Professional Documents
Culture Documents
for contractors
Vitotronic 100
Type KC2B, KC4B
Electronic boiler control unit
VITOTRONIC 100
Danger Note
This symbol warns against the risk of injury. Details identified by the word "Note" contain additional
information.
! Please note
This symbol warns against the risk of material
losses and environmental pollution.
Target group
These instructions are exclusively intended for quali- ■ Work on gas installations may only be carried out by
fied contractors. a registered gas fitter.
■ Work on electrical equipment may only be carried
out by a qualified electrician.
■ The system must be commissioned by the system
installer or a qualified person authorised by the
installer.
Regulations to be observed
2
Safety instructions
Safety instructions (cont.)
! Please note
Spare and wearing parts that have not been tes-
ted together with the system can compromise its
function. Installing non-authorised components
and making non-approved modifications or con-
versions can compromise safety and may inva-
lidate our warranty.
For replacements, use only original spare parts
supplied or approved by Viessmann.
Danger Danger
Escaping gas can lead to explosions which may Contact with condensate can be harmful to
result in serious injury. health.
■ Do not smoke. Prevent naked flames and Never let condensate touch your skin or eyes
sparks. Never switch lights or electrical appli- and do not swallow it.
ances on or off.
■ Close the gas shut-off valve. Flue systems and combustion air
■ Open windows and doors.
■ Evacuate any people from the danger zone. Ensure that flue systems are clear and cannot be
■ Notify your gas or electricity supply utility from sealed, for instance due to accumulation of conden-
outside the building. sate or other external causes.
■ Have the power supply to the building shut off Avoid continuous condensate disposal with a wind pro-
from a safe place (outside the building). tector.
Ensure an adequate supply of combustion air.
If you smell flue gas Inform system users that subsequent modifications to
the building characteristics are not permissible (e.g.
Danger cable/pipework routing, cladding or partitions).
Flue gas can lead to life threatening poisoning.
■ Shut down the heating system. Danger
■ Ventilate the installation site. Leaking or blocked flue systems, or an inade-
■ Close doors to living spaces to prevent flue quate supply of combustion air can cause life
gases from spreading. threatening poisoning from carbon monoxide in
the flue gas.
What to do if water escapes from the appliance Ensure the flue system is in good working order.
Vents for supplying combustion air must be non-
Danger sealable.
If water escapes from the appliance there is a
risk of electrocution. Extractors
Switch OFF the heating system at the external
isolator (e.g. fuse box, domestic distribution Operating appliances that exhaust air to the outside
board). (extractor hoods, extractors, air conditioning units, etc.)
can create negative pressure. If the boiler is operated
Danger at the same time, this can lead to a reverse flow of flue
If water escapes from the appliance there is a gas.
risk of scalding.
Never touch hot heating water. Danger
The simultaneous operation of the boiler and
appliances that exhausts air to the outside can
result in life threatening poisoning due to a
reverse flow of flue gas.
Fit an interlock circuit or take suitable steps to
ensure an adequate supply of combustion air.
5600124
3
Index
Index
4
Index
Index
5
Index
Index (cont.)
5600124
6
Information
Disposal of packaging
Please dispose of packaging waste in line with statu- DE: Use the disposal system organised by
tory regulations. Viessmann.
AT: Use the ARA statutory disposal system (Altstoff
Recycling Austria AG, licence number 5766).
Information
CH: Packaging waste is disposed of by the HVAC
contractor.
Symbols
Symbol Meaning
Reference to other document containing
further information
Step in a diagram:
1.
The numbers correspond to the order in
which the steps are carried out.
Intended use
The appliance is only intended to be installed and Commercial or industrial usage for a purpose other
operated in sealed unvented heating systems that than the heating up of heating water shall be deemed
comply with EN 12828, with due attention paid to the inappropriate.
associated installation, service and operating instruc-
tions as well as the details in the datasheet. Intended use presupposes that a fixed installation in
It is only designed for the heating up of heating water. conjunction with permissible components designed for
this purpose has been carried out.
5600124
7
Information
Intended use (cont.)
Every other use will be deemed to be inappropriate. Any usage beyond this must be approved by the man-
Any resulting losses are excluded from the manufac- ufacturer for the individual case.
turer's liability.
Intended use also includes the adherence to mainte-
Information
Product information
The control units Vitotronic 100, type KC2B and For room temperature-dependent operation
KC4B for constant temperature operation, are
designed for use in single boiler systems.
System examples
5600124
8
Installation sequence
Opening the control unit
! Please note
When the power supply is connected, touching
electrical contacts can result in appliance dam-
age.
Before opening the control unit, switch off its
mains power supply.
Type KC2B
3.
Service
2.
1.
Fig. 1
5600124
9
Installation sequence
Opening the control unit (cont.)
Type KC4B
Service
Fig. 2
Only use the coding card included with the boiler prod-
uct documentation (see following table).
5
14
1
3
5
15
9
Fig. 3
10
Installation sequence
Inserting the coding card (cont.)
