Professional Documents
Culture Documents
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
SPOOL CONFIGURATION
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
METER IN & METER OUT (SYMMETRIC) SPOOL
A B
A B T P T
20N
This is the most common proportional valve
P T This is the most common proportional valve
spool where, for a given opening, the
spool where, for a given opening, the
restriction in all flow paths will be equal.
restriction in all flow paths will be equal.
For an equal area actuator (eg. motor) this
For an equal area actuator (eg. motor) this
will provide both meter-in and meter-out
will provide both meter-in and meter-out
control, For an unequal area actuator
control, For an unequal area actuator
(cylinder), the control will be
(cylinder), the control will be
predominantly meter-in or meter-out
predominantly meter-in or meter-out
depending upon the direction of movement.
depending upon the direction of movement.
METER OUT SPOOL
A B
A B T P T
28S
A B
A B T P T
22A
A B
A B T P T
20N10
A B
8 bar
P T
SYMMETRIC SPOOL
When the cylinder
When the cylinder
retracts, the hydrostat 2 : 1
retracts, the hydrostat
will maintain a constant 8
will maintain a constant 8
bar differential pressure
bar differential pressure
across the P to B flow path
across the P to B flow path
of the proportional valve.
of the proportional valve.
A B
P = 8 bar
8 bar
P T
SYMMETRIC SPOOL
Since the A to T flow is
Since the A to T flow is
double the P to B flow (for 2 : 1
double the P to B flow (for
a 2:1 area ratio cylinder),
a 2:1 area ratio cylinder),
the pressure drop A to T
the pressure drop A to T
will be 4 times the P to B
will be 4 times the P to B
pressure drop ie. 32 bar.
pressure drop ie. 32 bar.
A B
P = 32 bar
8 bar
P T
SYMMETRIC SPOOL
1) A back pressure of 32
1) A back pressure of 32
bar in the full bore side of 2 : 1
bar in the full bore side of
the cylinder requires a
the cylinder requires a
pressure of 64 bar in the
pressure of 64 bar in the
annulus side.
annulus side.
32 bar 64 bar
2) Which therefore
2) Which therefore
means a minimum P port
means a minimum P port
pressure of 72 bar is
pressure of 72 bar is
required simply to move
required simply to move
the cylinder with no
the cylinder with no
load. A B
load.
72 bar
P = 32 bar
8 bar
P T
ASYMMETRIC SPOOL
If the proportional valve
If the proportional valve
spool is changed to an 2 : 1
spool is changed to an
asymmetric spool (with a
asymmetric spool (with a
2:1 ratio, the pressure
2:1 ratio, the pressure
drop P to B will still be 8
drop P to B will still be 8
bar as determined by the
bar as determined by the
hydrostat.
hydrostat.
A B 2:1 SPOOL
P = 8 bar
8 bar
P T
ASYMMETRIC SPOOL
However, a 2:1 spool with a
However, a 2:1 spool with a
2:1 cylinder means that 2 : 1
2:1 cylinder means that
the A to T pressure drop
the A to T pressure drop
will now also be 8 bar.
will now also be 8 bar.
A B 2:1 SPOOL
P = 8 bar
8 bar
P T
ASYMMETRIC SPOOL
The 8 bar back
The 8 bar
pressure in the full
back 2 : 1
pressure in the full
bore side of the
bore side of the
cylinder required 16 bar
cylinder required 16 bar
in the annulus side and
in the annulus side and
therefore a minumum P
therefore a minumum P
port pressure of 24 bar. 8 bar 16 bar
port pressure of 24 bar.
Use of an asymmetric
Use of an asymmetric
spool has thus reduced
spool has thus reduced
the minimum P port
the minimum P port
pressure from 72 bar to
pressure from 72 bar to
24 bar.
24 bar.
A B 2:1 SPOOL
24 bar
P = 8 bar
8 bar
P T
SPOOL OPTIONS
A B A B
T P T T P T
The choice of spool
20N The choice of spool
metering characteristics is 28S
metering characteristics is
therefore determined by
therefore determined by
the type of actuator and
the type of actuator and
the nature of the load.
