulators to move forward,
which may result in them being burnt. This can
also lead to damage to the thermal insulation on
the boiler door.
Before insertion, the turbulators must be slightly
bent (see steps).
Note
Ensure that turbulators cannot easily be pulled out
Fig. 4 of the hot gas flues.
Note Danger
On gas burners, mount the gas supply pipe. Escaping gas leads to a risk of explosion.
Check all gas connections for tightness.
A
4x
Fig. 5
5692 701 GB
9
Commissioning, inspection, maintenance
Securing the boiler door and cleaning cover (cont.)
Danger
Leaks can result in a risk of poisoning through
escaping gas.
Check gaskets carefully.
Checking connections and sensor well on the heating water side for tight-
ness
Expansion vessel
1. Drain the system until the pressure gauge indicates 2. If the pre-charge pressure of the expansion vessel
"0" or close the cap valve on the expansion vessel is lower than the static system pressure, top up with
and reduce the pressure in the expansion vessel. nitrogen until the pre-charge pressure is 0.1 to
0.2 bar (0.01 to 0.02 MPa) higher.
Note The static pressure corresponds to the static head.
The pre-charge pressure of the expansion vessel
(p0) is made up of the static system pressure (pSt) 3. Top up with softened water*1 until the charge pres-
(= static head) and a supplement (p0 = pSt + supple- sure of the cooled system is 0.1 to 0.2 bar (0.01 to
ment). 0.02 MPa) higher than the pre-charge pressure of
The supplement depends on the high limit safety the expansion vessel.
cut-out setting. The following applies for the respec- Permiss. operating pressure: 5 bar (0.5 MPa)
tive high limit safety cut-out settings
■ 100 °C: 0.2 bar (0.02 MPa)
■ 110 °C: 0.7 bar (0.07 MPa).
! Please note
Pressure fluctuations may cause damage to the
Boiler out-
put
kW up to
300
up to
500
up to
1000
boiler or to other system components.
Expansion litre 50 80 140
In heating systems with automatic pressure
vessel
maintaining systems, and in particular pump-
controlled systems with integral deaeration, we
recommend the installation of an expansion ves-
sel for each boiler as individual boiler protection.
This reduces the frequency and level of pres-
sure fluctuations. This contributes considerably
to improved operational reliability and a longer
service life of the system components.
5692 701 GB
! Please note
The ingress of oxygen can result in system dam-
Carry out all checks in accordance with the manufac-
turer's instructions. Limit pressure fluctuations to the
age as a consequence of oxygen corrosion. lowest possible differential. Cyclical pressure fluctua-
Only use pump controlled pressure maintaining tions and more significant pressure differentials point
systems that are sealed against corrosion. The towards a system fault. Immediately remedy such
pressure maintaining systems must be protected faults or other heating system components may be
against oxygen ingress into the heating water. damaged.
Pump controlled pressure maintaining systems
with atmospheric deaeration through cyclical
pressure release bring about central post-venti-
lation of the heating system. They do not pro-
vide oxygen removal in the sense of corrosion
protection as described in Directive VDI 2035
Part 2.
Checking the firm seating of electrical plug connections and cable grom-
mets
Observe the instructions in chapter "Water quality Enter the amount of top-up water and the total hard-
requirements". ness of the feed and boiler water into the table.
Meter reading Fill and top-up water Total water volume Total hardness pH value Date
Feedwater Boiler water
m3 m3 m3 °dH °dH
5692 701 GB
11
Commissioning, inspection, maintenance
Checking the water quality (cont.)
The total hardness of the feed and top-up water must The pH value should be between 9 and 10.5.
not exceed 0.11 °dH (total value of alkaline earths
≤ 0.02 mol/m3).
Fig. 6
1. Remove the motorised lever from the mixer handle. 3. Check the mixer for tightness. Replace the O-ring
gaskets if the mixer is leaking.
2. Check the mixer for ease of operation. 4. Snap the motorised lever into place.
Release the latch on the control disc. The control disc must swing freely during burner oper-
ation.
Burner service instructions or separate docu- Adjust the maximum oil or gas throughput of the
mentation by the burner manufacturer burner to the rated boiler heating output.
5692 701 GB
12
Commissioning, inspection, maintenance
Adjusting the burner (cont.)
Rated heating Pressure drop on the hot gas Safeguard the boiler return temperature (minimum
output side temperature) of 65 °C.
kW Pa mbar Set the minimum heating output for the base load
stage according to the conditions of the flue system.
150 60 0.6 Note that the flue system must be suitable for the low
200 120 1.2 flue gas temperatures that may occur.
250 130 1.3
310 230 2.3 In the event of frequent cycling in standby mode and
for partial loads below 40 %, we recommend the fol-
400 250 2.5 lowing:
410 250 2.5 ■ Insulate the flue gas collector
500 230 2.3 ■ Install a motorised flue gas damper
■ Set the minimum boiler runtime to 10 min
620 310 3.1
13
Parts lists
Ordering parts
5692 701 GB
14
Parts lists
Ordering parts
Components
5692 701 GB
15
Parts lists
Parts
210
013
200
009
010
Components
011
002 001
007
005
019
008
021
006
004
020
008 022
Fig. 7
16
Parts lists
Parts (cont.)