Service
Vitorondens 200-T, type J2RA, 67.6 to
107.3 kW
Vitorond 100, type VR2B, 80 to 100 kW 00c6:02 7435 811 7834 998
Vitogas 200-F, type GS2, 72 to 144 kW
Vitogas 200-F, type GS2, 11 to 60 kW 00f0:02 7435 806 7834 993
The high limit safety cut-out is factory-set to 110 °C. It If the high limit safety cut-out is adjusted to 100 °C, do
can be changed to 100 °C. not set the temperature controller to above 75 °C.
Note
The temperature cannot be returned to its original set-
ting.
5600124
11
Installation sequence
Adjusting the high limit safety cut-out (if… (cont.)
Type KC2B
2.
1.
Service
95
0
10
0
11
120
°C B
4.
3.
Fig. 4
Type KC4B
1.
3.
2.
Fig. 5
5600124
12
Installation sequence
Adjusting the high limit safety cut-out (if… (cont.)
B A
95
0
10
0
11
120
°C
Service
1.
Fig. 6
The temperature controller is set to 75 °C in the deliv- 1. Remove rotary selector " ".
ered condition. It can be adjusted to 87/95 °C.
2. Using a pair of pointed pliers, break off the tabs
Note between "75" and "90" or "95" from the stop dial,
If the high limit safety cut-out is adjusted to 100 °C, do as shown in the diagram.
not set the temperature controller to above 75 °C.
3. Fit rotary selector " " so that the mark sits
! Please note
Excessive DHW temperatures can damage the
DHW cylinder.
between "75" and "90" or "95". Turn rotary selector
" " clockwise as far as it will go.
13
Installation sequence
Adjusting the temperature controller (if… (cont.)
Type KC2B
2.
Service
3.
1.
Fig. 7
Type KC4B
2.
X1
2
3.
1.
Fig. 8
5600124
14
Electrical connections
Overview of electrical connections
Danger
Incorrect wiring can lead to serious injury from
electrical current and result in appliance dam-
! Please note
Electronic assemblies can be damaged by elec-
trostatic loads.
age. Before beginning work, touch an earthed object
■ Route LV leads < 42 V separately from cables such as a heating or water pipe to discharge any
> 42 V/120 V~/208 V~. static.
■ Only strip the minimum of insulation from
cables, as close to the terminals as possible, Opening the control unit
and bundle them close to the corresponding See page 9
terminals.
■ Secure cables with cable ties.
A B
Installation
N L 1 L N L N L N
41 191 1
M M
1~ 1~
fÖ lH sÖ sA ) aG % § aVG
N L 1L N
230 V~ 230 V~
1 L N
3 2 4 6 C
1 L
COM
D
NO
NC
N L 1
E
NO
COM
NC
N
L
Fig. 9
15
Electrical connections
Overview of electrical connections (cont.)
cylinder
sA Circulation pump for cylinder heating (accessories)
fÖ Power supply
fA Burner
lH ■ Mains connection for accessories
■ Vitotrol 100
or
■ External demand/external blocking
X12 External burner start, stage 1
3.
2.
1.
Fig. 10
5600124
16
Electrical connections
Inserting cables/leads and applying strain… (cont.)
1.
2.
Fig. 11
Installation
Plug Component
§ Boiler water temperature sensor
% Cylinder temperature sensor
) Buffer temperature sensor (accessories)
aG Flue gas temperature sensor (accessories)
17
Electrical connections
Connecting the pumps (cont.)
230 V~ pumps
M A
1~
B
Fig. 12
A Pump
B To the control unit
Installation
230 V~ pumps with power consumption greater than 2 A or high efficiency circulation pumps
D D
L N L N
N L
N L
L N C
L N C
L N PE
External
ON/OFF A L N PE
B
Fig. 13 B A
Fig. 14
A Pump
B To the control unit
C Contactor A Pump
D Separate power supply (observe manufacturer's B To the control unit
instructions) C Contactor
D Separate power supply (observe manufacturer's
instructions)
5600124
18
Electrical connections
Connecting the pumps (cont.)
400 V~ pumps
N L L1 L2 L3 N PE
M
A 3~
Fig. 15
Installation
A Pump
B To the control unit
C Contactor
! Please note
Live contacts lead to short circuits or phase fail-
ure.
If the contact is closed, burner stage 1 is switched on
and the boiler water temperature is limited by the tem-
perature controller.
The external connection must be potential-
free. Rated voltage 230 V~
Rated current 6 A~
A
1 2
X12
Fig. 16
Insert jumper across terminals 1 and 2 of plug "X12". Burner stage 1 is switched on. The boiler water tem-
perature is limited by the temperature controller.
1 2
X12
Fig. 17
5600124
19
Electrical connections
External demand via switching contact
Connection options:
■EA1 extension (accessories, see page 65).
■Plug lH if no Vitotrol 100 is connected.
Connection
! Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connection must be potential-
free.
B
A [{A
DE [{S
DE [{D
DE
Installation
1 L?N
lH
Codes
20
Electrical connections
External demand via 0-10 V input (cont.)
+- SÖ P L N N L
U
+
Fig. 18
Installation
Connection options:
■ Plug lH if no Vitotrol is connected.
■ EA1 extension (accessories, see page 65).
! Please note
Live contacts lead to short circuits or phase fail-
ure.
