You are on page 1of 1

GENERAL NOTES:

SCHEDULE OF LOAD A. THE INSTALLATION AND EQUIPMENT SHALL CONFORM


TO GOOD ENGINEERING PRACTICES AND IN PARTICULAR
COMPLY WITH THE REQUIREMENTS LAID DOWN IN THE
FOLLOWING DOCUMENTS OR ITS EQUIVALENT WHICH
ARE MANDATORY AND MODIFIED ONLY BY SPECIFIC
AGREEMENT.
PANEL BOARD - (PB)
PHILIPPINE ELECTRICAL CODE........................................................PEC
CIRCUIT LOAD DESCRIPTION No. OF SWITCHES WATTS VOLTS CIRCUIT CURRENT CONDUCTOR CONDUIT NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION..........NEMA
BREAKER LOCAL UTILITY POWER COMPANY..................................................ZAMSURECO-1
No. OUTLETS S1 S2 S3 AT SIZE SIZE
LIGHTING OUTLET B. IN ADDITION TO THE REQUIREMENTS OF THESE CODES
C1 (4-12 W & 2-40W LED LIGHT) 6 2 1 128 220 15 0.58 2.0 mm2 THHN Cu. WIRE 15 mmØ PVC AND THE UTILITY POWER COMPANY'S REQUIREMENT,
LOCAL GOVERNMENT REGULATIONS AND SUPPLIERS
LIGHTING OUTLET SPECIFICATIONS IF ANY, SHALL BE FOLLOWED.
C2 (6-30 W LED LIGHT) 6 2 180 220 15 0.82 2.0 mm2 THHN Cu. WIRE 15 mmØ PVC
C. ALL MATERIALS TO BE INSTALLED SHALL BE UNUSED,
LIGHTING OUTLET BRAND NEW AND SHALL CONFORM WITH THE STANDARDS
2
C3 (7-12W LED LIGHT) 7 1 1 84 220 15 0.38 2.0 mm THHN Cu. WIRE 15 mmØ PVC OF THE UNDERWRITERS LABORATORIES, INC. IN EVERY
CASE WHERE SUCH A STANDARD HAS BEEN ESTABLISHED
APPLIANCE OUTLET FOR THE PARTICULAR TYPE OF MATERIALS TO BE USED.
C4 (7-180W) 7 1,260 220 20 5.72 3.5 mm2 THHN Cu. WIRE 15 mmØ PVC
D. ALL PANEL BOARDS SHALL BE SET PLUMB AND SYMMETRICAL
WITH THE SURROUNDING OBJECTS. PANEL BOARD SHALL
C5 SPARE 1 1500 220 --- 6.82 --- --- BE INSTALLED IN A PERFECTLY FIT CABINET OF APPROPRIATE
SIZE PROVIDED WITH A STOP IN-DOOR TRIM AND GOOD
QUALITY CYLINDER LOCK.
TOTAL 3,152 220 40 14.32 8.0 mm2 THW Cu. WIRE 20 mmØ PVC
E. GROUNDING, IN ELECTRICAL, SHALL CONFORM WITH THE PROVI-
DESIGN COMPUTATION: SIONS OF THE NATIONAL ELECTRICAL CODE OF THE PHILIPPINES
AND AS RECOMMENDED BY THE EQUIPMENT MANUFACTURER.
FEEDER CONDUCTORS: MAIN OVER CURRENT PROTECTION:
F. ELECTRICAL SYSTEM LAYOUT INDICATED ON THE DRAWINGS ARE
IR = 14.32(1.25) = 17.90A ICB = 14.32(2) = 35.80A GENERALLY DIAGRAMMATIC AND THE LOCATION OF OUTLETS,
DEVICES, APPARATUS AND EQUIPMENT ARE ONLY APPROXIMATE.

USE : 8.0 mm2 THW USE: 40 AT/100 AF, 2 POLE G. ALL MATERIALS SHALL BE BRAND NEW AND SHALL BE OF THE
20 mm Diam. PVC 240V, 10 KAIC, PLUG-IN TYPE, I.T.D. MOULDED CASE CIRCUIT BREAKER APPROVED TYPE. IT SHALL CONFORM WITH THE REQUIREMENTS
OF THE PHILIPPINE ELECTRICAL CODE AND SHALL BEAR THE
PHILIPPINE STANDARD AGENCY (PSA) MARK.

H. ALL ELECTRICAL WORKS SHALL BE DONE BY COMPETENT


ELECTRICIAN WITH THE DIRECT SUPERVISION OF PROFESSIONAL
ELECTRICAL ENGINEER.
OTHER GENERAL SPECIFICATIONS:

ALL MATERIALS TO BE USED SHALL BE GOOD QUALITY


AND STANDARD, ALL INSTALLATIONS SHALL CONFORM TO THE
LOCAL CODE OF THE PHILIPPINES.

METHODS OF WIRING: USE CIRCULAR LOOMS FOR WIRES


PASSING THRU CEILING, WIRES SHALL PASS THRU ELECTRICAL
PVC PIPES, FOR CONVENIENCE OUTLETS UNDERNEATH COUNTER
TOP (NEAR BASE BOARD/SKIRTING).

WIRES FOR SWITCHES SHALL BE LOCATED 1.50M ABOVE


THE FINISHED FLOOR LEVEL (FFL) AT WALL.

GENERAL ELECTRICAL INSTALLATIONS SHALL BE UNDER


THE DIRECT SUPERVISION OF A DULY LICENSED PROFESSIONAL
ELECTRICAL ENGINEER.

I. MOUNTING HEIGHTS FOR DEVICES AND OUTLETS SHALL BE AS


FOLLOWS:
LIGHT SWITCHS: 1400 mm CENTER OF DEVICES FROM F.F.L.
CONVENIENCE OUTLET: 300 mm CENTER OF DEVICES FROM F.F.L.
ELECTRICAL PANEL: 1900 mm TOP OF PANEL TO F.F.L.

PROJECT TITLE: PREPARED BY: CHECKED AND REVIEWED BY: RECOMMENDING APPROVAL: APPROVED BY: SHT. CONTENT SHT. NO.
PRC NO:

Republic of the Philippines


DEPARTMENT OF AGRICULTURE CONSTRUCTION OF COPRA
VALID UNTIL:

PTR NO:
*SCHEDULE OF
LOAD
3
PHILIPPINE RURAL DEVELOPMETN PROJECT
CONSOLIDATED FACILITY PLACED ISSUED:
PROVINCIAL GOVERNMENT OF ZAMBOANGA SIBUGAY *GENERAL NOTES
PROVINCIAL ENGINEERING OFFICE
WITH TRUCK SHED

Location: Brgy. Kagawasan, V. Sagun, ZDS


ENGR. ANTONIO N. LAURENCIANA JR.
PPMIU- I Build Head
DATE ISSUED:

TIN NO:
ENGR. JUANITO C. TARIPE JR.

RPCO-IX I-BUILD Component Head


REYNALDO M. CAMPOMANES

RPCO-IX Deputy Regional Director


DIR. RAD DONN L. CEDEÑO

RPCO-IX Project Director


E3