Professional Documents
Culture Documents
10.4-1
Check classification of shape.
h 45 120, 3. 76 E 3. 76 29000 90. 55
tw 3/8 Fy 50
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
453/8
aw Aw 1. 688 10
Af 101
[10-1]
M n R pg F cr S xc 1. 050571. 5 2. 858 10 4 in.-kips 2380 ft-kips
10.4-2
Check classification of shape.
h 70 140. 0 5. 70 E 798. 0 E 5. 70 29, 000 137. 3
tw 0. 5 Fy Fy 50
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
700. 5
aw Aw 0. 530 3 10
Af 223
[10-2]
10.4-3
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
603/8
aw Aw 2. 143 10
Af 127/8
[10-3]
7/8" 12"
10"
3/8"
(not to scale)
10.4-4
[10-4]
Since h 5. 70 E , the web is slender.
tw Fy
2 2
h tf 52 3/4
I x 1 t w h 3 2A f 1 1/452 3 23/4 18
12 2 12 2
2. 171 10 4 in. 4
bf
18 12. 0, p 0. 38 E 0. 38 29, 000 9. 152
2t f 23/4 Fy 50
3/4" 18"
8.667"
1/4"
(not to scale)
[10-5]
h 52 8. 667 in., I 1 8. 6671/4 3 1 3/418 3 364. 5 in. 4
6 6 12 12
A 8. 6671/4 183/4 15. 67 in. 2 , rt I 364. 5 4. 823 in.
A 15. 67
L b 50/2 25 ft
R pg 1 − ar h c − 5. 70 E ≤ 1. 0
1200 300a r tw Fy
10.4-5
[10-6]
1. 980 10 5 in. 4
R pg 1 − ar h c − 5. 70 E ≤ 1. 0
1200 300a r tw Fy
780. 5
aw Aw 0. 709 1 10
Af 222. 5
[10-7]
10.5-1
(a) h 70 140, a 70 1 3
tw 1/2 h 70
Tension field action cannot be used in an end panel. From AISC Equation G2-6,
V n 0. 6F y A w C v1
kv 5 5 5 5 10
2
a/h 1. 0 2
1029000
1. 10 k v E 1. 10 83. 77
Fy 50
Since h/t w 83. 77,
1. 10 k v E
Fy
C v1 83. 77 0. 598 4
h/t w 140
V n 0. 6F y A w C v1 0. 6500. 5 700. 5984 628. 3 kips
V n 628 kips
V n 0. 6F y A w C v2 1 − C v2
1. 15 1 a/h 2
5. 61329000
Compute C v2 . 1. 37 k v E 1. 37 78. 17
Fy 50
[10-8]
1. 515. 61329000
Since h 78. 11, C v2 1. 51k2v E 0. 250 8
tw h/t w F y 140 2 50
1. 10 k v E 62. 76
Fy
1. 10 k v E
Fy
C v1 62. 76 0. 448 3
h/t w 140
A w dt w 70 3 30. 5 38. 0 in. 2
V n 0. 6F y A w C v1 0. 650380. 4483 511 kips 531 kips
V n 531 kips
(c) If no intermediate stiffeners are used, a 3, and k v 5. 34 (no tension field
h
permitted)
5. 3429000
1. 10 k v E 1. 10 61. 22
Fy 50
1. 10 k v E
Fy
Since h 61. 22, C v1 61. 22 0. 437 3
tw h/t w 140
V n 0. 6F y A w C v1 0. 65038. 00. 4373) 498. 5kips
V n 499 kips
10.5-2
(a) h 90 160
tw 9/16
w u 1. 2w D 1. 6w L 1. 24 1. 65 12. 8 kips/ft
[10-9]
12. 875
Reaction w u L 480. 0 kips required v V n in end panel
2 2
Required V n 480 533. 3 kips
0. 90
A w 90 1 19/16 51. 75 in. 2
V n 0. 6A w F y C v1 0. 651. 7550C v1 533. 3, Solution is: C v1 0. 343 5
1. 10 k v E/F y 1. 10 k v 29000/50
C v1 0. 3435, Solution is: k v 4. 304
h/t w 160
kv 5 5 5 5 4. 304
a/h 2 a/h 2
This will result in a negative value of a.
If no intermediate stiffeners are used, a 3, and k v 5. 34 (no tension field
h
permitted)
5. 3429000
1. 10 k v E 1. 10 61. 22
Fy 50
1. 10 k v E
Fy
Since h 61. 22, C v1 61. 22 0. 382 6
tw h/t w 160
V n 0. 6F y A w C v1 0. 65051. 750. 3826 594. 0 kips 533.3 kips
No intermediate stifferers are required.
(b) h 90 160
tw 9/16
wa D L 4 5 9
975
Reaction w a L 337. 5 kips required V n / v in end panel
2 2
Required V n v V n 1. 67337. 5 563. 6 kips
v
A w 90 1 19/16 51. 75 in. 2
V n 0. 6A w F y C v1 0. 651. 7550C v1 563. 6, Solution is: C v1 0. 363
1. 10 k v E/F y 1. 10 k v 29000/50
C v1 0. 363, Solution is: k v 4. 807
h/t w 160
kv 5 5 5 5 4. 807
a/h 2 a/h 2
This will result in a negative value of a.