■ Plug aBÖ of external H5 extension (accessories, see The external connection must be potential-
page 66). free.
B
A A [{A
DE [{S
DE [{D
DE
1 L?N
lH
A
EIN EIN
STB N STB TR TR
B A Floating contact
B EA1 extension
A Floating contact
B Plug lH
A Floating contact
B Remove jumper "TR" – "ON/TR"
When the contact is open, the burn- When the contact is closed, the burner is switched off. The heating circuit
er is switched OFF. pump and circulation pump for cylinder heating are switched according to
the set code (see the following table "Codes").
Note
Connect only safety shutdown
equipment, e.g. a temperature limit-
er, to these terminals.
5600124
21
Electrical connections
External blocking via switching contact (cont.)
! Please note
During blocking, there is no frost protection
of the heating system. The boiler is not main-
tained at the lower boiler water temperature.
Codes
The burner cable is included in the standard delivery of Connect the burner in accordance with DIN 4791.
Installation
Terminal codes
L1 Phase via high limit safety cut-out to the burner
PE Earth conductor to burner
41 N Neutral conductor to burner
T1, T2 Control chain
N T1 T2 S3 B4 L S3 Connection for burner fault
B4 Connection for hours run meter
Signal pass direction:
Control unit → Burner
Signal pass direction:
Burner → Control unit
Equipment codes
41
Störung H1
BZ
L1
Fig. 19
The function extension is supplied with the boiler. Max. power consumption
■2-stage: 1 (0.5) A
■Modulating: 0.1 (0.05) A
5600124
22
Electrical connections
Connecting a pressure-jet oil/gas burner (cont.)
Terminal codes
T6, T7, T8 Control chain "Burner stage 2", via two-
A point controller
Control chain "modulation controller", via
three-point controller
T6 From the burner
T7 Modulating burner close
T8 Modulating burner open/stage 2 ON
BN BU BK Signal flow direction:
Control unit → burner
Signal flow direction:
K1 Burner → control unit
K1
C
K2
K2 Colour coding to IEC 60 757
BK Black
BN Brown
BN BK BU BU Blue
Installation
B
Fig. 20
The burner cable is included in the standard delivery of Connect the burner to DIN 4791 [or local regulations].
the boiler.
5600124
23
Electrical connections
Connecting an atmospheric burner (cont.)
A Terminal designations
T1, T2 Control chain
S3 Burner fault
41 B4 Hours run meter
N T1 T2 S3 B4 L
B4 S3 T2 T1 N L
41
Installation
B
Fig. 21
BN BU BK
K1
K1
C
K2
K2
BU BK BN
B
Fig. 22
24
Electrical connections
Power supply
Power supply for accessories and external compo- Colour coding to IEC 60757:
nents BN Brown (L)
■ For accessories and external components that will BK Black
not be connected to the control unit, we recommend BU Blue (N)
making the power connection to the same MCB/fuse, GY Grey
or at the very least in-phase with the control unit. GNYE Green/yellow (PE)
Installation
■ Connection to the same MCB/fuse provides addi-
tional safety in the event of the power being switched Recommended power cable
off. Observe the power consumption of the connec- ■ 3-core cable, flexible
ted consumers. ■ Cable cross-section: 1.5 mm2
■ Rated voltage: 300 V/500 V
Additional regulations for oil and gas combustion ■ Temperature resistance: Min. 70 °C
equipment ■ If the mains connection is made with a flexible power
■ Observe the national combustion equipment ordi- cable, it must be ensured that the live conductors are
nance for your local region. pulled taut before the earth conductor in the event of
■ For oil and gas combustion equipment above strain relief failure. The length of the earth conductor
100 kW an "emergency stop switch" must be instal- wire will depend on the design.
led outside the installation room, in line with the
Sample Combustion Ordinance "FeuVO".
■ For combustion equipment to EN 50156-1, the
"emergency stop switch" installed on site must com-
ply with the requirements of EN 50156-1.
Danger
Incorrectly executed electrical installations can
result in injuries from electrical current and in
appliance damage.
25
Electrical connections
Power supply (cont.)
A B C
40A
40A
145
145
145
145
145
40
96
40
40
D
Fig. 23
A B C
40A
40A
145
145
145
145
145
40
96
40
40
D
Installation
Fig. 24
5600124
26
Electrical connections
Power supply (cont.)
BN
N L
40
Installation
Fig. 25
27
Commissioning
Testing the high limit safety cut-out
Type KC2B
1. Hold down the "test" key (position " ") until the 3. Wait until the boiler water temperature has dropped
burner switches off: approx. 15 to 20 K below the selected safety tem-
The temperature controller " " is bridged. When perature.
the boiler water temperature reaches the safety
temperature, the high limit safety cut-out switches 4. Press the reset button.
the burner and the electronic control off.
Type KC4B
5. Remove jumper C.
A B
Fig. 26
1. Press OK and simultaneously for approx. 4 s. 3. Select required actuator with / (see following
flashes on the display. table).
The display shows the number for the activated
2. Use to select and confirm with OK. actuator and "On".
5600124
28
Commissioning
Checking the outputs (actuator test) (cont.)