Pos. Part
001 Boiler door
002 Studs
003 Sight glass set, comprising: pos. 004 to 008
004 Hose
005 Sight glass closure
006 Sight glass with pos. 007
007 Seal ring
008 Hose nozzle
009 Gasket Ø 18 mm
010 Thermal insulation block
011 Thermal insulation mat
013 Gasket 20 x 15 mm
019 Cleaning brush (wearing part)
020 Brush handle (accessory)
Components
021 Extension piece (accessory)
022 Turbulator extractor (accessory)
200 Front panel, top
205 Top panel, right
206 Top panel, left
210 Control unit fascia
211 Edge protector
5692 701 GB
17
Parts lists
Parts
016
015 208 201 017
015
202
014
Components
209
207
C
212 204
Fig. 8
18
Parts lists
Parts (cont.)
Pos. Part
014 Turbulator
015 Gasket
016 Cleaning cover
017 Gasket 10 x 10 mm
018 Sensor well
201 Back panel, top
202 Back panel, bottom
203 Side panel, back left
204 Side panel, front left and back right
207 Thermal insulation jacket
208 Thermal insulation mat, back
209 Vitoplex 100 logo
212 Side panel, front right with pos. 209
Components
Information on pos. 014
Rated heating output kW 150 200 250 310 400 410 500 620
Number 20 22 26 26 30 30 40 45
5692 701 GB
19
Water quality
Water quality requirements
Note
Observing the following requirements is necessary to
safeguard your warranty rights.
The warranty excludes damage due to corrosion and
scaling.
■ The total volume of fill and top-up water will not ■ During expansion or repair work, only drain the nec-
exceed three times the water content of the heating essary pipework sections.
system during its service life. ■ Check, clean and activate filters, dirt traps and other
■ The specific system volume is less than 20 l/kW blow-down or separating facilities in the heating
heating output. In multi boiler systems, apply the out- water circuit more frequently after commissioning or
put of the smallest boiler. in case of new installations, later on subject to the
■ All measures to prevent corrosion on the water side water treatment applied (e.g. water softening).
in accordance with Directive VDI 2035 Part 2 have ■ No further steps are required during commissioning
been implemented. if you fill the heating system with fully softened
water.
Soften the fill and top-up water in heating systems If the heating system is not filled with fully soft-
operating under the following conditions: ened water, but with water that meets the require-
■ The total of alkaline earths in the fill and top-up water ments in the above table, also observe the follow-
exceeds the standard value. ing during commissioning:
■ Higher fill and top-up water volumes are expected. ■ Commission the system step by step, starting with
■ The specific system volume is greater than 20 l/kW the lowest boiler output and a high heating water
heating output. In multi boiler systems, apply the out- flow rate. This prevents localised concentration of
put of the smallest boiler. limescale deposits on the boiler heating surfaces.
■ In multi boiler systems, start all boilers simultane-
■ In systems > 50 kW, install a water meter to capture ously to prevent the entire limescale deposit settling
the amount of fill and top-up water. Enter the volume in the heat exchanger of just one boiler.
of fill water and the water hardness into the boiler ■ Where water treatment is required, treat even the
maintenance checklists. first fill of the heating system prior to commissioning.
■ For systems with a specific system volume in excess This also applies to any subsequent filling, e.g. when
of 20 l/kW heating output (in multi boiler systems adding top-up water or after a repair, or for any sys-
apply the output of the smallest boiler), apply the tem expansion.
requirements of the next higher category of total out-
put (in accordance with the table). In the case of seri- The build-up of limescale deposits on the heating sur-
ous deviations (> 50 l/kW) soften down to a total of faces will be minimised if these instructions are
alkaline earths ≤ 0.02 mol/m3. observed.
5692 701 GB
20
Water quality
Water quality requirements (cont.)
If limescale deposits have formed because of a failure It is essential that the faulty operating parameters are
to observe the requirements of Directive VDI 2035 the corrected to prevent renewed formation of excessive
service life of the installed heating appliances will, in scale deposits.
most cases, already have been reduced.
Removing the limescale deposits is one option for
restoring operational viability. This measure must be
carried out by a qualified contractor. Inspect the heat-
ing system for possible damage prior to returning it into
use.