[10-10]
If no intermediate stiffeners are used, a 3, and k v 5. 34 (no tension field
h
permitted)
5. 3429000
1. 10 k v E 1. 10 61. 22
Fy 50
1. 10 k v E
Fy
Since h 61. 22, C v1 61. 22 0. 382 6
tw h/t w 160
V n 0. 6F y A w C v1 0. 65051. 750. 3826 594. 0 kips 563.6 kips
No intermediate stifferers are required.
10.5-3
Before developing the LRFD and ASD solutions, compute the nominal shear strength
of each panel.
h 66 211. 2
tw 5/16
End panel: a 612 2 74 in., a 74 1. 121 3
h 66
kv 5 5 5 5 8. 979
2
a/h 1. 121 2
8. 97929000
1. 10 k v E 1. 10 79. 38
Fy 50
1. 10 k v E
Fy
Since h 79. 38, C v1 79. 38 0. 375 9
tw h/t w 211. 2
A w 66 1. 5 1. 55/16 21. 56
V n 0. 6F y A w C v1 0. 65021. 560. 3759 243. 1 kips
Second panel:
a 1212 9 − 74 79 in.
a 79 1. 197 3, therefore, tension-field action can be used,
h 66
kv 5 5 5 5 8. 490
a/h 2 1. 197 2
8. 49029000
1. 10 k v E 1. 10 77. 19
Fy 50
[10-11]
Since h 77. 19, use AISC Equation G2-7 or G2-8
tw
A w dt w 66 1. 5 1. 55/16 21. 56 in. 2
2A w 221. 56
0. 958 2 2. 5
A fc A ft 21. 5 15
h h 66 4. 4 6. 0
b fc b ft 15
∴ use AISC Equation G2-7.
V n 0. 6F y A w C v2 1 − C v2
1. 15 1 a/h 2
8. 49029000
Compute C v2 . 1. 37 k v E 1. 37 96. 14
Fy 50
1. 518. 49029000
Since h 96. 14, C v2 1. 51k2v E 0. 166 7
tw h/t w F y 211. 2 2 50
1. 10 k v E
Fy
C v1 61. 22 0. 289 9
h/t w 211. 2
V n 0. 6F y A w C v1 0. 65021. 560. 2899 187. 5 kips
(a) LRFD solution
End panel: Design strength v V n 0. 90243. 1 218. 8 kips
w u 1. 2w D 1. 6w L 1. 20. 225 1. 62. 0 3. 470 kips/ft
[10-12]
3. 47055
Left reaction V L 95. 4 kips 219 kips (OK)
2
Second panel: Design strength v V n 0. 90390. 6 352 kips
V u at beginning of panel V L − w u x 95. 43 − 3. 4706. 167
74. 0 kips 408 kips (OK)
Middle panel: Design strength v V n 0. 90187. 5 169 kips
V u at beginning of panel V L − w u x 95. 43 − 3. 47012. 75
51. 2 kips 169 kips (OK)
Girder has enough shear strength
(b) ASD solution
10.5-4
[10-13]
18. 229, 000
1. 10 k v E 1. 10 113. 0
Fy 50
Since h 113. 0,
tw
1. 10 k v E
Fy
C v1 113 0. 724 4
h/t w 156
V n 0. 6A w F yw C v 0. 641. 5500. 7244 901. 9 kips
First interior panel. a 144 1. 846 3. Tension field action can be used.
h 78
kv 5 5 5 5 6. 467
a/h 2 1. 846 2
6. 46729000
1. 10 k v E 1. 10 67. 37
F yw 50
V n 0. 6F y A w C v2 1 − C v2
1. 15 1 a/h 2
6. 46729000
Compute C v2 . 1. 37 k v E 1. 37 83. 9
Fy 50
1. 516. 46729000
Since h 83. 9, C v2 1. 51k2v E 0. 232 7
tw h/t w F y 156 2 50
[10-14]
4. 480 760
Left reaction V L w u L P u 556. 0 kips
2 2
At 4 ft, V u V L − 4. 4x 556 − 4. 44 538. 4 kips
At 16 ft, V u 556 − 4. 416 485. 6 kips
At 28 ft, V u 556 − 4. 428 432. 8 kips
End panel:
Design strength v V n 0. 9901. 9 812 kips 556 kips (OK)
First interior panel:
Design strength v V n 0. 9685. 4 617 kips 538 kips (OK)
The shear strength of all of the 12-ft panels will be the same, and the shear is less than
617 kips in each 12-ft panel. Therefore, there will be enough shear strength in all of the
12-ft panels.
The girder has enough shear strength.
(b) Compute the required strength at the beginning of each panel (this will be the
maximum shear in the panel).
w a 1 2 3 kips/ft
P a P L 475 kips
380 475
Left reaction V L w a L P a 357. 5 kips
2 2
At 4 ft, V a V L − 4. 4x 357. 5 − 34 345. 5 kips
At 16 ft, V a 357. 5 − 316 309. 5 kips
At 28 ft, V u 357. 5 − 328 273. 5 kips
End panel:
[10-15]
The shear strength of all of the 12-ft panels will be the same, and the shear is less than
346 kips in each 12-ft panel. Therefore, there will be enough shear strength in all of the
12-ft panels.
