Company: ENKA INSAAT VE SANAYI A.S. Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Specifier's comments:
1 Anchor Design
1.1 Input data
Anchor plate
CBFEM
: lx x ly x t = 580.0 mm x 690.0 mm x 50.0 mm;
Profile: IPBi/HEA, IPBI 400 / HE 400 A; (L x W x T x FT) = 390.0 mm x 300.0 mm x 11.0 mm x 19.0 mm
Base material: uncracked concrete, 4000, fc' = 4,000 psi; h = 2,000.0 mm
Reinforcement: tension: present, shear: present; anchor reinforcement: tension, shear
edge reinforcement: > No. 4 bar
CBFEM
- The anchor calculation is based on a component-based Finite Element Method (CBFEM)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Anchor forces are calculated based on a component-based Finite Element Method (CBFEM)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Variables
2 2
Ase,N [mm ] futa [N/mm ]
379 448.16
Calculations
Nsa [kN]
173.770
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
173.770 0.750 130.327 28.463
Variables
'
y c,p Abrg [mm ]
2
la fc [psi]
1.400 570 1.000 4,000
Calculations
Np [kN]
125.831
Results
Npn [kN] f concrete f Npn [kN] Nua [kN]
176.164 0.700 123.315 28.463
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Variables
'
ca1 [mm] ca2 [mm] Abrg [mm ]
2
la fc [psi] s [mm]
70.0 - 570 1.000 4,000 150.0
Calculations
agroup Nsb [kN]
1.357 116.634
Results
Nsbg [kN] f concrete f Nsbg [kN] Nua,edge [kN]
158.290 0.750 118.717 25.949
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Variables
2 2
Ase,V [mm ] futa [N/mm ]
379 448.16
Calculations
Vsa [kN]
173.770
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
173.770 0.650 112.950 14.510
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Nc0
ec,N y ed,N y c,N y cp,N Nb ] ACI 318-19 Eq. (17.7.3.1b)
f Vcpg ³ Vua ACI 318-19 Table 17.5.2
ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
2
ANc0 = 9 hef ACI 318-19 Eq. (17.6.2.1.4)
( )
1
'
y ec,N = 2 eN £ 1.0 ACI 318-19 Eq. (17.6.2.3.1)
1+
3 hef
ef
ACI 318-19 Eq. (17.6.2.4.1b)
= MAX(
c ) £
c 1.5h a,min ef
y cp,N , 1.0 ACI 318-19 Eq. (17.6.2.6.1b)
c ac ac
1.5
Nb = kc l a √ '
fc hef ACI 318-19 Eq. (17.6.2.2.1)
Variables
kcp hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm]
2 250.0 99.0 2.0 70.0
'
y c,N cac [mm] kc la fc [psi]
1.250 ∞ 24 1.000 4,000
Calculations
ANc [mm ]
2
ANc0 [mm ]
2
y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
1,074,000 562,500 0.791 0.995 0.756 1.000 208.491
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
592.137 0.700 414.496 158.632
1.5 Combined tension and shear loads, per ACI 318-19 section 17.8
z z
bNV = bN + bV <= 1
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
1.6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates as per current regulations (ETAG 001/Annex C, EOTA
TR029, etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor
plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above.
The proof if the rigid base plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the
potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or
where pullout or pryout strength governs.
• For additional information about ACI 318 strength design provisions, please go to
https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• Attention! In case of compressive anchor forces a buckling check as well as the proof of the local load transfer into and within the base
material (incl. punching) has to be done separately.
• The design of Anchor Reinforcement is beyond the scope of PROFIS Engineering. Refer to ACI 318-19, Section 17.5.2.1 (a) for information
about Anchor Reinforcement.
• The design of Anchor Reinforcement is beyond the scope of PROFIS Engineering. Refer to ACI 318-19, Section 17.5.2.1 (b) for information
about Anchor Reinforcement.
• Anchor Reinforcement has been selected as a design option, calculations should be compared with PROFIS Engineering calculations.
• The anchor design methods in PROFIS Engineering require rigid anchor plates, as per current regulations (AS 5216:2021, ETAG 001/Annex
C, EOTA TR029 etc.). This means that the anchor plate should be sufficiently rigid to prevent load re-distribution to the anchors due to
elastic/plastic displacements. The user accepts that the anchor plate is considered close to rigid by engineering judgment."
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Hilti AWS welded headed stud anchor with 250 mm embedment, 7/8, Steel galvanized, installation per instruction for use
y
290.0 290.0
120.0
12 8 4 13
345.0
150.0
11 7 3 14
150.0
10 6 2 15
150.0
345.0
9 5 1 16
120.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
2.2 Summary
Description Profile Anchor plate Concrete [%]
sEd [N/mm²] ePl [%] sEd [N/mm²] ePl [%] Hole bearing [%]
1 Only Gravity 150.17 0.00 19.49 0.00 2 1
2 1.0 Gravity+1.0 166.67 0.00 15.75 0.00 2 2
Service
3 1.0 Gravity -1.0 146.66 0.00 20.10 0.00 2 1
Service
4 1.2 Gravity+1.6 185.19 0.00 22.31 0.00 2 2
Service
5 1.2 Gravity -1.6 174.35 0.00 24.15 0.00 2 1
Service
2.3 Anchor plate classification
Results below are displayed for the decisive load combinations: 1.2 Gravity -1.6 Service
Anchor tension forces Equivalent rigid anchor plate (CBFEM) Component-based Finite Element Method
(CBFEM) anchor plate design
Anchor 1 2.319 kN 0.000 kN
Anchor 2 5.692 kN 4.320 kN
Anchor 3 9.066 kN 16.861 kN
Anchor 4 12.438 kN 12.789 kN
Anchor 5 0.000 kN 3.321 kN
Anchor 6 3.226 kN 7.662 kN
Anchor 7 6.598 kN 4.873 kN
Anchor 8 9.970 kN 0.581 kN
Anchor 9 0.000 kN 7.767 kN
Anchor 10 0.759 kN 9.784 kN
Anchor 11 4.131 kN 0.000 kN
Anchor 12 7.502 kN 0.000 kN
Anchor 13 14.906 kN 25.167 kN
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Anchor tension forces Equivalent rigid anchor plate (CBFEM) Component-based Finite Element Method
(CBFEM) anchor plate design
Anchor 14 11.533 kN 27.940 kN
Anchor 15 8.159 kN 2.007 kN
Anchor 16 4.785 kN -0.002 kN
User accepted to consider the selected anchor plate as rigid by his/her engineering judgement. This means the anchor design guidelines can
be applied.
