Professional Documents
Culture Documents
Pipe Leak Test Record Pipe Leak Test Record
Pipe Leak Test Record Pipe Leak Test Record
4.MATERIAL GI
5.TESTING CONDITION
DI water/City Water/ Nitrogen / Others ( )
1) Test with
Compressed Air (Oil Free / Untreated )
2) Working Pressure 0.80 MPa
3) Testing Pressure 0.88 MPa
4) Pressure holding Time 30 minutes
5) Testing points All connection / Partial (see the attached drawings)
6.TESTING RESULT
1) Testing Date & time Start 3/10/2022 5.00PM
End 3/10/2022 5.30PM
2) Conducted by TTE Person name SHAKIRIN
3) Witness IBIDEN/TTE Person name MAN
4) Before Testing 0.95 MPa (S) 0.97 MPa (R)
5) After Testing 0.95 MPa (S) 0.97 MPa (R)
6) Result Accept ・Reject Person name/sign
7.TESTING INSTRUMENT
Instrument Name Measurement Range Model Brand Remark
1) Pressure Gauge 0 ~ 2 MPa Unijin
2) ~
3) ~
8.REMARKS
[Format 7-1]Table
9.Reference documents.
1)Piping schematic shop drawing show testing line
2)Testing record photo.
3)Others
Initial Air Leak Testing Pressure (S) = 0.95MPa Initial Air Leak Testing Pressure (S) = 0.95MPa
Initial Air Leak Testing Pressure (R) = 0.97MPa Initial Air Leak Testing Pressure (R) = 0.97MPa
After Air leak Testing Reading(S) = 0.95MPa After Air leak Testing Reading(S) = 0.95MPa
After Air leak Testing Reading(R) = 0.97MPa After Air leak Testing Reading(R) = 0.97MPa