Professional Documents
Culture Documents
All loads, pressures and capacities are prepared based on limit state design.
Note:
• For wind pressure tables, refer to Section 5: Racking Forces from AS4055.
• For bracing systems, refer to Section 8: Racking and Shear Forces (Bracing)
AS1684.2
AS4055 - Section 5 Racking Forces
Racking forces
• Lateral (Horizontal) forces transferred to the
foundation through bracing provided for each storey
of the house & subfloor.
Bracing for racking lateral forces
Br
the slab and the
ac
Wind forces on the bottom half of ground via bracing
e
this wall are carried direct to the walls.
ground via the wall framing, slab
& footings.
Wind forces on the roof are carried
to the ceiling sheeting (ceiling
diaphragm) via the roof & ceiling
framing Ceiling diaphragm
Br
a
Wind forces on the bottom half of diaphragm' via bracing
ce
this wall are carried to the
flooring (floor diaphragm) via the
wall & floor framing Floor diaphragm
Br
are carried down
ac
ac to the
e
Total racking force (kN) = Area of elevations (m2) X Lateral wind pressure (kPa)
Example 1
Example 2
Working Example 1:
The single storey house shown in Figure 1 below is in N2 wind class site. The
wall height above the ground is 2400mm, the roof pitch is 20o and there is a
600mm wide eave all around the building.
Calculate the racking force on the walls for each lateral wind direction.
Wind Direction 1
Step 1:
Find Wall Area
Step 2:
Find Roof Area
Step 3:
Total Elevation Area =
Wall area + Roof Area
Step 4:
Table 5.1
Find Wind Pressure from Table
5.1
Step 5:Calculate Racking FORCE
AS4055
Wind Direction 1
Step 2:
Find Roof Area
Step 3:
Total Elevation Area =
Wall area + Roof Area
Step 4:
Find Wind Pressure from Table 5.4
Table 5.4
Step 5:Calculate Racking
FORCE
Wind
direction 2
of AS1684.2
Wind Direction 2
Table 8.18 is applicable for STRUCTURAL WALL BRACING (MAXIMUM WALL HEIGHT 2.7M)
Table 8.18 is applicable for STRUCTURAL WALL BRACING (MAXIMUM WALL HEIGHT 2.7M)
If wall height is more than 2700 mm, the capacity in Table 8.18 shall be
multiplied by the values in Table 8.19.
AS1684.2-2010
Table 8.18
AS1684.2-2010
Table 8.18
AS1684.2-2010
Table 8.18
AS1684.2-2010
Table 8.18
AS1684.2-2010
Table 8.18
AS1684.2-2010
Table 8.18
AS1684.2-2010
Table 8.18
Design of Subfloor bracing using AS1684.2 (Section 8.3.5)
• Roof and wall bracing is designed to transfer the lateral loads to the floor plane, which
is then to be transfer to & resisted by the foundations of the building.
Stump may be either of timber/ concrete and placed into either a concrete/ soil backfill.
• Backfilled by Concrete:
Stumps shall be backfilled with a concrete mix of minimum N20 grade with a
maximum20 mm nominal aggregate size.
AS2870-2011
When other soil classifications are found (H1, H2 and E), refer to Table 8.6
below for capacity reduction factor.
Bracing capacity of a diagonally braced stump in concrete backfill-soil classification A, S
and M - wind classification up to N3.
Table 8.7 AS1684.2
Bracing load capacity of a diagonally braced stump in soil backfill-soil classification A, S and
M- wind classification up to N3.
A concrete filled stump pad (also called bored pier) is 250mm diameter and is 400 mm deep.
Timber cross braces of 140X45 F17 seasoned hardwood are used to brace two 100 X 100 mm
concrete stumps with 1 M16 bolt to each stump.
Calculate the capacity of the brace set of two stumps.
140 x 45 mm F11
timber braces
over 2 stumps
= 140 X 45 F17 seasoned
15kN
hardwood fixed with 1M16
bolt to each stump.
Maximum ‘set’
capacity =
Foundation
400
400
Bracing capacity-cantilevered
stumps in concrete backfill-soil
classification A, S and M-Wind
classification to N3.
• The total minimum length of unreinforced masonry bracing walls in any full
length of wall shall be 3000 mm with the minimum length of individual panels
in the wall not less than 900 mm
Unreinforced masonry bracing capacity. Reproduced from Table 8.16 of AS 1684.2