2.4 Profile/Stiffeners/Plate
Profile and stiffeners are verified at the level of the steel to concrete connection. The connection design does not replace the steel design for
critical cross sections, which should be performed outside of PROFIS Engineering.
317.16 N/mm²
0.00 N/mm²
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
5.00%
0.00%
2.4.2 Plate hole bearing resistance, AISC 360-16 Section J3
Decisive load combination: 5 - 1.2 Gravity -1.6 Service
Equations
FRn = 0.75 Rn
V ≤ FRn
Variables
lc [mm] t [mm] Fu [N/mm²] d [mm] Rn [kN]
Anchor 1 450.5 50.0 399.90 22.2 1,066.523
Anchor 2 126.2 50.0 399.90 22.2 1,066.523
Anchor 3 126.2 50.0 399.90 22.2 1,066.523
Anchor 4 115.7 50.0 399.90 22.2 1,066.523
Anchor 5 311.6 50.0 399.90 22.2 1,066.523
Anchor 6 126.2 50.0 399.90 22.2 1,066.523
Anchor 7 262.1 50.0 399.90 22.2 1,066.523
Anchor 8 120.9 50.0 399.90 22.2 1,066.523
Anchor 9 517.0 50.0 399.90 22.2 1,066.523
Anchor 10 414.9 50.0 399.90 22.2 1,066.523
Anchor 11 260.2 50.0 399.90 22.2 1,066.523
Anchor 12 103.8 50.0 399.90 22.2 1,066.523
Anchor 13 113.0 50.0 399.90 22.2 1,066.523
Anchor 14 126.2 50.0 399.90 22.2 1,066.523
Anchor 15 126.2 50.0 399.90 22.2 1,066.523
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
12
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 13
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Results
V [kN] FRn [kN] Utilization [%] Status
Anchor 1 11.787 799.892 2 OK
Anchor 2 11.277 799.892 2 OK
Anchor 3 11.320 799.892 2 OK
Anchor 4 11.907 799.892 2 OK
Anchor 5 9.256 799.892 2 OK
Anchor 6 8.589 799.892 2 OK
Anchor 7 8.647 799.892 2 OK
Anchor 8 9.403 799.892 2 OK
Anchor 9 6.941 799.892 1 OK
Anchor 10 6.101 799.892 1 OK
Anchor 11 6.168 799.892 1 OK
Anchor 12 7.151 799.892 1 OK
Anchor 13 14.506 799.892 2 OK
Anchor 14 14.107 799.892 2 OK
Anchor 15 14.049 799.892 2 OK
Anchor 16 14.381 799.892 2 OK
2.5 Concrete
Decisive load combination: 2 - 1.0 Gravity+1.0 Service
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
13
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 14
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
0.00 N/mm²
2.5.2 Concrete block compressive strength resistance check, AISC 360-16 Section J8
Equations
Fp = F fp,max
A A
2 2
fp,max = 0.85 fc' √( ) ≤ 1.7 fc; √( )≤2
A A
1 1
N
s = A
1
Utilization =
s
Fp
Variables
N [kN] fc' [N/mm²] F A1 [mm²] A2 [mm²]
26.191 27.58 0.65 125,818 96,112
Results
Load combination Fp [N/mm²] s [N/mm²] Utilization [%] Status
1.0 Gravity+1.0 Service 13.32 0.21 2 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
14
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 15
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
2.7 Warnings
● By using the CBFEM calculation functionality of PROFIS Engineering you may act outside the applicable design codes and your specified
anchor plate may not behave rigid. Please, validate the results with a professional designer and/or structural engineer to ensure suitability
and adequacy for your specific jurisdiction and project requirements.
● The anchor is modeled considering stiffness values determined from load displacement curves tested in an independent laboratory.
Please note that no simple replacement of the anchor is possible as the anchor stiffness has a major impact on the load distribution
results.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
15
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 16
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
3 Summary of results
Design of the anchor plate, anchors, welds and other elements are based on CBFEM (component based finite element method) and AISC.
Load combination Max. utilization Status
Anchors 1.2 Gravity -1.6 Service 39% OK
Anchor plate 1.2 Gravity -1.6 Service 10% OK
Concrete 1.0 Gravity+1.0 Service 2% OK
Profile 1.2 Gravity+1.6 Service 59% OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
16
Hilti PROFIS Engineering 3.0.88
www.hilti.com
Company: ENKA INSAAT VE SANAYI A.S. Page: 17
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CG7 Date: 11/10/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
17