The girder has enough shear strength.
10.6-1
Bearing strength: A pb 6 − 0. 51/2 2 5. 5 in. 2
R n 1. 8F y A pb 1. 8365. 5 356. 4 kips
Compressive strength: Use a length of web equal to
25t w 255/16 7. 813 in.
Compute the radius of gyration about an axis along the middle of the web:
I 1 7. 8135/16 3 2 1 1/26 3 61/23 5/32 2 77. 79 in. 4
12 12
A 7. 8135/16 261/2 8. 442 in. 2
[10-16]
10.6-2
Bearing strength: A pb 6 − 0. 59/16 4 12. 38 in. 2
R n 1. 8F y A pb 1. 85012. 38 1114 kips
Compressive strength: The maximum permissible length of web is
12t w 123/16 2. 25 in.
(This small contribution could be ignored, but we will include it here.)
Compute the radius of gyration about an axis along the middle of the web:
I 1 2. 253/16 3 4 1 9/166 3 69/163 3/32 2 169. 7 in. 4
12 12
A 2. 253/16 469/16 13. 92 in. 2
10.7-1
Try t f ¾ in., h 73 − 20. 75 71. 5 in.
h ≥ 5. 70 E 5. 70 29, 000 137. 3
tw Fy 50
[10-17]
∴ tw ≤ h 71. 5 0. 520 8 in.
137. 3 137. 3
bf
14 9. 333, p 0. 38 E 0. 38 29, 000 9. 152
2t f 20. 75 Fy 50
Since p r ,
− p
F cr C b F yf 1 − 1 ≤ F yf
2 r − p
[10-18]
Compute the plate girder strength reduction factor.
a r A w 22. 34 2. 128 10
Af 10. 5
R PG 1 − ar h c − 5. 70 E ≤ 1. 0
1200 300a r tw F cr
bf
17. 5 11. 67, p 0. 38 E 0. 38 29, 000 9. 152
2t f 20. 75 Fy 50
Since p r ,
− p
F cr C b F yf 1 − 1 ≤ F yf
2 r − p
a r A w 22. 34 1. 701 10
Af 13. 13
R PG 1 − ar h c − 5. 70 E ≤ 1. 0
1200 300a r tw F cr
[10-19]
1− 1. 701 228. 8 − 5. 70 29, 000 0. 918 4 1. 0
1200 3001. 701 43. 76
M n S x R PG R e F cr 12000. 91841. 043. 76 4. 823 10 4 in.-kips
b M n 0. 948, 230/12 3620 ft-kips 3600 ft-kips (OK)
5 3
Use a 16
71 12 web and 4
17 12 flanges
10.7-2
(a) Try t f 2.5 in., h 78 − 22. 5 73. 0 in.
∴ tw ≤ h 73 0. 531 7 in.
137. 3 137. 3
For a ≤ 1. 5, h ≤ 12. 0 E 12. 0 29000 289. 0
h tw Fy 50
0. 429000
For a 1. 5, h ≤ 0. 4E 232. 0
h tw Fy 50
tw ≥ h 73 0. 314 7 in.
232. 0 232. 0
3
Try a 8
in. 73 in. web.
h 73 194. 7, A w 3/873 2. 5 2 29. 25 in. 2
tw 3/8
Estimate required flange size.
M u 1. 2M D 1. 6M L 1. 23800 1. 67800 1. 704 10 4 ft-kips
M u / b 1704012/0. 90
Af − Aw − 29. 25 57. 37 in. 2
hF y 6 7350 6
b f ≥ 57. 37 22. 95 in.
2. 5
Try a 2. 5-in. 23-in. flange. A f 232. 5 57. 5 in. 2
Check web width-thickness ratio:
r 5. 70 E 5. 70 29000 137. 3
Fy 50
Since r , web is slender and AISC Section F5 applies. Compute the section
[10-20]
modulus:
2
h tf 2
I x 1 t w h 3 2A f 1 3/873 3 257. 5 73 2. 5
12 2 12 2
1. 76 10 5 in. 4
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
23 4. 6 E 0. 38 29000 9. 152
bf
p 0. 38
2t f 22. 5 Fy 50
Since p , the flange is compact and F cr F y 50 ksi
Check lateral-torsional buckling.
h 73 12. 17 in., I 1 12. 173/8 3 1 2. 523 3 2535 in. 4
6 6 12 12
A 232. 5 12. 173/8 62. 06 in. 2 , rt I 2535 6. 391 in.
A 62. 06
L b 25. 0 ft
[10-21]
Since L p L b L r , the girder is subject to inelastic lateral-torsional buckling. From
AISC Equation F5-3,
Lb − Lp
F cr C b F y − 0. 3F y ≤ Fy
Lr − Lp
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
bf
24 4. 8 p 0. 38 E 0. 38 29000 9. 152
2t f 22. 5 Fy 50
Since p , the flange is compact and F cr F y 50 ksi
Check lateral-torsional buckling.
h 73 12. 17 in., I 1 12. 173/8 3 1 2. 524 3 2880 in. 4
6 6 12 12
[10-22]
A 242. 5 12. 173/8 64. 56 in. 2 , rt I 2880 6. 679 in.
A 64. 56
L b 25. 0 ft
∴ tw ≤ h 73 0. 531 7 in.
