Power for DDC Field Devices Installat Cable Termina tion on Cable Termina tion on DDC Pre- comm.

/
SL.NO. POINT DESCRIPTION QTY Field Eqp. Power BMS Loop Program ming Commiss ioning Graphics Remarks
/ BMS Devices ion BMS Devices Field Testing

3 DDC-SA-03 (MEZZ. )
100% 94% 100% 98% 100% 96% 98% 100% 77% 100%

3.1 CONSTANT VOLUME AIR HANDLING UNITS (AHU-SA-06,09) 2


Supply fan start/stop command 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Supply fan air flow status (run status) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Supply fan Hand-Auto switch status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Supply fan Trip status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Cooling valve control command 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Cooling valve position status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Pre-Filter Status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Supply Air Temperature 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Return Air Temperature 100% 100% 100% 0% 100% 100% 100% 100% 100% 100%

3.2 AIR HANDLING UNITS WITH VFD (AHU-SA-04) 1


Supply fan start/stop command 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Supply fan air flow status (run status) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Supply fan Hand-Auto switch status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Supply fan Trip status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Cooling valve control command 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Cooling valve position status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Pre-Filter Status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Supply Air Temperature 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Return Air CO2 Sensor 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
VFD Speed command 100% 100% 100% 100% 100% 100% 100% 100% 0% 100%
VFD Speed feedback 100% 100% 100% 100% 100% 100% 100% 100% 0% 100%

3.3 STAIR PRESSURIZATION FANS (SPF-SA-01.1) 1


SPF air flow status (run status) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
SPF Hand-Auto switch status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
SPF Trip status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
VFD Speed command 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
VFD Speed feedback 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Staircase Pressure Readings (from Level 02) 100% 100% 100% 100% 100% 100% 0% 100% 0% 100%
Damper open/close status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%

3.4 FRESH AIR FAN (PFAF-S-01) 1


Fresh Air Fans enable/disable command 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Fresh Air Fans air flow status (run status) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Fresh Air Fans Hand-Auto switch status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Fresh Air Fans VFD Trip status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%

3.5 CAR PARK EXTRACT AIR FANS (PEXF-S-01) 2


Car Park Fan VFD enable/disable command 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Car Park Fan air flow status (run status) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Car Park Fan Hand-Auto switch status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Car Park Fan VFD Trip status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Car Park Fan VFD Command 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Car Park Fan VFD Feedback 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%

3.6 WATER FEATURE PUMP SET -SA-MWFP(1DUTY/1STANDBY) 1


Pump Hand-Auto Status 100% 0% 100% 100% 100% 100% 100% 100% 0% 100%
Pump Run status 100% 0% 100% 100% 100% 100% 100% 100% 0% 100%
Pump Trip status 100% 0% 100% 100% 100% 100% 100% 100% 0% 100%

3.7 SPACE CO LEVEL MONITORING (MEZZ.) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
3.8 SPACE TEMPERATURE MONITORING (MEZZ.) 100% 100% 100% 100% 100% 100% 100% 100% 0% 100%

3.1 0 SMDB-(E) -SA-1,2,3,4, 4


Main incomer - On/Off Status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Main incomer - Trip Status 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%

3.11 GATE BARRIERS GF-PB-01,02,03,04,05,06 6


Gate Barrier Open/Close Status 100% 100% 100% 100% 100% 0% 100% 100% 0% 100%
common Fault 100% 100% 100% 100% 100% 0% 100% 100% 0% 100%

3.12 WATER METERS 1


Water Meter readings -Pulse Output- Mezz. 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%