Display Explanation
0 All actuators are off.
1 The burner or burner stage 1 is switched on.
2 Burner stage 2 is switched on.
4 The heating circuit pump starts.
5 The circulation pump for cylinder heating starts.
15 Output for solar circuit pump sF on solar control module, type SM1 active.
16 Output for solar circuit pump sF on solar control module, type SM1, switched to mini-
mum speed.
17 Output for solar circuit pump sF on solar control module, type SM1, switched to maxi-
mum speed.
18 Output sS on solar control module, type SM1 active.
19 Contact P - S at plug aBJ of EA1 extension closed.
Commissioning
5600124
29
Coding levels
Calling up coding levels
■ Which codes are shown depends on the heating sys- 6. Exiting coding level 1: Press .
tem configuration. or
■ The codes are divided into groups: Automatically after 30 min
1: "General"
2: "Boiler" Coding level 2
3: "DHW"
4: "Solar" 1. Press OK and simultaneously for approx. 4 s.
5: "Heating circuit 1" flashes on the display.
6: "All codes std device"
In this group, all codes of the coding levels are lis- 2. Press OK and simultaneously for approx. 4 s.
ted in ascending order (except the codes in the
"Solar" group). 3. Use to select 2. Confirm with OK.
7: "Standard setting" I flashes on the display for the coding addresses in
group 1.
Coding level 1
4. Use / to select the group for the required coding
1. Press OK and simultaneously for approx. 4 s. address.
flashes on the display. Confirm with OK.
2. Use to select 1 and confirm with OK. 5. Use / to select the coding address.
I flashes on the display for the coding addresses in
group 1. 6. Use / to set the value according to the following
tables. Confirm with OK.
3. Use / to select the group for the required coding
address. 7. Exiting coding level 2: Press .
Confirm with OK. or
Automatically after 30 min
4. Use / to select the coding address.
Note
This also resets codes in the other coding level.
5600124
30
Coding level 1
Group 1 "General"
Coding
Note
The boiler circuit pump runs on for
approx. 5 minutes after the burner
has switched off.
Group 2 "Boiler"
Coding
Codes
02:0 1-stage burner 02:1 2-stage burner
Gas/oil operation
03:0 Never adjust
Maximum boiler water temperature limit
06:75 Set to 75 °C. 06:20 Adjustable from 20 to 127 °C.
to
Note 06:127
The code has no effect during
DHW heating demand.
31
Coding level 1
Group 2 "Boiler" (cont.)
Group 3 "DHW"
Coding
Group 4 "Solar"
SM1.
Coding
32
Coding level 1
Group 4 "Solar" (cont.)
Codes
Coding
33
Coding level 1
Group 5 "Heating circuit 1" (cont.)
5600124
34
Coding level 2
Group 1 "General"
Coding
Codes
tension: 3b:2 External demand with set minimum
No function boiler water temperature
Selection of set value in coding ad-
dress "9b" in group 1 "General".
3b:3 External blocking
3b:4 External blocking with fault message
input
3b:5 Fault message input
3b:6 No function
3C:0 Function of input DE3 at EA1 ex- 3C:1 No function
tension: 3C:2 External demand with set minimum
No function boiler water temperature
Selection of set value in coding ad-
dress "9b" in group 1 "General".
3C:3 External blocking
3C:4 External blocking with fault message
input
3C:5 Fault message input
3C:6 No function
5600124
35
Coding level 2
Group 1 "General" (cont.)
Note
The boiler circuit pump runs on for
approx. 5 minutes after the burner
has switched off.
52:0 Without buffer temperature sensor 52:1 With buffer temperature sensor; au-
tomatic recognition.
54:0 Without solar thermal system 54:1 With Vitosolic 100; automatic recog-
nition.
Codes
36
Coding level 2
Group 1 "General" (cont.)
Group 2 "Boiler"
Coding
Codes
ing operation (integral) = 2560 Ks 10:199 1 step ≙ 128 Ks.
11:20 Hook-up delay for enabling stage 2 11:0 Hook-up delay adjustable from 0 to
in addition to stage 1 during cylin- to 25,472 Ks.
der heating (integral) = 2560 Ks 11:199 1 step ≙ 128 Ks.
12:20 Shutdown delay for blocking stage 12:0 Shutdown delay adjustable from 0 to
1 in addition to stage 2 (integral) = to 25,472 Ks.
2560 Ks 12:199 1 step ≙ 128 Ks.
13:6 Never adjust
15:15 Never adjust
1C:120 Signal B4 at plug fA not available: 1C:1 Delay adjustable from 1 to 199 s.
Compensation of signal delay for to This time is deducted from the oper-
hours run meter. Time from initia- 1C:199 ating time at every burner start.
tion of burner start signal at T2 in E.g. operating situations where the
plug fA to opening of the solenoid burner is shut down via the mechan-
valve. At each burner start, 120 s ical temperature controller, but a
will be taken off the runtime. burner demand is still present (hours
run continue to be counted).
If required, change coding address
"06" in this group.
1F:0 With flue gas temperature sensor: 1F:1 If the limit for the flue gas tempera-
Flue gas temperature is not moni- to ture is exceeded, is displayed.
tored for burner service indication 1F:250 °C
5600124
37
Coding level 2
Group 2 "Boiler" (cont.)
