You are on page 1of 2

JOB NO.

W023
TITLE RCC Design of CABLE TRENCH for MCC Room
SHEET NO.
REVISION 0
PROJECT
THIS DOCUMENT IS MBE'S PROPERTY AND MUST NOT BE USED EXCEPT IN
PREPARED A.M.
CONNECTION WITH MBE'S WORK.REPRODUCTION, USE OR DISCLOSURE OF
DOCUMENT APPROVED R.K.B.
THE CONTENT OFTHIS DOCUMENT TO THIRD PARTY/IES WITHOUT
NO.
EXPRESS/WRITTEN PERMISSION OF MBE IS STRICTLY PROHIBITED. DATE 2/12/2024

DESIGN OF R.C.C. CABLE TRENCH: W 1500 x D 1500

Surcharge = 1 T/m2
1500
Unit wt. of water = 1 T/m3

150

150 150 1.5 t/m2 0.750 0.50 t/m2


1650 (earth) t/m2 (Surcharge)
1500 (water)

Grade of concrete M25 25 N/mm2


Grade of steel Fe500 500 N/mm2

Submerged unit wt. of soil gd 1 t/m3


Coefficient of Earth Pressure = 0.5

Depth 150 mm
Effective cover 40 mm
Effective depth 105 mm
Width 1000 mm

DESIGN OF SIDE WALL:

Moment at bottom of wall = 1.398 t m/m


Mu/bd2 = 1.902 N/mm2
pt = 0.484
Ast (Required) = 5.1 cm2

PROVIDED 10 DIA. @ 150 mm C/C 5.23 cm2 ( pt = 0.498 ) AT BOTTOM. O.K.

Check for shear :


Shear at the face of support = 2.438 T
Nominal shear stress.tv = 0.35 N/mm2
tc = 0.85*Ö(0.8fck(Ö(1+5b)-1)/6b = 0.482 N/mm2
where, b = 0.8 fck/ 6.89pt = 5.997
where, Total pt = 0.484
Shear Capacity= 7.24 T > 2.44 T OK
JOB NO. W023
TITLE RCC Design of CABLE TRENCH for MCC Room
SHEET NO.
REVISION 0
PROJECT
THIS DOCUMENT IS MBE'S PROPERTY AND MUST NOT BE USED EXCEPT IN
PREPARED A.M.
CONNECTION WITH MBE'S WORK.REPRODUCTION, USE OR DISCLOSURE OF
DOCUMENT APPROVED R.K.B.
THE CONTENT OFTHIS DOCUMENT TO THIRD PARTY/IES WITHOUT
NO.
EXPRESS/WRITTEN PERMISSION OF MBE IS STRICTLY PROHIBITED. DATE 2/12/2024

DESIGN OF BASE OF TRENCH

Self weight of trench = 1.69 t/m


Live load over trench = 1 t/m
Total 2.69 t/m
Upward pressure = 1.65 t/m2
Net pressure = 1.04 t/m2
Free B.M at span = 0.353 t m/m
Mu/bd2 = 0.480 N/mm2
pt = 0.120
Ast (Required) = 1.3 cm2

PROVIDED 8 DIA. @ 250 mm C/C 2.01 cm2 ( pt = 0.191 ) AT BOTTOM. O.K.

Distribution Steel:

Distribution reinforcement= 0.060 % of gross cross sectional area on each face


Ast required = 0.06*150*1000/100 90.00 mm2
Spacing required = 558 mm

Provide 8 mm dia 250 mm c/c as distribution reinforcement OK

10 @ 150 c/c

8 @ 250 c/c
8 @ 250 c/c
1500

8 @ 250 c/c

1500

8 @ 250 c/c

8 @ 250 c/c