You are on page 1of 2

Report No: SHEET 1 OF 2

114486/UT/005

Doosan Babcock Client:CLP Power Hong Kong LTD


Service Technology
Test Location: BPPS
Porterfield Road, Renfrew, United Kingdom, PA4 8DJ
Contract Name: Black Point – C2 Inspection
Telephone: +44 (0)141 886 4141
Facsimile: +44 (0)141 885 3700 Project/Sub-Project/Activity: 114486
Test Date(s): 17 & 18-02-2023
REPORT OF ULTRASONIC TEST
Section 1 - Component Details
Component Deaerator Storage Tank Manufacturing Stage In Service Weld Type Butt Weld
Material ASTM A182 Grade F22 Dimensions (t x dia.) T= 16mm Surface Condition & Dressed
temperature
Drawing No N/A Welding Process T.I.G / M.M.A.W Heat Treatment N/A

Section 2 - Equipment Details


Flaw Detector Make & Model No: SIUI CTS-9006 Couplant: UCA2M
Flaw Detector Unique ID: N-001-38
Calibration Block Type: BS2704: 1978 A2 & A4 Block Reference Block Type: Dia 3mm Side Drilled Holes DAC Block
Calibration Block Unique ID: N-003-38 & 49 Reference Block Unique ID: N-003-23
Unique ID 69524 69528 23234 9901455
Make GBSS60 GBSS70 GBSS45 GBTC10-5
Wave Mode Shear Shear Shear Compression
Angle o 60˚ 70˚ 45˚ 0˚
Probe
Frequency (MHz) 4MHZ 4MHZ 4MHZ 5MHZ
Details
Crystal size (mm) 10mm 10mm 10mm 10mm
Twin or Single Single Single Single Twin
Focal range (mm) N/A N/A N/A N/A
Timebase range 0-150mm 0-150mm 0-100mm 0-100mm
Equipment complies with OP-303-0454-300 (Rev A) YES/NO

Section 3 - Inspection Details


Reference Sensitivity dB 44 50 48.5 50
Scanning Sensitivity dB 58 64 62.4 50

Extent of Testing: 100% Location of Scanning Areas: N/A Reference Points:0°TDC+CWF


Procedure: Technique (if applicable): WI-303-0454-305-001 Rev B Acceptance Standard:
OP-303-0454-305 Rev B Report All In Service Indications

Section 4 - Inspection Results (incl. Parent Material Check & Any Test Limitations / Deviations)
1. Penetration Weld : P17, P22, P23, P49 & P52 (See attached sketch - No Recordable Indication)
2. Circumference Weld : C1 & C3 (See attached sketch - No Recordable Indication)
3. Longitudinal Junction Weld : L1 (See attached sketch - No Recordable Indication)

Role Name Job Title PCN/ASNT Employer Signature Date


No.

Tested by: L.K.Cheung PCN-UT-Level II 315592 Fugro

Approved by: CHANDRASEKHARAN P NDT Coordinator 315535 Altrad


Babcock

Client (if required):

Doosan-AMBER
F-303-0454-000-01 ASG Technology Rev C
Doosan-AMBER
F-303-0454-000-01 ASG Technology Rev C