27:0 Burner fuel consumption (stage 1): 27:1 Input from 10 to 1990
No metering if "26:0" and "27:0" to 1 step ≙ 10 l/h or gallons/h
are programmed. 27:199
28:0 No burner interval ignition 28:1 Time interval adjustable from 1 to
to 24 h. The burner is force-started for
28:24 30 s each time.
29:0 Burner fuel consumption (stage 2): 29:1 Input from 0.1 to 9.9
No metering if "29:0" and "2A:0" to 1 step ≙ 0.1 l/h or gallons/h
are programmed. 29:99
Note
Values of coding addresses "29" and
"2A" are added together.
2A:0 Burner fuel consumption (stage 2): 2A:1 Input from 10 to 1990
No metering if "29:0" and "2A:0" to 1 step ≙ 10 l/h or gallons/h
Codes
Group 3 "DHW"
Coding
Note
Observe the maximum permissible
DHW temperature.
Adjust temperature controller " ".
58:0 Without auxiliary function for DHW 58:10 Entry of a 2nd set DHW temperature
heating to Adjustable from 10 to 90 °C (ob-
58:60 serve coding addresses "56" and
"63")
5600124
38
Coding level 2
Group 3 "DHW" (cont.)
Codes
Above the selected set tempera- 67:90 specific parameters).
ture reheating is suppressed
(DHW heating by the boiler is
blocked).
Group 4 "Solar"
Coding
39
Coding level 2
Group 4 "Solar" (cont.)
40
Coding level 2
Group 4 "Solar" (cont.)
cylinders) is set:
When the set DHW temperature
is achieved in one DHW cylinder,
the 2nd DHW cylinder is heated.
12:20 Minimum collector temperature 12:0 No minimum limit enabled
(minimum start temperature for the 12:1 Minimum collector temperature ad-
solar circuit pump) 20 °C to justable from 1 to 90 °C.
12:90
20:0 No extended control function ac- 20:1 Auxiliary function for DHW heating
tive. 20:2 Differential temperature control 2
20:3 Differential temperature control 2
and auxiliary function
20:4 Differential temperature control 2 for
central heating backup
20:5 Thermostat function
20:6 Thermostat function and auxiliary
function
20:7 Solar heating via external heat ex-
changer without additional tempera-
ture sensor S7
20:8 Solar heating via external heat ex-
Codes
changer with additional temperature
sensor S7
20:9 Solar heating of 2 DHW cylinders
22:8 Start temperature differential for 22:2 Start temperature differential adjust-
central heating backup: 8 K (code to able from 2 to 30 K
"20:4" must be set). 22:30
Switching output sS is switched on
when the temperature at sen-
sor / exceeds the temperature at
sensor aÖ by the selected value.
23:4 Stop temperature differential for 23:2 Stop temperature differential adjust-
central heating backup. 4 K (code to able from 1 to 29 K
"20:4" must be set). 23:30
Switching output sS is switched off
when the temperature at sen-
sor / falls below the stop point.
The stop point is the sum of the
temperature at sensor aÖ and the
value selected as stop temperature
differential.
5600124
41
Coding level 2
Group 4 "Solar" (cont.)
42
Coding level 2
Group 4 "Solar" (cont.)
Coding
Codes
F5:12 Heating circuit pump run-on time F5:0 No heating circuit pump run-on time
12 min F5:1 Heating circuit pump run-on time ad-
to justable from 1 to 20 min.
F5:20
F6:25 In "DHW only" operating mode: F6:0 Heating circuit pump is constantly
Heating circuit pump is constantly OFF.
ON. F6:1 The heating circuit pump starts 1 to
to 24 times per day for 10 min each
F6:24 time.
F7:25 In "Standby mode": F7:0 Heating circuit pump constantly
Heating circuit pump is constantly OFF.
ON. F7:1 The heating circuit pump starts 1 to
to 24 times per day for 10 min each
F7:24 time.
5600124
43
Service checks
Calling up the service level
Operating data
Operating data can be checked in the "i" menu. For further information on operating data, see chapter
"Brief scan".
Operating instructions
Saved data (e.g. hours run) can be reset to "0". 3. Use / to select the required information.
Brief scan
In the brief scan, you can call up temperatures, soft- 3. Select the required scan with / . E.g. "b" for cod-
ware versions and connected components, ing card (see the following table) and confirm with
for example. OK.
44
Service checks
Brief scan (cont.)
Service display
45
Service checks
Service display (cont.)
a 150
Fig. 27
Press OK.
Diagnosis
5600124
46
Troubleshooting
Fault display
1 d1
Fig. 28
The 10 most recent faults (including those remedied) 2. Use to select ã and activate fault history with
are saved and can be called up. OK.
Faults are sorted by date.
3. Use / to select fault messages.
1. Press OK and simultaneously for approx. 4 s.
Fault codes
18 Control mode A sensor was inserted in- Select code "25:0" in group 1
correctly in socket !. "General".
5600124
47
Troubleshooting
Fault display (cont.)
or sensor at S1 of the
Vitosolic.
93 Control mode Short circuit, temperature Check sensor at the solar control
sensor, unit (see separate installation and
connection at S3 of the service instructions).