137. 3 137. 3
For a ≤ 1. 5, h ≤ 12. 0 E 12. 0 29000 289. 0
h tw Fy 50
0. 429000
For a 1. 5, h ≤ 0. 4E 232. 0
h t w Fy 50
tw ≥ h 73 0. 314 7 in.
232. 0 232. 0
3
Try a 8
in. 73 in. web.
h 73 194. 7, A w 3/873 2. 5 2 29. 25 in. 2
tw 3/8
Estimate required flange size.
M a M D M L 3800 7800 11 600 ft-kips
1. 671160012
Af bMa − Aw − 29. 25 58. 81 in. 2
hF y 6 7350 6
[10-23]
b f ≥ 58. 81 23. 52 in.
2. 5
Try a 2. 5-in. 25-in. flange. A f 252. 5 62. 5 in. 2
Check web width-thickness ratio:
r 5. 70 E 5. 70 29000 137. 3
Fy 50
Since r , web is slender and AISC Section F5 applies. Compute the section
modulus:
2
h tf 2
I x 1 t w h 3 2A f 1 3/873 3 262. 5 73 2. 5
12 2 12 2
1. 903 10 5 in. 4
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
25 5. 0 E 0. 38 29000 9. 152
bf
p 0. 38
2t f 22. 5 Fy 50
Since p , the flange is compact and F cr F y 50 ksi
[10-24]
Check lateral-torsional buckling.
h 73 12. 17 in., I 1 12. 173/8 3 1 2. 525 3 3255 in. 4
6 6 12 12
A 252. 5 12. 173/8 67. 06 in. 2 , rt I 3255 6. 967 in.
A 67. 06
L b 25. 0 ft
3
Use a 8
in. 73 in. web. and 2 12 -in. 25-in flanges
10.7-3
Assume a girder weight of 160 lb/ft.
w u 1. 2w D 1. 6w L 1. 20. 5 0. 160 0. 792 kips/ft
P u 1. 6P L 1. 6115 184. 0 kips
18450
M u 1 w u L 2 P u L 1 0. 79250 2 2548 ft-kips
8 4 8 4
0. 79250 184
Vu VL wuL Pu 111. 8 kips
2 2
Total depth: L 5012 60 in., L 5012 50 in.
10 10 12 12
Try a total depth of 55 in. and t f 1. 5 in.
h 55 − 21. 5 52 in.
[10-25]
Determine web thickness.
tw ≤ h 52 0. 378 7 in.
137. 3 137. 3
From h ≤ 12 E 12 29000 289. 0
tw Fy 50
1. 10 k v E
Fy
C v1 61. 22 0. 441 4
h/t w 138. 7
V n 0. 6A w F y C v1 0. 620. 63500. 4414 273. 2 kips
Design strength v V n 0. 9273. 2 245. 9 kips V u (OK)
Estimate required flange size.
[10-26]
Check for web area compression flange area ≤ 10 :
20. 63 1. 528 10 (OK)
13. 5
Girder weight 20. 63 213. 5 0. 490
144
0. 162 1 kips/ft ≈ 0.160 kips/ft (Say OK)
2
h tf 2
I x 1 t w h 3 2A f 1 3/852 3 213. 5 52 1. 5
12 2 12 2
2. 371 10 4 in. 4
23, 710
S xt S xc Icx Ix 862. 2 in. 3
h/2 t f 52/2 1. 5
Tension flange: M n F y S xt 50862. 2 4. 311 10 4 in.-kips
Compression flange: Check FLB:
bf
9 3. 0, p 0. 38 E 0. 38 29, 000 9. 152
2t f 21. 5 Fy 50
Since p , F cr F y 50 ksi
Check lateral-torsional buckling.
1½" 9"
8.667"
3/8"
(not to scale)
[10-27]
L p 1. 1r t E 1. 12. 333 29000 61. 8 in. 5.15 ft
Fy 50
a r A w 20. 63 1. 528 10
Af 13. 5
R pg 1 − ar h c − 5. 7 E ≤ 1. 0
1200 300a r tw Fy
10.7-4
248
(a) At the support, Vu VL wuL Pu 120 168 kips
2 2
M u 16824 − 224 2 /2 − 1208 2496 ft-kips
(Girder weight is included.)
Try t f 2 in., h 50 − 22 46. 0 in.
∴ tw ≤ h 46 0. 335 in.
137. 3 137. 3
[10-28]
For a ≤ 1. 5, h ≤ 12. 0 E 12. 0 29000 289. 0
h tw Fy 50
0. 429000
For a 1. 5, h ≤ 0. 4E 232. 0
h t w Fy 50
tw ≥ h 46 0. 198 3 in.
232. 0 232. 0
1
Try a 4
in. 46 in. web.
h 46 184. 0, A w 1/446 2 2 12. 5 in. 2
tw 1/4
Estimate required flange size.
M u / b 249612/0. 90
Af − Aw − 12. 5 12. 39 in. 2
hF y 6 4650 6
b f ≥ 12. 39 6. 195 in.
