You are on page 1of 1

GENERAL PLUMBING NOTES

1.0 GENERAL DETAIL A 5


1.1. ALL PLUMBING WORKS HEREIN SHALL BE EXECUTED IN 1.7. ALL PIPES SHALL BE INSTALLED AS INDICATED, ANY 50 300 P-03
ACCORDANCE WITH THE PROVISION OF THE LATEST EDIT RELOCATION REQUIRED FOR A PROPER EXECUTION. 10
OF THE PHILIPPINE PLUMBING CODE, NATIONAL BUILDING

12
DETAIL A 3
CODE AND OTHER REGULATION OF THE MUNICIPALITY. 1.8. ALL FIXTURES SHALL BE VENTED UNLESS OTHERWISE NOTED, IDA255MPG SUMP GRATING
P-03

1.2. COORDINATE ALL DRAWINGS AND SPECIFICATION. THE 1.9. ALL WATER PIPES SHALL PROVIDE 30mm PIPE EXTENSION L30 X 30 X 4.5mm THK.
LINE OF CHB ANGULAR RAME
PLUMBING ENGINEER SHALL BE NOTIFIED IMMEDIATELY IF WITH CAP.

340
378
WALL BELOW
ANY DISCREPANCY FOUND HEREIN.
L30 X 30 X 4.5mm THK. DOWEL BARS
1.10. ALL WATER PIPES SHOULD BE HYDROSTATICALLY TESTED

100
1.3. ALL PLUMBING PIPES SHALL BE INSTALLED IN ANY TO A PRESSURE OF 1030 KPA FOR 2 HRS. MINIMUM. ANGULAR RAME
ALUMINUM WINDOW CREEN
RELOCATION REQUIRE FOR PROPER EXECUTION OF OTHER MESH SIZE 20

10
TRADE AND SHALL BE WITH THE PRIOR APPROVAL OF 1.11. ALL WATER TANKS SHALL BE THOROUGHLY FLUSHED AND DOWEL BARS
THE OWNER AND SANITARY ENGINEER. DISINFECTED. 350
10 400 50mm THK. GRAVEL BEDDING
411

400
1.4. THE PROPOSED PLUMBING UTILITIES SHALL CONFORM TO 1.12. ALL SANITARY AND STORM DRAINAGE PIPE SHALL BE
THE ACTUAL LOCATION DEPTH AND INVERT ELEVATION HYDROSTATICALLY TESTED (AT LEAST 3.00 M HIGH) TO
OF ALL EXISTING PIPES AND STRUCTURES AS VERIFIED INSURE THAT THE SYSTEM IS WATER TIGHT. 150mm THK. CHB W/
BY THE GENERAL CONTRACTOR.
1.13. WORKMANSHIP, THE WORK SHALL BE EXECUTED IN THE P CATCH BASIN PLAN 10mmØ HOR. & VER.
REBARS
1 SCALE 1:10mts.

100
1.5. THE PLUMBING CONTRACTOR SHALL VERIFY ALL EXISTING BEST AND THOROUGH MANNER TO SATISFY THE
UTILITIES AT THE SITE AND COORDINATE THE WORKS WITH ARCHITECT AND ENGR.
THE SEWER LINE EFFLUENT DISPOSAL POINT AND WATERLINE 50mm THK. GRAVEL BEDDING
SERVICE CONNECTING POINT. 1.14. THE PLUMBING CONTRACTOR SHALL SECURE ALL LICENSES, 400
PERMITS, AND OTHER REQUIREMENTS NEEDED FOR THE 300 COMPACTED SUBGRADE
1.6. ALL SLOPES FOR HORIZONTAL DRAINAGE AND SEWER LINES PROPOSED PROJECT.
SHALL MAINTAIN A ONE (1%) SLOPES, UNLESS OTHERWISE 1.15. THE PLUMBING CONTRACTOR SHALL SUBMIT THE AS-BUILT

39 50 50 50 50 50 49 39
SPECIFIED HEREIN. DRAWINGS TO THE PLUMBING ENGINEER AND OR THE
OWNER. IDA255MPG CATCH BASIN
SUMP GRATING
SECTION THRU A

378
P
A. MATERIAL SPECIFICATIONS: 1 SCALE 1:10mts.

COLD WATER LINE --- SHALL BE POLYPROPYLENE PIPES (PPR) PN-20


W/ SUITABLE FITTINGS, BY VESBO
33 30 TYP 33
SEWER PIPES --- SHALL BE CONCRETE PIPES

STORM DRAINAGE --- SHALL BE POLYVINYL CHLORIDE (PVC) PIPES,


* IDA255MPG
PIPES SERIES 1000. (FOR APPROVED EQUAL)

VENT PIPES --- SHALL BE POLYVINYL CHLORIDE (PVC) PIPES NOTES:


SERIES 600.
FLAT BARS ARE WELDED TO TWIST RODS BY FORGED
WELDING TECHNOLOGY (PROCESS OF WELDING BY FUSION).
MATERIALS CONFORM W/ AS3769 GRADE 250, BS4360,
GRADE 43A STANDARDS & HOT-DIP GALVANIZED IN ACCORDANCE
B. FIXTURE CONNECTION SCHEDULE: W/ BS EN ISO 1461.

NOTES:
WASTE TRAP VENT CWL 1. ALL GRATINGS TO BE WEBFORGE IDA325MPG. SITE HERE
FIXTURE mm in mm in mm in mm in 2. ALL PANELS AND SAHLL BE BANDED.
3. ALL DIMENSIONS IN MILLIMETERS.
WATER CLOSET 100 4 INTEGRAL 50 2 20 3/4
STANDARD SYMBOLS:

LAVATORY 50 2 32 1 1/4 50 2 12 1/2


INDICATES DIRECTION OF SPAN

IDA225MPG SUMP GRATING


SYMBOLS & ABBREVIATIONS: P DETAIL A
GV GATE VALVE F FAUCET
1 SCALE 1:10mts.

WATER METER SHO SHOWER


400
CV CHECK VALVE DS DOWN SPOUT

BOOSTER PUMP CB CATCH BASIN 4.5 5


L30 X 30 X 4.5mm THK.
ANGULAR RAME
5 IDA255MPG
P VICINITY MAP
SUMP GRATING
1 SCALE NTS
30

PRESSURE TANK FD FLOOR DRAIN

FLOOR CLEAN OUT


30 340 30
FCO HB HOSE BIBB (CLEAR OPENING)
DOWEL BARS
URIN URINAL CWL COLD WATER LINE LATERAL TIES

TD TRENCH DRAIN DP DRAINAGE PIPE

WC WATER CLOSET SP SOIL PIPE IDA225MPG SUMP GRATING


LAV LAVATORY VSTR VENT STACK THRU ROOF P DETAIL B
1 SCALE 1:05mts.

APPROVED BY: PROJECT: APPROVED BY: NOTED BY: SHEET CONTENT: SHEET NO.

ericson c. joson SEAOIL PHILIPPINES, INCORPORATED RETAIL ENGINEERING DEPARTMENT


SEAOIL FILLING STATION
SEAOIL PHILIPPINES, INCORPORATED
22/f The Taipan Place,F.Ortigas Ave.,
sanitary engineer AS SHOWN
P 01
Ortigas Center, Pasig City reg. no.:0002542 issued on:01-03-2022 LOCATION: FRANCIS GLENN YU ENGR. MICHAEL RENEE M. LUCAS
ptr no.: 0154698 issued at:manila MOLO, ILO-ILO CHIEF EXECUTIVE OFFICER RENG MANAGER
CAD/DRAWN BY:
DESIGNED BY:
REVISED BY:
DATE:
4