1 Flue Gas temp.(Max) = 150 ℃ (Stack Inlet) 2 Gas flow rate (Vgt) = At maximum continuous input(MCR) flow design case = 11,000 NM3/HR (+10% Margin Rate) 3 Theory Draft of Stack (h) Info for item D : h = 355 x H x ( 1/T1 - 1/T2 ) Information of Chimney Item 12 (i ~vi) = 355 x 25 x ( 1/303.0 - 1/419.9 ) = 8.15 mmAQ Where H ; STACK Height = 25 M T1 ; AMB. Temp. = 30 + 273 = 303 K T2 ; AVERAGE TEMP. OF STACK INSIDE = (STACK BOTTOM TEMP. + DOWNSTREAM TEMP. OF INSIDE)/2 + 273 = 419.875 K [ DOWN STREAM TEMP. OF STACK = 0.25℃/M H x 0.25 = 6.25 ℃ = 150 - 6.25 = 143.8 ℃
4 STACK INSIDE DIAMETER AT THE TOP (D)
Where D = SQRT( 4 * F / π ) F ; STACK INSIDE SECTIONAL AREA AT THE TOP ( M2 ) T ; STACK OUTLET GAS TEMP. ( K ) F = ( Vgt x T )/( 273 x 3600 x V ) = 416.8 K = 0.5488 M2 V ; STACK GAS VELOCITY= 8.5 m/sec
D = 0.8359 M 860 mm
V ; ACTUAL GAS VELOCITY OF STACK INSIDE8.14
= m/sec 5. DRAFT LOSS OF STACK 1) GAS FLOW RATE (NM3/Hr) Q = 11000.0 NM3/HR 2) AVER. FLUE GAS TEMP (℃) T= (150+145.5)/2 = 146.9 ℃ FLUE GAS PRESSURE(mmAQ) p= 0 mmAQ 2 3) SECTIONAL AREA OF STACK (M ) A= 0.58 M2 STACK INSIDE DIAMETER(TOP) (mm) D= 860 mm 4) FLUE GAS VISCOCITY (M2/sec) υ=( μ/ρ)=(μg/Υ) = 2.40E-05 5) STACK INSIDE VELOCITY (m/sec) Vo= 8.14 m/sec 7) ROUGHNESS ε= 1 8) RE. NUMBER Re=(V x de / υ) = 196,717 3 9) FLUE GAS DENSITY (M /Kg) γo = 0.719 10) FRICTION FACTOR OF STACK λ=0.0055{1+(20000xε/de+10 6/Re)(1/3)}= 0.0223 11) DRAFT LOSS OF STCAK ※ STACK HEIGHT = 25.000 m △P = λ(L/D)x(γo x Vo2/2g) x (To/T) x (P/Po) = 2.26 mmAq
6. CHECK Info for item D :
THEORY DRAFT > DRAFT LOSS = 8.15mmAq > 2.26mmAq OK. Information of Chimney Item 12 (i ~vi)