2
Try a 2-in. 9-in. flange, A f 29 18. 0 in. 2
2
h tf 2
I x 1 t w h 3 2A f 1 1/446 3 218 46 2
12 2 12 2
2. 276 10 4 in. 4
4
S xt S xc Icx Ix 2. 276 10 910. 4 in. 3
h/2 t f 46/2 2
Compression flange: Check FLB:
bf
9 2. 25, p 0. 38 E 0. 38 29, 000 9. 152
2t f 22 Fy 50
Since p , F cr F y 50 ksi
Check lateral-torsional buckling.
[10-29]
Since L p ≤ L b L r ,
Lb − Lp
F cr C b F y − 0. 3F y ≤ Fy
Lr − Lp
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
460. 25
aw hctw 0. 638 9 10
b fc t fc 92
(b) Shear:
For the first stiffener, determine the required a/h manually (i.e., do not use the Manual
Curves).
From V n 0. 6A w F y C v1 ,
Vn 168/0. 9
Required C v1 0. 497 8
0. 6A w F y 0. 612. 550
Determine required k v . Assuming that AISC Eq. G2-4 controls,
1. 10 k v E
Fy
C v1
h/t w
C 2v1 h/t w 2 F y 0. 4978 2 184 2 50
kv 11. 95
1. 10 2 E 1. 10 2 29000
kv 5 5
a/h 2
a 5 5 1. 038
h kv − 5 9. 643 − 5
[10-30]
The required stiffener spacing is
a 1. 038h 1. 03846 47. 75. Use a 48 in.
At 48 in. from left end, V u 168 − 2 48 160. 0 kips
12
a 48 1. 043 3 ∴ tension field action can be used.
h 46
kv 5 5 5 5 9. 596
a/h 2 1. 043 2
9. 59629000
1. 10 k v E 1. 10 82. 06
Fy 50
[10-31]
5. 3429000
1. 10 61. 22
50
Since h 184. 0 61. 22,
tw
C v1 61. 22 0. 332 7
184
V n 0. 6F y A w C v1 0. 65012. 50. 3327 124. 8 kips
V n 0. 9124. 8 112. 3 kips V u (OK)
∴ stiffeners not needed in middle 1/3.
The theoretical required stiffener spacing is 1@48 in., 1@97 in. each end
For a symmetrical spacing, use 1@48, 1@97/2 ≈ 48 in. each end
10.7-5
1
From Problem 10.7-4, use a 4
46 web and 2 9 flanges. Reaction 168 kips
Design the bearing stiffeners at the supports and use the same design for the interior
stiffeners.
bf − tw 9 − 1/4
Maximum stiffener width 4. 375 in.
2 2
Try b 4 in. and
t≥ b F yst
4 50 0. 296 6 in.
0. 56 E 0. 56 29000
5
Try two plates, 16
in. 4 in., with 1-in. cutouts.
Bearing strength: A pb 4 − 15/16 2 1. 875 in. 2
R n 1. 8F y A pb 1. 8501. 875 168. 8 kips
R n 0. 75168. 8 126. 6 kips V L 168 kips (N.G.)
Determined required thickness.
Required R n 168/0. 75 224. 0 kips
[10-32]
Compressive strength: The maximum permissible length of web is
12t w 121/4 3. 0 in.
(This small contribution could be ignored, but we will include it here.)
Compute the radius of gyration about an axis along the middle of the web:
I 1 3. 00. 25 3 2 1 7/164 3 47/162. 0 1 1 2 20. 48 in. 4
12 12 2 4
A 31/4 247/16 4. 25 in. 2
10.7-6
(a) w u 1. 2w D 1. 6w L 1. 21. 0 1. 62 4. 4 kips/ft
P u 1. 6P L 1. 6475 760. 0 kips
4. 480 760
Left reaction V L w u L P u 556. 0 kips
2 2
2
h tf 2
I x 1 t w h 3 2A f 1 0. 578 3 22. 5 22 78 2. 5
12 2 12 2
1. 980 10 5 in. 4
The shear flow is
2. 522 78 2. 5
tf
Q Af h 2214 in. 3
2 2 2 2
VuQ 556. 02214
At the support, 6. 217 kips/in.
Ix 198000
3
Minimum weld size 16
in. (AISC Table J2.4)
Minimum length of intermittent fillet welds 4 3 0. 75 in. 1.5 in., use 1.5 in.
16
Use E70 electrodes, R n 1. 392D kips/in., where D weld size in sixteenths.
[10-33]
5
Try 16
-in. 1 12 -in. intermittent fillet welds. For two welds,
Weld strength 2 1. 3925 13. 92 kips/in.
Base metal shear yield strength 0. 6tF y 0. 60. 550 15. 0 kips/in.
Base metal shear rupture strength 0. 45tF u 0. 450. 565 14. 63 kips/in.
For a 1.5-in. length, R n 1. 513. 92 20. 88 kips
Required spacing:
R n VuQ 20. 88 6. 217
s Ix s s 3. 358 in.
(b) w a 1 2 3 kips/ft
P a 475 kips
380 475
Left reaction V L 357. 5 kips
2
2
h tf 2
I x 1 t w h 3 2A f 1 0. 578 3 22. 5 22 78 2. 5
12 2 12 2
1. 980 10 5 in. 4
The shear flow is
[10-34]
2. 522 78 2. 5
tf
Q Af h 2214 in. 3
2 2 2 2
VLQ 357. 52214
At the support, 3. 998 kips/in.
