Emergency Stop of level 1

Shorthand of the words:


ACl: Air-Cooler
STC: Stop Time Checking
DP: Differential Protection
Trip GCB. immediately
DT: Discharge Tank
Close EG: Electrical Governor
EP: Electrical Protection
ESL: Emergency Stop Of Level
Electrical protection activated
ESV: Emergency Slide Valve
Exc: Excitation
EP. of Gen. activated
FBC: Mechanical Governor Feedback Cable
FC: Fire Center
Int. EP. of MT. activated OR FF: Fire Fighting
FLP: Failuer Low Pressure
FOL: Failuer Oil Low Level
Exc. Pro. activated GB: Generator Bearing
GAC: Generator Air Chamber
Gen: Generator
GGB: Generator Guide Bearing
Impact to GNS. diagram (*)
GNS: Generator Normal Stop
GS: Generator Speed
GSa: Generator Startup
Int: Internal
DP. activated
Inc: Increasing
AND IG: Intake Gate
FC. activated OR Man: Manual
MDL: Motor Driving for Opening Limiter
MG: Mechanical Governor
Man. FF. in Gen. MT: Main Transformer
OLL: Oil Low Level
Generator Fire Fighting System activated OS: Over Speed
Pre: Pressure
Pro: Protection
PT: Pressure Tank
Over-heat protection activated SPW: The Shear Pin Of Wicket Gate
Tem: Temperature
Tem. of GGB. Thrust No.1 inc. high (≥ 80°C) TGB: Turbine Guide Bearing
WG: Wicket Gate

Tem. of GGB. Thrust No.2 inc. high (≥ 80°C)

Tem. of GB. Thrust No.1 inc. high (≥ 80°C)


Impact to Emergency Stop of level 1

Tem. of GB. Thrust No.2 inc. high (≥ 80°C) Open


MDL. immediately
Close

Tem. of TGB. Thrust No.1 inc. high (≥ 80°C) OR

Tem. of TGB. Thrust No.2 inc. high (≥ 80°C)

Oil Tem. of TGB. inc. high (≥ 60°C)

Tem. of hot air at ACl. No.1 of GAC. inc. high (≥ 80°C)

Tem. of hot air at ACl. No.2 of GAC. inc. high (≥ 80°C)

MHY oil system protection activated

OLL. in MHY DT. (≤ 20%)

OLL. in MHY PT. (≤ 20%) OR

FLP. in MHY PT. (≤ 29kg/cm²)

AND Delay 20 sec. Impact to ESL. 2


WG. ≥ 10%

Intake Gate down to ≤ 7.1m

IG. down to ≤ 7.1m

AND
Gen. rotating

Failure oil low level in Generator bearing

FOL. in GB. activated Delay 3 sec.

Failure oil low level in Turbine guide bearing

FOL. in TGB. activated

Emergency stop of level 2 activated


The Shear Pin Of Wicket Gate broken AND Impact to ESL. 3

ESL. 2 activated (**)


SPW. broken

AND
WG. ≥ 2%

Emergency stop of level 3 activated

ESL. 3 activated (**)

Hold & Reset

Man. Reset (***) HOLD