FAT REPORT
SMART
OH-LBS/LINE-SECTIONALIZER
Rated Voltage: __________ KV
Unit SN:
Date of Testing:
Testing for: Mass Production FAT ( ) / Prequalification FAT ( )
Manufacturer:
Location:
Signature: Signature:
Signature: Signature:
Manufacturer:
Name: Name:
Signature: Signature:
1
Classified as Confidential Internal by SEC - )الشركة السعودية للكهرباء مصنف مقيد (داخلي
Main Circuit
R-GND Y-GND B-GND Accepted
Before HI-POT After HI-POT Before HI-POT After HI-POT Before HI-POT After HI-POT
Testing conditions: Secondary wiring OPEN & Main body for the CPT is grounded (GND).
2
Classified as Confidential Internal by SEC - )الشركة السعودية للكهرباء مصنف مقيد (داخلي
2. Dielectric( HI-POT)Test:
Rated Voltage: KV
Applied Voltage: 38 KV for Rated Voltage 17.5 KV
Applied Voltage: 70 KV for Rated Voltage 36 KV
Testing conditions: All switching devices are Close (LBS and CB) and Earth switch is OFF & Main body is grounded (GND).
N
SwitchingDevice ANY BREAKDOWN
No. Tested Phase Other Phases
Status (LBS & CB) ACCEPTED
1 Closed R Y&B short with
GND (body)
2 Closed Y R&B short with
GND (body)
3 Closed B Y&R short with
GND (body)
Applied HI-POT
voltage value ANY BREAKDOWN ACCEPTED
3
Classified as Confidential Internal by SEC - )الشركة السعودية للكهرباء مصنف مقيد (داخلي
4
Classified as Confidential Internal by SEC - )الشركة السعودية للكهرباء مصنف مقيد (داخلي
AUTOMATION
Product Item: RTU (……………………) Serial No. :
OH-LBS/Sectionalizer ( Open )
OH-LBS/Sectionalizer ( Close )
COMMAND (DO)
Local (Laptop) Remote (DCC)
OH-LBS/Sectionalizer ( Open )
OH-LBS/Sectionalizer ( Close )
Result
Status Input (DI) (OK-Fail)
Local Indication Remote (DCC)
OH-LBS/Sectionalizer
Open status
Close status
Remote status
Local status
OH-LBS mode status
Line-Sectionalizer mode status
Common (Indication / Alarms)
LOCK/UNLOCK Common
Battery low Alarm
Gas Low ( if the Sectionalizer is SF6) Alarm
AC Power Fail Alarm
Door open Alarm
RTU Self Diagnostic (RTU Alarm) Alarm
DC Power Fail Alarm
Motor/Actuator(Open/Close) Circuit Fail Alarm
Phase loss (miss-phase) Alarm
Over Current (load) Alarm
Unbalance (load) Alarm
Undervoltage Alarm
Fault indication Alarm
Dismatch phases Between Phases: (R-S-T) (U-V-W)
Negative Seq Voltage Protection Alarm
5
Classified as Confidential Internal by SEC - )الشركة السعودية للكهرباء مصنف مقيد (داخلي HQ. : Smart Grid Dept.
إدارة الشبكات الذكيّة: المركز الرئيس
Reading
(AI) Analog input Result
Local Remote DCC SEC(Specs) (OK, fail)
Current A ±3%
Current B ±3%
Current C ±3%
Neutral Current ±3%
Voltage A ±3%
Voltage B ±3%
Voltage C ±3%
Voltage ( N ) ±3%
Voltage ( U-V ) ±3%
Voltage ( V-W ) ±3%
Voltage ( U-W ) ±3%
Voltage ( N ) ±3%
Counter (setting number) 1-2-3
Reading
Measurement Calculated
Remote Result
Local Formula (OK, Fail)
DCC
OH-LBS/Sectionalizer
The following
Active Power (W) is Total of
three phase:
Reactive Power (KVar)
P: Active Power
Q: Reactive Power
Cos(ρ): power factor
Power Factor P=V*I* Cos(ρ)
Cos(ρ)=P/S
6
Classified as Confidential Internal by SEC - )الشركة السعودية للكهرباء مصنف مقيد (داخلي HQ. : Smart Grid Dept.
إدارة الشبكات الذكيّة: المركز الرئيس
• The sectionalizer counts each over current interruption of the back-up re-closing device and will open
after a preset number of counts have been registered, within a pre -determined time span. The
sectionalizer shall only lockout during the open interval of the re-closing back-up device.
• Total number of counts to opening, adjustable to 1, 2 or 3. Each instantaneous (fast) and delayed
interruption of back-up device will be counted individually.
• Minimum actuating-current settings: phase fault sensing; adjustable form 16 to 640 Amps.
Auto-Recloser Sequence
Current
Load
Time
Line-Sectionalizer Sequence
7
Classified as Confidential Internal by SEC - )الشركة السعودية للكهرباء مصنف مقيد (داخلي HQ. : Smart Grid Dept.