Ix 198000
3
Minimum weld size 16
in. (AISC Table J2.4)
Minimum length of intermittent fillet welds 4 3 0. 75 in. 1.5 in., use 1.5 in.
16
Use E70 electrodes, R n / 0. 9279D kips/in., where D weld size in sixteenths.
5
Try 16
-in. 1 12 -in. intermittent fillet welds. For two welds,
Weld strength 2 0. 92795 9. 279 kips/in.
Base metal shear yield strength 0. 4tF y 0. 40. 550 10. 0 kips/in.
Base metal shear rupture strength 0. 3tF u 0. 30. 565 9. 75 kips/in.
For a 1.5-in. length, R n / 1. 59. 279 13. 92 kips
Required spacing:
R n / V Q 13. 92 3. 998
s a s s 3. 482 in.
Ix
For a center-to-center spacing of 3 in., the clear spacing is 3 − 1. 5 1. 5 in.
Maximum clear spacing: From AISC E6,
[10-35]
The small variation in required spacing does not warrant using more than one spacing.
5
Use 16
-in. 1 12 -in. E70 fillet welds spaced at 3 in. c-c.
5
Alternate: Use a 16
-in. E70 continuous fillet weld.
10.7-7
(a) Assume a girder weight of 200 lb/ft.
w u 1. 2w D 1. 6w L 1. 21. 3 0. 200 1. 62. 3 5. 48 kips/ft
P u 1. 2P D 1. 6P L 1. 228 1. 649 112. 0 kips
5. 4866
Vu VL wuL Pu 112 292. 8 kips
2 2
M u 292. 833 − 5. 4833 2 /2 − 11266/6 5447 ft-kips
Try t f 1. 5 in. h 80 − 21. 5 77. 0 in.
Try a slender plate girder.
h ≥ 5. 70 E 5. 70 29000 137. 3
tw Fy 50
∴ tw ≤ h 77 0. 560 8 in.
137. 3 137. 3
From h ≤ 12. 0 E 12. 0 29000 289. 0
tw Fy 50
Girder weight 40. 0 212. 38 0. 490 0. 220 4 kips/ft 0.200 kips/ft
144
[10-36]
Assume girder weight 0.25 kips/ft
w u 1. 2w D 1. 6w L 1. 21. 3 0. 250 1. 62. 3 5. 54 kips/ft
5. 5466
Vu VL wuL Pu 112 294. 8 kips
2 2
M u 294. 833 − 5. 5433 2 /2 − 11266/6 5480 ft-kips
Estimate required flange size.
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
770. 5
aw hctw 3. 111 10
b fc t fc 8. 251. 5
bf
8. 25 2. 75, p 0. 38 E 0. 38 29, 000 9. 152
2t f 21. 5 Fy 50
Since p , F cr F y 50 ksi
Check lateral-torsional buckling.
[10-37]
A 12. 830. 5 8. 251. 5 18. 79 in. 2 , rt I 70. 32 1. 935 in.
A 18. 79
L b 22 ft.
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
770. 5
aw hctw 1. 833 10
b fc t fc 141. 5
bf
14 4. 667, p 0. 38 E 0. 38 29, 000 9. 152
2t f 21. 5 Fy 50
Since p , F cr F y 50 ksi
Check lateral-torsional buckling.
h 77 12. 83 in., I 1 12. 830. 5 3 1 1. 514 3 343. 1 in. 4
6 6 12 12
[10-38]
A 12. 830. 5 141. 5 27. 42 in. 2 , rt I 343. 1 3. 537 in.
A 27. 42
L b 22 ft.
[10-39]
bf − tw
Maximum stiffener width 14 − 0. 5 6. 75 in.
2 2
1. 5 14 77 1. 5
tf
The shear flow is Q Af h 824. 3 in. 3
2 2 2 2
VuQ 295. 8824. 3
At the support, 2. 912 kips/in.
Ix 83730
5
Minimum weld size 16
in. (AISC Table J2.4)
[10-40]
Minimum length 4 5 1. 25 in. 1.5 in., use 1.5 in.
16
Use E70 electrodes, R n 1. 392D kips/in., where D weld size in sixteenths.
5
Try 16
-in. 1 12 -in. intermittent fillet welds. For two welds,
Weld strength 2 1. 3925 13. 92 kips/in.
Base metal shear yield strength 0. 6tF y 0. 60. 550 15. 0 kips/in.
Base metal shear rupture strength 0. 45tF u 0. 450. 565 14. 63 kips/in.
For a 1.5-in. length, R n 1. 513. 92 20. 88 kips
Required spacing:
R n VuQ 20. 88 2. 912
s Ix s s 7. 195 in.
[10-41]
5
Use 16
in. 1 12 in. intermittent E70 fillet welds.
[10-42]
4 1. 3923 16. 7 kips/in.
Base metal shear yield strength 0. 6tF y 0. 62 0. 550 30. 0 kips/in.
Base metal shear rupture strength 0. 45tF u 0. 452 0. 565 29. 25 kips/in.
Weld strength controls:
R n 1. 516. 7 25. 05 kips
The shear to be transferred is
P u length available for weld 112 1. 493 kips/in.