Vitosolic.
5600124
48
Troubleshooting
Fault display (cont.)
49
Troubleshooting
Fault display (cont.)
1. Pull out all 230 V plugs from the control unit (pumps, burner).
2. Replace the F1 fuse.
3. To determine the faulty device, reconnect all 230 V devices in sequence, until the faulty device is identified.
Pumps are running
Is plug fA live between L1 and N?
No Yes
Check plug fA, burner connecting The fault is unlikely to be due to the control unit; instead the burner termi-
cable and high limit safety cut-out, nal area or the burner itself may be the cause: Is terminal T1 of plug fA
as well as any other limiters (low wa- live when connected?
Service
50
Troubleshooting
Faults that are not displayed at the… (cont.)
Heating circuit pump is not running although boiler water temperature is sufficiently high
2
Resistance in kΩ
1
0.8
0.6
0.4
10 30 50 70 90 110
Temperature in °C
Service
Fig. 29
51
Troubleshooting
Checking the sensors (cont.)
20
10
1
Resistance in kΩ
0.1
0 20 40 60 80 100 120 140 160 180 200
Temperature in °C
Fig. 30
1. Pull out plug aG. 3. In the case of severe deviation, check sensor
installation and replace the sensor if necessary.
2. Check the sensor resistance and compare it to the
curve.
1. Switch OFF the power supply. 3. Check the fuses. Replace if necessary (see con-
nection and wiring diagram).
2. Open the control unit.
Danger
Incorrect or improperly fitted fuses can lead
to an increased risk of fire.
■ Insert fuses without using any force. Posi-
tion fuses correctly.
■ Only use structurally identical types with
the specified response characteristics.
For location of the fuse, see parts list. ■ Max. power loss ≤ 2.5 W
■ To protect the overall appliance, the burner, pumps
F1: and PCB
■ 6.3 A (slow), 250 V~
■ Breaking capacity H
Service
5600124
52
Parts lists
Ordering parts
Service
5600124
53
Parts list type KC2B
Casing assembly
0081
Components
0082
0084
0109 0042
0102 0104
Fig. 31
5600124
54
Parts list type KC2B
Casing assembly (cont.)
Pos. Part
0013 Casing, upper part (drawer)
0018 Programming unit
Components
0042 Temperature sensor with plug
0065 Burner connecting cable with plug fA (for boilers with pressure-jet oil/gas burners)
0070 Power cable with plug fÖ
0071 5-core burner connecting cable with plug fA (for boilers with an intermittent ignition system)
0072 6-core burner connecting cable with plug fA (for boilers with an intermittent ignition system)
0074 Connection pipe
0081 Operating instructions
0082 Abridged operating instructions
0084 Installation and service instructions
0099 Fixing screws
0100 Plugs for sensors (5 pce) and plugs for KM-BUS (2 pce)
0101 Plugs for pumps (3 pce) and plug lH
0102 Plugs "X12" (3 pce)
0104 Power plug fÖ (3 pce)
0109 Burner plugs fA, lÖ , aBA and a:A
5600124
55
Parts list type KC2B
PCB assembly
0050
Components
0054
0092
0090
0014
0052
0098
0016
0017
A
0035
0051
0001
0097
A Type plate
5600124
56
Parts list type KC2B
PCB assembly (cont.)
Pos. Part
0001 Cable clamp
0004 Stop dial for temperature controller
Components
0005 Plug for high limit safety cut-out
0010 Front cover
0011 Front user panel, bottom right
0014 PCB covers
0016 Casing, lower section
0017 Back cover
0030 High limit safety cut-out
0031 Temperature controller
0033 Temperature controller rotary selector
0035 Pushbutton, single pole ("Test" button)
0036 Switch, 2-pole (ON/OFF switch)
0050 PCB
0051 Optolink PCB
0052 Main PCB
0054 Power supply unit PCB
0090 Fuse 6.3 A (slow), 250 V~
0092 Fuse holder
0097 Snap-in hook
0098 Strain relief fittings and cable entries
5600124
57
Parts list type KC4B
Casing assembly
0081
0082
0084
Service
0017
0074
0099 0100 0010
0007
0101 0109
0102
0104
Fig. 33
5600124
58
Parts list type KC4B
Casing assembly (cont.)
Pos. Part
0007 Front cover
0010 Casing, upper part
0017 Casing, upper part, back
0042 Temperature sensor with plug
0065 Burner connecting cable with plug fA (for boilers with pressure-jet oil/gas burners)
0071 5-core burner connecting cable with plug fA (for boilers with an intermittent ignition system)
0072 6-core burner connecting cable with plug fA (for boilers with an intermittent ignition system)
0074 Connection pipe
Service
0081 Operating instructions
0082 Abridged operating instructions
0084 Installation and service instructions
0099 Fixing screws
0100 Plugs for sensors (5 pce) and plugs for KM-BUS (2 pce)
0101 Plugs for pumps (3 pce) and plug lH
0102 Plugs "X12" (3 pce)
0104 Power plug fÖ (3 pce)
0109 Burner plugs fA, lÖ , aBA and a:A
5600124
59
Parts list type KC4B
PCB assembly
0050
0054
0092
0090
0052
Service
0033
0004
0014
0031
0016
0051
0011 0098
A Type plate
5600124
60
Parts list type KC4B
PCB assembly (cont.)
