You are on page 1of 11

PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL

EMPLOYER ALDAR DATE 18.11.2021


PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 1 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

SS-RD 3604
LV SWITCHGEAR

1. VISUAL INSPECTION

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021
PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL
EMPLOYER ALDAR DATE 18.11.2021
PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 2 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

SI. No Description Yes No Remarks


Principle dimension of switchboard as per manufacturing
1
document (Height, width, depth) ✔

2 Paint shade( RAL 7032) as per specification ✔

3 Lifting lugs available ✔

4 Rating plate & name plate as per manufacturing document ✔

Compartment size and location according to front view


5
drawings ✔

Technical data of main circuit devices according to switchboard


6
Drawings ✔

Equipment designation according to drawings complete visible


7
and legible for main circuit devices ✔

Feeder Identification labels and panel mounting devices are


8
provided with labels on front, rear and on the device ✔

Mimic diagram & cubicle labeling as per manufacturing


9
document ✔

10 Warning labels are in place ✔

11 Installation and fixing of equipment tightness checked ✔

12 Earth bar is continuous. ✔


LV PANEL FUNCTIONAL TESTS

1. Name Plate Details:

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021
PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL
EMPLOYER ALDAR DATE 18.11.2021
PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 3 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

Make AL HAMAD
Rated Voltage 440 V
Normal Current rating of load 2700 A
Normal Current rating of Bus bar 2700 A
Rated short circuit current 50 KA
Frequency 50 Hz
Year of manufacturing 10/2020
Serial No. LVAC-124/20/003

2. Functional Checks:
SI No. DESCRIPTION REMARKS
1 Manual close/open operation of the Incomer OK
1 Voltmeter function OK
3 Ammeter function OK
4 Control wiring checks OK
5 Indication lamps OK
6 Panel heater function OK
7 Bus bar tightness OK
8 Earthing of panel OK
9 Fuse rating verification OK
10 Phase Sequence Check OK
11 Continuity Test OK

Remarks:-

3. BUSBAR TORQUE MEASURMENT CHECK:

Sl.No. FEEDER REFERENCE L1-L1(Nm) L2-L2(Nm) L3-L3 (Nm) Neutral (Nm)


1 Incomer-1 to Outgoing-1 Busbar 70 70 70 70

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021
PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL
EMPLOYER ALDAR DATE 18.11.2021
PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 4 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

2 Incomer-2 to Outgoing-2 Busbar 70 70 70 70


3 Incomer-1 to Incomer-2 Busbar 70 70 70 70
4 Outgoing-1 to Outgoing-2 Busbar 70 70 70 70

4. BUSBAR CONTACT RESISTANCE TEST:

CURRENT INJECTED: 100A DC

L1-L1 L2-L2 L3-L3 Neutral


Sl.No. FEEDER REFERENCE
(μΩ) (μΩ) (μΩ) (μΩ)
1 Incomer-1 to Outgoing-1 Busbar 43.6 44.2 45.1 54.5
2 Incomer-2 to Outgoing-2 Busbar 44.9 46.1 44.7 58.8
3 Incomer-1 to Incomer-2 Busbar 80.0 78.8 81.2 81.5
4 Outgoing-1 to Outgoing-2 Busbar 53.2 52.5 52.9 110.0

Test Equipment Details

Description Serial No Make/Type Calibration due date


Micro Ohm Meter RD 170 Y OMICRON / CPC 100 16.03.2022

Remarks:-

5. HIGH VOLTAGE TEST:


SWITCHBOARD DETAILS:

Normal Current
2700 A Rated Volts 440 V
rating of busbar

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021
PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL
EMPLOYER ALDAR DATE 18.11.2021
PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 5 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

Normal Current rating of


Short Circuit rating 50KA 2700
load
Serial no. LVAC-124/20/003 Frequency 50 Hz

IR Measurement before HV Test: 1000V DC


Sl. No Phase IR Value in (GΩ)
1 R - Y+B+N+E 8.20
2 Y - R+B+N+E 6.71
3 B - R+Y+N+E 8.04
4 N - R+Y+B+E 3.75

HV Test: Voltage applied 2000 VAC for one minute.


Sl. No Test Combination Leakage current in mA
1 R - Y+B+N+E 3.0
2 Y - R+B+N+E 3.0
3 B - R+Y+N+E 3.0
4 N - R+Y+B+E 5.0

IR Measurement after HV Test: 1000V DC.


Sl. No Phase IR Value in (GΩ)
1 R - Y+B+N+E 8.74
2 Y - R+B+N+E 7.12
3 B - R+Y+N+E 8.66
4 N - R+Y+B+E 4.19
Remarks: -
Test Equipment Details:
Equipment Detail Serial No Due Date
AC HV Test kit 1508 26.01.2022
Insulation Tester B20235 27.08.2022
CURRENT TRANSFORMER

Switch Board No. : LV Panel Designation: Incomer-1

CT Name Plate Details:

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021
PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL
EMPLOYER ALDAR DATE 18.11.2021
PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 6 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

Description
Make HOBUT
Type CT211
Burden 10 VA
Class 0.5FS10
Ratio 2500/5 A
Serial No. 165898//1/210 165898/1/257 165898/1/200

Visual Checks:

Mechanical Damage : No damage Tight Connections: Ok


Star Point Connected and Earth : Ok

Insulation Resistance Test:


Test Points R Y B
Secondary – Earth (500VDC)/1min (GΩ) 41.2 27.9 38.5

Primary Injection Test :