77 − 21. 0
25. 05 1. 493 kips/in. s 16. 78 in.
s
For a center-to-center spacing of 16 34 in., the clear spacing is
16. 75 − 1. 5 15. 25 in. 9 in. max. (9 1. 5 10. 5 in. c-c)
3
Use 16
in. 1 12 in. E70 fillet welds spaced at 10 12 in. c-c
10.7-8
(a) Assume a girder weight of 600 lb/ft.
w u 1. 2w D 1. 6w L 1. 20. 3 0. 6 1. 60. 7 2. 2 kips/ft
P u 1. 2P D 1. 6P L 1. 250 1. 6150 300. 0 kips
2. 2100 3300
V u V L w u L 3P u 560. 0 kips
2 2
M u 56050 − 2. 250 2 /2 − 30025 1. 775 10 4 ft-kips
[10-43]
From h ≤ 12 E 12 29000 289. 0
tw Fy 50
and
h ≤ 0. 40E 0. 4029000 232. 0
tw Fy 50
tw ≥ h 115 0. 495 7 in.
232. 0 232. 0
3
Try a 4
in. 115 in. web.
h 115 153. 3, A w 3/4115 2. 5 2. 5 90. 0 in. 2
tw 3/4
Estimate required flange size.
bf
15. 5 3. 1, p 0. 38 E 0. 38 29, 000 9. 152
2t f 22. 5 Fy 50
Since p , F cr F y 50 ksi
Check lateral-torsional buckling.
[10-44]
rt I 776. 5 3. 823 in.
A 53. 13
L b 25 ft
Cb 12. 5M max
2. 5M max 3M A 4M B 3M C
12. 517750
1. 103
2. 517750 314550 415700 316770
F cr 1. 103 50 − 0. 350 25 − 8. 442 41. 70 ksi (controls)
28. 81 − 8. 442
Compute the bending strength reduction factor.
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
1150. 75
aw hctw 2. 226 10
b fc t fc 15. 52. 5
[10-45]
3
Try a 4
in. 115 in. web and 2 12 in. 15 12 in. flanges
1. 10 k v E
Fy
h 153. 3 63. 44 ∴ C v1 63. 44 0. 413 8
tw h 153. 3
tw
V n 0. 6F y A w C v1 0. 650900. 4138 1117 kips
v V n 0. 901117 1005 kips 560 kips (OK)
No intermediate stiffeners (other than the bearing stiffeners) are required.
[10-46]
R n 0. 75810 607. 5 kips V L 560 kips (OK)
Compressive strength: The maximum permissible length of web is
12t w 120. 75 9. 0 in.
Compute the radius of gyration about an axis along the middle of the web:
I 1 9. 00. 75 3 2 1 0. 757 3 70. 753. 5 3/8 2 200. 9 in. 4
12 12
A 90. 75 270. 75 17. 25 in. 2
4. 71 E 4. 71 29000 113. 4
Fy 50
Since Lrc 4. 71 E
Fy
Fy 50
F cr 0. 658 F e Fy 0. 658 448. 2 50 47. 72 ksi
Because there is a large difference between the reactions and the interior concentrated
loads, use a different size for the interior bearing stiffeners. Design the interior bearing
stiffeners for a load of P u 300 kips.
[10-47]
R n 0. 75450 338 kips P u 300 kips (OK)
Compressive strength: The maximum permissible length of web is
25t w 250. 75 18. 75 in.
Compute the radius of gyration about an axis along the middle of the web:
I 1 18. 750. 75 3 2 1 0. 56 3 60. 53 3/8 2 87. 0 in. 4
12 12
A 18. 750. 75 260. 5 20. 06 in. 2
r I 87 2. 083 in.
A 20. 06
Compute the compressive strength:
L c KL 0. 75115 86. 25 in.
L c 86. 25 41. 41
r 2. 083
2 2 29000
Fe E 2 166. 9 ksi
Lc 41. 41 2
r
4. 71 E 4. 71 29000 113. 4
Fy 50
Since Lrc 4. 71 E
Fy
Fy 50
F cr 0. 658 F e Fy 0. 658 166. 9 50 44. 11 ksi
38. 75 115 2. 5
tf
Shear flow: Q Af h 2277 in. 3
2 2 2 2
VuQ 5602277
At the support, 3. 517 kips/in.
Ix 3. 626 10 5
1
Minimum weld size 4
in. (AISC Table J2.4)
[10-48]
1
Try 4
-in. 1 12 -in. intermittent fillet welds. For two welds,
Weld strength 2 1. 3924 11. 14 kips/in.
Base metal shear yield strength 0. 6tF y 0. 60. 7550 22. 5 kips/in.
Base metal shear rupture strength 0. 45tF u 0. 450. 7565 21. 94 kips/in.
Weld strength controls.
For a 1.5-in. length, R n 1. 511. 14 16. 71 kips
Required spacing:
R n VuQ 16. 71 3. 517
s Ix s s 4. 751 in.
[10-49]
Welds for bearing stiffeners: Welds for bearing stiffeners at the supports (3/4 7):
1
Minimum weld size 4
in. (AISC Table J2.4, based on a thickness of 3/4 in.)
Minimum length 41/4 1 in. 1.5 in., use 1.5 in.
Use E70 electrodes, R n 1. 392D kips/in., where D weld size in sixteenths.