Pos. Part
0004 Stop dial for temperature controller
0005 Plug for high limit safety cut-out
0011 Front user panel
0014 Temperature controller bracket
0016 Casing, lower section
0018 Programming unit
0030 High limit safety cut-out
0031 Temperature controller
Service
0033 Temperature controller rotary selector
0036 Switch, 2-pole (ON/OFF switch)
0050 PCB
0051 Optolink PCB
0052 Main PCB
0054 Power supply unit PCB
0090 Fuse 6.3 A (slow), 250 V~
0092 Fuse holder
0098 Strain relief fittings and cable entries
5600124
61
Function description
Boiler water temperature control
Brief description
■ The boiler water temperature is regulated by switch- ■ If a Vitotrol 100 is connected, it is only switched on if
ing the burner on or off. In the delivered condition, required by the Vitotrol 100.
the switching differential is ±2 K, relative to the cur- ■ When the DHW cylinder is heated, the specified set
rent set value. boiler water temperature is 20 K above the set DHW
■ The set boiler water temperature is determined from temperature (adjustable via coding address "60" in
the following parameters: group 3 "DHW").
– Heating circuit set flow temperature
– Set DHW temperature
– External demand
Functions
Lower control range limits: ■ Extension for controlling a 2-stage burner (see
Boiler water temperature regulated subject to the rele- page 22).
vant boiler (specified by the coding card). ■ External hook-ups (messages) via external EA1
extension (see page 65).
Operation with Vitotrol 100 ■ Plug "X12" for external burner start (see page 19).
■ Plug lH for external demand or external blocking
For connection, see page 15 and separate installation (see page 20 or 21).
instructions.
Set code "40:0" in group 1 "General". Burner switching hysteresis
During the heating times enabled by the Vitotrol 100, in
the "Heating and DHW" operating program, when Permanent switching hysteresis
there is demand, heating is carried out to the set boiler
water temperature selected at the control unit. The Code "04:0"
boiler is maintained at the minimum temperature speci-
fied by the coding card. ON
Burner
62
Function description
Boiler water temperature control (cont.)
The switching hysteresis, i.e. the burner runtime, var- ERB80 function
ies subject to the current heat demand.
Code "04:2"
ERB50 function Depending on the heat demand, values between 6 and
20 K result.
Code "04:1"
Depending on the heat demand, values between 6 and ON
Burner
12 K result.
OFF Time
ON
+17
Burner
OFF Time
+9
+3
set +3
-3 set
low average high -3
heat demand heat demand heat demand low average high
heat demand heat demand heat demand
Fig. 36
Fig. 37
Functions
Control sequence
Brief description
Functions
■ With priority control: (code "A2:2" in group 5 "Heating If the DHW temperature falls below 5 °C, the DHW cyl-
circuit"): inder is heated to 20 °C.
During cylinder heating, the set flow temperature is
set to 0 ºC. Set DHW temperature
The heating circuit pump is switched off.
■ Without priority control: The set DHW temperature can be adjusted between
The heating circuit pump continues to run. 10 and 60 °C.
5600124
63
Function description
Cylinder temperature control (cont.)
The set value range can be extended to 90 °C via cod- Operating instructions
ing address "56" in group 3 "DHW".
Auxiliary function for DHW heating System with solar control unit
Select a second set DHW temperature in coding A third set DHW temperature can be specified via cod-
address "58" in the "DHW" group. This function is ena- ing address "67" in group 3 "DHW".
bled by setting the fourth DHW time phase for DHW The DHW cylinder is only reheated by the boiler if the
heating. temperature falls below this value.
Control sequence
The DHW cylinder goes cold (set value -2.5 K, adjusta- With adaptive cylinder heating, the speed of the tem-
ble at coding address "59"): perature rise during DHW heating is taken into
■ The set boiler water temperature is set 20 K higher account.
than the set DHW temperature (adjustable via coding
address "60"). The DHW cylinder goes cold (set value −2.5 K, adjust-
Functions
64
Function description
EA1 extension
Functions
Fig. 38
Analogue input 0 - 10 V
65
Function description
EA1 extension (cont.)
Output aBJ
Connection of a central fault message facility. Observe coding address "36" in group 1 "General".
External H5 extension
■External burner blocking Live contacts lead to short circuits or phase fail-
■External safety equipment ure.
■Flue gas damper The external connections must be potential-
free.
41 150
41
Fig. 39
A Vitotronic
B External extension H5
C Burner
5600124
66
Function description
External H5 extension (cont.)
D P
ON ON
STB N STB TR TR
A B
150
E P
Fig. 40
Functions
External burner blocking
1. Remove jumper "STB" – "STB". 2. Connect the external safety equipment in series.
Insert jumper "TR" – "ON/TR" across "TR" – "ON". The burner is heated up in stage 1. Shutdown takes
place via the temperature controller.
5600124
67
Function description
External H5 extension (cont.)