The corrosion resistance of ferrous materials on the The use of gas-permeable components, e.g. permea-
heating water side of heating systems and heat gener- ble plastic pipes in underfloor heating systems, should
ators depends on the absence of oxygen in the heating be avoided. Provide system separation if such compo-
water. The oxygen introduced into the heating system nents are nevertheless used. This must separate the
with the first fill and subsequent top-ups reacts with the water flowing through the plastic pipes from other heat-
system materials without causing damage. ing circuits, e.g. from the boiler, by the provision of a
The characteristic blackening of the water after a cer- corrosion-resistant heat exchanger.
tain time in operation indicates that there is no more No further anti-corrosion measures are required for
free oxygen present. The technical rules and in partic- sealed hot water heating systems, subject to the above
ular Directive VDI 2035-2 therefore recommend that points being observed. However, take additional pre-
heating systems are designed and operated so that a cautions where there is a risk of oxygen ingress, for
constant ingress of oxygen into the heating water is example by adding oxygen binder sodium sulphite (5 -
prevented. 10 mg/l into the excess). The pH value of the heating
During operation, oxygen can normally only enter due water should be between 9 and 10.5.
Appendix
to: Different conditions apply to systems that contain alu-
■ Open expansion vessels receiving a flow minium components.
■ Negative pressure in the system Where chemicals are used as part of the corrosion
■ Gas-permeable components protection, we recommend that the manufacturer of the
Sealed unvented systems – e.g. with an expansion chemicals issues a certificate of suitability of the addi-
vessel – offer good protection against the ingress of tives with regard to the boiler materials and the materi-
airborne oxygen into the system, if correctly sized and als of the other heating system components. We rec-
operating at the correct pressure. ommend you refer questions regarding water treat-
In all operating states and at all points in the heating ment to a qualified contractor.
system, including the intake side of the pump, the For further details, see Directives VDI 2035-2 and
pressure must be higher than atmospheric pressure. EN 14868.
Check the pre-charge pressure of the expansion ves-
sel at least during the annual service. For pressure
maintaining systems, see page 10.
Viessmann boilers are designed and built for water as ■ Check the compatibility with sealing materials. If
a heat transfer medium. To protect boiler systems from other sealing materials are used, take this into
frost, it may be necessary to treat the boiler water or account when designing the system.
circulating water with antifreeze. ■ Antifreeze developed especially for heating systems
contains inhibitors and buffer substances for corro-
When doing so, observe the following: sion protection as well as glycol. When using anti-
■ In general, follow the specifications given by the anti- freeze, always observe the manufacturer's instruc-
freeze manufacturer. tions regarding minimum and maximum concentra-
■ The properties of antifreeze and water are very dif- tions.
ferent.
■ The temperature stability of the antifreeze must be
sufficient for the particular application.
5692 701 GB
21
Water quality
Using antifreeze in boilers (cont.)
22
Commissioning/service reports
Commissioning/service reports
date:
by:
date:
by:
date:
by:
Appendix
Service Service Service
date:
by:
date:
by:
5692 701 GB
23
Specification
Specification
Rated heating output kW 150 200 250 310 400 410 500 620
Flue gas parameters *2
5692 701 GB
*2 Values for sizing the flue system to EN 13384 relative to 13 % CO2 for fuel oil EL and 10 % CO2 for natural gas.
24
Certificates
Declaration of conformity
We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, declare as sole responsible body, that the following
product complies with the listed standards:
EN 267 EN 60335-1
EN 303 EN 60335-2-102
EN 676 EN 61000-3-2
EN 14394 EN 61000-3-3
EN 50090-2-2 EN 62233
EN 55014-1 TRD 702
EN 55014-2
92/42/EEC 2006/95/EC
2004/108/EC 2009/142/EC
This product meets the requirements of the Efficiency Directive (92/42/EEC) for standard boilers (boilers
< 400 kW).
Appendix
Allendorf, 01 October 2014 Viessmann Werke GmbH & Co KG
25
Keyword index
Keyword index
A H
Adjusting the burner................................................... 12 Heating surface cleaning..............................................8
B I
Boiler door Instructing the system user........................................ 13
– Opening.....................................................................8
– Securing.................................................................... 9 O
Boiler water total hardness......................................... 11 Operating and service documents............................. 13
C P
Checking the diaphragm expansion vessel................10 Parts...........................................................................16
Checking the mixer for ease of operation and tight-
ness............................................................................12 S
Checking the system pressure...................................10 Safety equipment function, checking......................... 10
Checking the water quality......................................... 11 System
Cleaning cover – Commissioning..........................................................7
– Opening.....................................................................8 – Filling with water........................................................7
– Securing.................................................................... 9 – Shutting down........................................................... 7
Cleaning the sight glass in the boiler door................. 12 – Venting...................................................................... 7
D T
Draught stabiliser Vitoair Turbulators
– Checking................................................................. 12 – Cleaning.................................................................... 8
– Closing...................................................................... 7 – Inserting.................................................................... 9
F W
Fill and top-up water................................................... 11 Water quality requirements........................................ 20
Flue outlet cleaning...................................................... 8
Flue pipe cleaning........................................................ 8
5692 701 GB
26
5692 701 GB
27
Subject to technical modifications.
Applicability
Serial No.:
7184508 7184509 7184510 7184511
7184512 7184513 7184649 7553287