1
Try 4
in. 1 12 in. intermittent fillet welds. For four welds, the weld strength is
4 1. 3924 22. 27 kips/in.
Base metal shear yield strength 0. 6tF y 0. 62 0. 7550 45. 0 kips/in.
Base metal shear rupture strength 0. 45tF u 0. 452 0. 7565 43. 88 kips/in.
Weld strength controls. For a 1.5-in. length,
R n 1. 522. 27 33. 41 kips
Reaction length available for weld 560 4. 956 kips/in.
115 − 21. 0
33. 41 4. 956, Solution is: 6. 74 in.
s
For a center-to-center spacing of 6 12 in., the clear spacing is 6. 5 − 1. 5 5. 0 in.
1
Use 4
in. 1 12 in. E70 fillet welds spaced at 6 12 in. c-c for bearing stiffener at support.
[10-50]
Maximum clear spacing:
10.7-9
(a) Assume a girder weight of 875 lb/ft.
w u 1. 2w D 1. 6w L 1. 21. 9 0. 875 1. 62. 8 7. 81 kips/ft
P u 1. 2P D 1. 6P L 1. 2112 1. 6168 403. 2 kips
7. 81120 3403. 2
V u V L w u L 3P u 1073 kips
2 2
M u 107360 − 7. 8160 2 /2 − 403. 230 3. 823 10 4 ft-kips
Try t f 3 in., h 1012 − 23 114 in.
In order for this flexural member to be a slender girder,
h ≥ 5. 70 E 5. 70 29, 000 137. 3
tw Fy 50
[10-51]
Girder weight 0. 75114 284. 0 0. 490
144
0. 863 kips/ft 0.875 kips/ft (OK)
2
h tf 2
I x 1 t w h 3 2A f 1 0. 75114 3 284. 0 114 3
12 2 12 2
6. 675 10 5 in. 4
bf
28 4. 667, p 0. 38 E 0. 38 29, 000 9. 152
2t f 23 Fy 50
Since p , F cr F y 50 ksi
Check lateral-torsional buckling.
Since L b L p , F cr F y
Compute the bending strength reduction factor.
R pg 1 − aw h c − 5. 7 E ≤ 1. 0
1200 300a w tw Fy
1140. 75
aw hctw 1. 018 10
b fc t fc 283
[10-52]
3
Try a 4
in. 114 in. web and 3 in. 28 in. flanges
1. 10 k v E
Fy
h 152 61. 22 ∴ C v1 61. 22 0. 402 8
tw h 152
tw
V n 0. 6F y A w C v1 0. 650900. 4028 1088 kips
v V n 0. 901088 979. 2 kips 936.2 kips (OK)
No additional intermediate stiffeners are needed.
3
Use a 4
114 web and 3 28 flanges
From b ≤ 0. 56 E
t st F yst
12 ≤ 0. 56 29000
t 50
t ≥ 0. 1258 in. Try t 5/16 in.
Use I st ≈ I st1
[10-53]
1.5
h 4 1.3 F yw
st
40 E
max 50 , 1
F yw
st max ,1 1
F yst 50
1.5
h 4 1.3 F yw 114 4 1 50 1.5
I st st
302. 3 in. 4
40 E 40 29000
Try two 5/16 12 plates.
5/1612 3
I st 5/16126 3/8 2 2
12
394. 8 in. 4 302. 3 in. 4 (OK)
Length: From Figure 10.9 in the textbook,
c ≥ 4t w 40. 75 3. 0 in., and c ≤ 6t w 60. 75 4. 5 in.
3
Assume a flange-to-web weld size of w 16
in. (minimum size) and c 4 in.
(c) Design bearing stiffeners for the concentrated loads of P u 403. 2 kips
bf − tw 28 − 3/4
Maximum stiffener width 13. 63 in.
2 2
[10-54]
Compute the compressive strength:
L c KL 0. 75114 85. 5 in.
L c 85. 5 32. 58
r 2. 624
2 2 29000
Fe E 2 269. 6 ksi
Lc 32. 58 2
r
4. 71 E 4. 71 29000 113. 4
Fy 50
Since Lrc 4. 71 E
Fy
Fy 50
F cr 0. 658 e
F Fy 0. 658 269. 6 50 46. 27 ksi
84 114 3
tf
Shear flow: Q Af h 4914 in. 3
2 2 2 2
VuQ 10734914
At the support, 7. 899 kips/in.
Ix 6. 675 10 5
1
Minimum weld size 4
in. (AISC Table J2.4)
[10-55]
For a center-to-center spacing of 2 in., the clear spacing is 2 − 1. 5 0. 5 in.
Maximum clear spacing: From AISC E4,
[10-56]
1
Use 4
1 12 in. intermittent E70 fillet welds spaced at 5 14 -in. from B to C
and from C to D.
5
Welds for intermediate stiffeners 16
in. 12 in. :
3
Minimum weld size 16
in. (AISC Table J2.4)
[10-57]
22. 27 3. 6 kips/in. s 6. 186 in.
s
For a center-to-center spacing of 6 in., the clear spacing is 6 − 1. 5 4. 5 in 10 in.
max.
1
Use 4
in. 1 12 in. E70 fillet welds spaced at 6 in. c-c for bearing stiffeners.
[10-58]