EIN EIN
STB N STB TR TR
A
150
1 2 3
M C B
~
Fig. 41
A Plug aBÖ
B Flue gas damper motor
C Limit switch
Functions
5600124
68
Function description
Vitoair draught stabiliser
Functions
A
Fig. 42
A To the burner
B To the control unit
Function check
Motor faulty
69
Connection and wiring diagram
Connection and wiring diagram
Appendix
AB
Fig. 44
70
Specification
Specification
Appendix
5600124
*1 Total max. 4 A~
71
Settings and equipment
Settings and equipment
■ Setting range for DHW temperature 10 to 60 °C = Setting range for DHW temperature 10 to 90 °C
■ Circulation pump for cylinder heating starts if the = Circulation pump starts immediately
boiler water temperature is 7 K higher than the
actual DHW temperature.
■ Circulation pump for cylinder heating runs on for = During cylinder heating, the circulation pump for cyl-
a maximum of 2 min after cylinder heating. inder heating is switched OFF when the set DHW
Appendix
temperature is reached.
■ Without adaptive DHW cylinder control = With adaptive DHW cylinder control
■ Without auxiliary function for DHW heating = With auxiliary function for DHW heating, input of a
second set value of ...........°C
Connected accessories
= Vitotrol 100, type UTA
= Vitotrol 100, type UTDB
= Vitotrol 100, type UTDB-RF
= KM BUS distributor
= Flue gas temperature sensor
= Solar control module, type SM1
= Vitosolic
= Vitoconnect 100 OPTO1
= 2-stage burner extension
= Vitoair
= Extension EA1
= External extension H5
5600124
72
Keyword index
Keyword index
2 Fuel consumption.......................................................38
2-stage burner (connection)................................. 22, 24 Fuses......................................................................... 52
A H
Acknowledged fault display High efficiency circulation pumps............................... 18
– Calling up................................................................ 47 High limit safety cut-out
Actuator test, carrying out.......................................... 28 – Adjusting..................................................................11
Adaptive cylinder heating........................................... 64 – Testing.....................................................................28
Applying strain relief...................................................16
Auxiliary circuits, boiler water temperature control.....62 I
Auxiliary function for DHW heating............................ 64 Installation sequence................................................... 9
Intended use................................................................ 7
B Isolators......................................................................25
Boiler water temperature control................................ 62
Boiler water temperature sensor................................ 51 M
Brief scan................................................................... 44 Mains isolator............................................................. 25
Buffer temperature sensor......................................... 51 Matching coding addresses....................................... 28
Burner........................................................................ 62 Modulating burner (connection)................................. 22
Burner, connecting..................................................... 22 Motorised flue gas damper.........................................68
C O
Checking appliance fuses.......................................... 52 Operating data
Code 1 – Calling up................................................................ 44
– Coding addresses................................................... 31 – Checking................................................................. 44
Code 2 – Resetting................................................................. 44
– Coding addresses................................................... 35 Outputs, checking...................................................... 28
Codes.........................................................................22
Coding card................................................................10 P
Coding levels, calling up............................................ 30 Parts list
Commissioning...........................................................28 – Type KC2B.............................................................. 54
Connecting an atmospheric burner............................ 23 – Type KC4B.............................................................. 58
Connection and wiring diagram..................................70 PCB
Control unit, opening.................................................... 9 – 230 V~.....................................................................16
Cylinder priority control.................................. 33, 43, 63 – Low voltage............................................................. 16
Cylinder temperature control......................................63 Power supply..............................................................25
Cylinder temperature sensor......................................51 – Accessories.............................................................26
– Control unit..............................................................27
D Pressure-jet oil/gas burner, connecting......................22
DHW heating..............................................................64 Priority control............................................................ 63
Draught stabiliser Vitoair............................................ 69 Product information...................................................... 8
Provisional burner operation...................................... 19
E Pumps
EA1 extension............................................................ 65 – Connecting.............................................................. 17
Electrical connections, overview................................ 15 – Run-on.................................................................... 64
ERB50 function.......................................................... 63
ERB80 function.......................................................... 63 R
Extension, 2-stage/modulating burner....................... 22 Resetting codes......................................................... 30
Extension, 2-stage burner.......................................... 24
External blocking........................................................21 S
External burner start...................................................19 Sensors, checking......................................................51
External demand Sensors, connecting...................................................17
– Via 0-10 V input.......................................................20 Service, exiting...........................................................44
– Via switching contact...............................................20 Service display........................................................... 45
External H5 extension................................................ 66 Service level, calling up..............................................44
Set DHW temperature................................................63
F Settings and equipment............................................. 72
Fault codes.................................................................47 Solar control module, type SM1................................. 64
Fault display............................................................... 47 Solar control unit........................................................ 64
– Acknowledging........................................................ 47 Specification...............................................................71
5600124
Switching hysteresis V
– Heat demand-dependent........................................ 62 Vitoair......................................................................... 69
– Permanent...............................................................62 Vitosolic...................................................................... 64
Symbols....................................................................... 7 Vitotrol 100, operation with.........................................62
System equipment..................................................... 72
W
T Wiring diagram........................................................... 70
Temperature controller adjustment.............................13
5600124
74
5600124
75
Subject to technical modifications.