A B the nature of the load. A B
T P T T P T
22A 20N10
SPOOL CENTRE CONDITION
A B A B A B
P T P T P T
2C 33C 5C
Different centre condition options are also available with
Different centre condition options are also available with
most proportional directional valves. The correct choice
most proportional directional valves. The correct choice
depends again mainly on the load characteristics and
depends again mainly on the load characteristics and
auxiliary valves in the system. For example, where the
auxiliary valves in the system. For example, where the
proportional valve is used to prevent actuator movement
proportional valve is used to prevent actuator movement
a 2C spool could be used but where solenoid or pilot
a 2C spool could be used but where solenoid or pilot
operated check valves are used a type 33C spool may be
operated check valves are used a type 33C spool may be
more appropriate.
more appropriate.
RATED FLOW
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
SPOOL FLOW RATING
2) Different flow ratings are achieved by varying
2) Different flow ratings are achieved by varying
the size, shape or number of the spool metering
QR litres / min the size, shape or number of the spool metering
notches.
notches.
A B
5 bar P
P T
A1
V1
Q1
QR = ?
A1 A2
A1 A2
P1.A1 P2.A2 F
P1 P2
PP1.A.A1 ==P
P 2.A
.A2 ++FF
1 1 2 2
A1 A2
P1 Q. A2 P2
Q A1
PP1.A.A1 ==P
P 2.A
.A2 ++FF
1 1 2 2
P Q2
2
P2 – PT A2
PS PT =
PS – P1 A1
Q
POWER CAPACITY NON-FEEDBACK VALVE
1) The spool then opens 3) However, as flow
1) The spool then opens 3) However, as flow
until the solenoid force passes through the
until the solenoid force passes through the
and spring compression valve, flow forces also
and spring compression valve, flow forces also
force balance. act on the spool to
force balance. act on the spool to
oppose the solenoid
oppose the solenoid
force.
force.
P
2) At maximum opening
2) At maximum opening
the flow rate through the
the flow rate through the
valve will then be
valve will then be
proportional to the square
proportional to the square
root of the pressure
root of the pressure
difference across the
difference across the
valve.
valve.
Q
POWER CAPACITY NON-FEEDBACK VALVE
P
Q
POWER CAPACITY NON-FEEDBACK VALVE
Q
POWER CAPACITY FEEDBACK VALVE
P
Q
POWER CAPACITY FEEDBACK VALVE
Q
POWER CAPACITY FEEDBACK VALVE
Q
POWER CAPACITY FEEDBACK VALVE
Q
OPEN AND CLOSED LOOP CONTROL
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
OPEN LOOP CONTROL
1) In an open loop control system, an input voltage to the
RAMP 1) In an open loop control system, an input voltage to the POSITION
amplifier creates a current to the proportional valve which
amplifier creates a current to the proportional valve which
regulates flow to the actuator thus controlling the actuator
regulates flow to the actuator thus controlling the actuator ACCELERATION
velocity.
velocity.
CURRENT FLOW VELOCITY
VOLTAGE
PID
CURRENT FLOW VELOCITY
_ VOLTAGE VELOCITY
+
VOLTAGE
_ VOLTAGE POSITION
+
VOLTAGE 2) In most applications the amplifier will simply
2) In most applications the amplifier will simply
produce an output current proportional to the
produce an output current proportional to the
position error (input minus feedback). Positional
position error (input minus feedback). Positional
accuracy will therefore be much greater than
VOLTAGE accuracy will therefore be much greater than
with an open loop system.
with an open loop system.
3) In certain situations however, the amplifier integral and derivative functions can be
3) In certain situations however, the amplifier integral and derivative functions can be
used to enhance system performance but such applications require a relatively high level of
used to enhance system performance but such applications require a relatively high level of
expertise.
expertise.
The amplifier ramp generator can also be used to control the actuator velocity during
The amplifier ramp generator can also be used to control the actuator velocity during
movement from one position to another.
movement from one position to another.
CLOSED LOOP CONTROL - FORCE
RAMP
RATE OF CHANGE
OF FORCE
PID
CURRENT PRESSURE FORCE
FORCE
_ VOLTAGE
+
VOLTAGE
VOLTAGE Closed loop force control systems can use either a pressure or force
Closed loop force control systems can use either a pressure or force
transducer to provide a feedback signal. If the control is achieved using a
transducer to provide a feedback signal. If the control is achieved using a
spool type directional valve then the amplifier will normally provide an output
spool type directional valve then the amplifier will normally provide an output
consisting of both proportional and integral terms.
consisting of both proportional and integral terms.
