WALL

Lw= 3.75 3750


hw= 3 3000
d= 3 3000 mm
h= 200 mm
f'c= 21
fy= 415

Design for shear ultimate shear force @ the base of wall,


Vu= 500 KN
VC= 458.2575695 KN
Ovc= 389.5189341 KN
Vu= 500 KN > 0Vc/2= 194.7595
Vu=Ovn
Vs= 129.9777246 KN
OVn= 500 KN

Design of horizontal shear reinforcement and required spacings,


Av= 226.08 mm^2 db= 12
>
S2= 2166 Smax
=450 ( shear reinforcement may not be necessary)
MAX SPACING
S2= 750 mm
S2= 600 mm
S2= 450 mm USE
*use 2-12mm-dia. Hor. Reinforcement @ 450mm O.C.

Actual steel ratio of horizontal shear reinforcement


PH= 0.0025 = Phmin (OK)

2. Design of Vertical shear reinforcement,


Required steel ratio,
Pv min= 0.0025

S1= 450.32 SAY 450mm

MAX SPACING
S1= 1250 mm
S1= 600 mm
S1= 450 mm USE
B. Design for Flexure,
Mu= 1500 KN-m
Ru= 0.93
REQUIRED STEEL RATIO
P= 0.0023
Pmin= 0.0034 d= 16

As= 2024.096386 mm^2


Number of bars= 10
*use 10-16mm- dia. Vertical Flexural Reinforcement@ 450mm O.C.