Measured at CT Terminal in
Primary Amps Ammeter Display in Amps
CT Ratio
Phase Current
(A)
Injected (A) R Y B
R Y B
R- PHASE 500 2500/5 1.0 -- -- 500 -- --
Y- PHASE 500 2500/5 -- 1.0 -- -- 500 --
B- PHASE 500 2500/5 -- -- 1.0 -- -- 500

Switch Board No. : LV Panel Designation: Incomer-2

CT Name Plate Details:

Description

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021
PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL
EMPLOYER ALDAR DATE 18.11.2021
PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 7 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

Make HOBUT
Type CT211
Burden 10 VA
Class 0.5FS10
Ratio 2500/5 A
Serial No. 165898//1/231 165898/1/163 165898/1/223

Visual Checks:

Mechanical Damage : No damage Tight Connections: Ok


Star Point Connected and Earth : Ok

Insulation Resistance Test:


Test Points R Y B
Secondary – Earth (500VDC)/1min (GΩ) 31.9 48.7 34.6

Primary Injection Test :

Measured at CT Terminal in
Primary Amps Ammeter Display in Amps
CT Ratio
Phase Current
(A)
Injected (A) R Y B
R Y B
R- PHASE 500 2500/5 1.0 -- -- 500 -- --
Y- PHASE 500 2500/5 -- 1.0 -- -- 500 --
B- PHASE 500 2500/5 -- -- 1.0 -- -- 500

TEST EQUIPMENT DETAILS:

Description of Test Equipment Serial Number Calibration Due Date


Insulation Tester B20235 27.08.2022
MultiMeter 31780307 26.01.2022
Primary Injection Kit RD 170 Y 16.03.2022

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021
PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL
EMPLOYER ALDAR DATE 18.11.2021
PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 8 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

Clamp meter 33650056WS 03.07.2022

TEST REPORT FOR AMMETER CALIBRATION

Switchboard No: LV-Incomer-1 Class: 3

Manufacturer : CROMPTON Ratio: 2500/5 A

APPLIED EXPECTED ACTUAL READING


PHASES %ERROR
CURRENT(A) READING (A) MEASURED (A)
250 250 250 0
R
500 500 500 0
250 250 250 0
Y
500 500 500 0
250 250 250 0
B
500 500 500 0

Switchboard No: LV-Incomer-2 Class: 3

Manufacturer : CROMPTON Ratio: 2500/5 A

APPLIED EXPECTED ACTUAL READING


PHASES %ERROR
CURRENT(A) READING (A) MEASURED (A)
R 250 250 250 0

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021
PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL
EMPLOYER ALDAR DATE 18.11.2021
PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 9 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

500 500 500 0


250 250 250 0
Y
500 500 500 0
250 250 250 0
B
500 500 500 0

TEST EQUIPMENT DETAILS:

Description Manufacturer Serial No. Calibration Due Date


Secondary Injection Kit PROGRAMA / SVERKER 780 1502101 23.02.2022

TEST REPORT FOR VOLTMETER CALIBRATION

Switch board no. : LV Panel Location: INCOMER-1


Manufacturer : CROMPTON Class : 1.5

APPLIED EXPECTED ACTUAL READING


PHASES % ERROR
VOLTAGE (V) READING (V) MEASURED (V)

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021
PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL
EMPLOYER ALDAR DATE 18.11.2021
PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 10 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

R-N 230 230 230 0


Y-N 230 230 230 0
B-N 230 230 230 0
R-Y 415 415 415 0
Y-B 415 415 415 0
B-R 415 415 415 0

Switch board no. : LV Panel Location: INCOMER-2


Manufacturer : CROMPTON Class : 1.5

APPLIED EXPECTED ACTUAL READING


PHASES % ERROR
VOLTAGE (V) READING (V) MEASURED (V)

R-N 230 230 230 0


Y-N 230 230 230 0
B-N 230 230 230 0
R-Y 415 415 415 0
Y-B 415 415 415 0
B-R 415 415 415 0

TEST EQUIPMENT DETAILS:

Description Manufacturer Serial No. Calibration Due Date


3-phase
PROGRAMA / SVERKER 780 1502101 23.02.2022
Secondary Injection Kit

LV DB FUNCTIONAL CHECK

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021
PROJECT RIYADH CITY SOUTH EQUIPMENT LV PANEL
EMPLOYER ALDAR DATE 18.11.2021
PMC KBR SUBSTATION RD 3604
CONSULTANT ARCADIS
PAGE Page 11 of 11
CONTRACTOR NATIONAL PROJECTS & CONSTRUCTION
SITE ACCEPTANCE TEST REPORT FOR LV PANEL

CHECKED
SINO TYPE OF OPERATION
OK NOT OK

1 Wiring Tightness ✔
ON ✔
2 LV Incomer-1
OFF ✔
ON ✔
3 LV Incomer-2
OFF ✔
ON ✔
4 Bus Coupler
OFF ✔
415 V,3 Phase,50Hz AC supply is applied to LVDB Incomer
5
1 and indications ✔

415 V,3 Phase,50Hz AC supply is applied to LVDB Incomer


6
2 and indications ✔

415 V,3 Phase,50Hz AC supply is applied to LVDB and


7
Auxiliary Circuits ✔
Remarks: -

TESTED BY CONTRACTOR WITNESSED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER LLC NPC ARCADIS KBR ALDAR
NAME M.IDAYA CHANDIRAN

SIGNATURE

DATE 18.11.2021

You might also like