As before, the ramp generator will provide control over the rate of change
As before, the ramp generator will provide control over the rate of change
of actuator force.
of actuator force.
VALVE RESPONSE
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
STEP RESPONSE
INPUT OUTPUT
time
STEP RESPONSE
INPUT OUTPUT
100%
90%
In other cases the output may
In other cases the output may
FLOW
time
T
FREQUENCY RESPONSE
75%
50%
25%
time
FLOW (P to B)
75%
A1
A2
50%
25%
360º
L
1) But as the input frequency increases, the amplitude of the output time
1) But as the input frequency increases, the amplitude of the output
FLOW (P to B)
is reduced and also the output starts to lag behind the input.
is reduced and also the output starts to lag behind the input.
Phase Lag (º )
-3 135
90
Bandwidth
45
1 10 100 1 10 100
Frequency (Hz) Frequency (Hz)
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
LINEARITY
E x 100
LINEARITY (%) =
QMAX
Input Signal
REPEATABILITY
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
REPEATABILITY
E
QMAX
Signal
Output Flow
E x 100
REPEATABILITY (%) =
QMAX
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
REPRODUCIBILITY
E
QMAX
Signal
Output Flow
E x 100
REPRODUCIBILITY (%) =
QMAX
Successive applications
of signal
(different valve) Reproducibilty is a similar
Reproducibilty is a similar
measurement but relates to the
measurement but relates to the
same signal applied to different
same signal applied to different
valves.
valves.
HYSTERESIS
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
HYSTERESIS
QMAX
E x 100
HYSTERESIS (%) =
IMAX
PRESSURE GAIN
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
PRESSURE GAIN
The Pressure Gain of a valve is a
The Pressure Gain of a valve is a
measure of how quickly the spool
measure of how quickly the spool
opens and closes the service
opens and closes the service
ports of the valve as the spool
ports of the valve as the spool
moves away from the centre
moves away from the centre
position.
position.
PRESSURE GAIN
As the spool moves away from
As the spool moves away from
centre, port (A) will be gradually
centre, port (A) will be gradually
opened up to (P) and closed off
opened up to (P) and closed off
from (T) whereas the opposite
from (T) whereas the opposite
will happen to port (B).
will happen to port (B). AA BB
TT PP TT
PRESSURE GAIN
Once the spool has moved a certain
Once the spool has moved a certain
distance (typically 3 - 4% of its total
distance (typically 3 - 4% of its total
travel), port (A) will be at full pressure
travel), port (A) will be at full pressure
and port (B) at tank pressure. A high
and port (B) at tank pressure. A high
pressure gain is required in many closed
pressure gain is required in many closed AA P BB
loop control systems so that the valve
loop control systems so that the valve
will respond to correct even very small
will respond to correct even very small
errors.
errors.
P
PS
TT PPS
P TT
1 2 3 4
% Input
SPOOL LAP
Spool Configuration
Rated Flow
Power Capacity
Open Loop / Closed Loop
Valve Response
Linearity
Repeatability
Reproducibility
Hysteresis
Pressure Gain
Spool Lap
SPOOL LAP
Output Pressure
ap
er L
OVER LAP
U nd
L ap
er
Ov
UNDER LAP
Input Signal
The Lap Condition of the spool will affect the Pressure Gain as can be seen. The over-lapped spool will
The Lap Condition of the spool will affect the Pressure Gain as can be seen. The over-lapped spool will
have a deadband region where the output does not change until a certain input signal level is reached.
have a deadband region where the output does not change until a certain input signal level is reached.
Valves for use in open loop control systems often use an over-lapped spool (to reduce leakage) but use
Valves for use in open loop control systems often use an over-lapped spool (to reduce leakage) but use
electronic compensation to reduce the effective deadband. Closed loop control valves however normally
electronic compensation to reduce the effective deadband. Closed loop control valves however normally
use under-lapped spools for optimum control.
use under-lapped spools for optimum control.
APPLICATION GUIDELINES
YES This chart indicates typical application areas for the different type of proportional
This chart indicates typical application areas for the different type of proportional
VALVE
valves. As always however, there will be exceptions to these guidelines.
MAYBE valves. As always however, there will be exceptions to these guidelines.
NO
CONTROL
SHOCK
ACCEL.
O/LOOP
SPEED
C/LOOP
SPEED
C/LOOP
POSITION
C/LOOP
PRESSURE
PROPORTIONAL VALVE SELECTION FACTORS