You are on page 1of 57

UPR: Ciencias Médicas

Project:Reemplazo MDP

SUBMITTAL #1

Equipment

Contractor’s Review

Submitted for review and approval


Resubmitted for review and approval

ENGINEER’S ACTION

_____Approved _____Revise / Resubmit

_____Approved as noted _____Rejected / Resubmit

SIGNATURE______________________________________

DATE_________________

20 Ave LMM Ste 1 Urb Villa Blanca PMB-499 Caguas, PR 00725


Tel. 787-590-1553
Email:davila@medaelectrical.com
PO Box 363622
San Juan, PR 00936

3/19/2024

MEDA Electrical

Attention: Jose Davila

Subject: Primates
P05V0214X4K1

Dear Jose,

Thank you for allowing Eaton the opportunity to participate in this project. Eaton is pleased to provide the
following proposal for the Primates project for your review and consideration.

Summary:

Qty Description
1 Switchboards

Commercial Terms and Conditions


Terms and Conditions are based on Selling Policy 25-000
Shipment terms are FOB Point of Shipment.
Payment terms are Net 30.
Warranty is based on Eaton Standard Warranty.

If you have any questions or concerns please feel free to give me a call.

Regards,

Rafael Aguiar
Managing Director
raguiar@martelec.com
787-703-1818

©2024, Eaton Corporation, Revision Date: 3/19/2024


All Rights Reserved
Primates

Submittal for Approval

Negotiation Number
P05V0214X4K1
Volume 1 of 1
Equipment:
Switchboards

Date: 3/19/2024 ©2022 Eaton Corporation, All Rights Reserved


Main Table of Contents

Combined Bill of Material For All Items (Detailed) 4


1.0 Switchboards 7
1.1 Bill of Material 9
1.2 Drawings 13
1.3 Technical Documents 18
1.4 Instruction Data 32
Detail Bill of Material Page 1 of 3
Project Nam e: Primates Negotiation No: P05V0214X4K1
General Order No: Alternate No: 0000

Item No. Qty Product Description Unit Quote Price Extended Quote
1 Switchboards Pow-R-Line Xpert Switchboard, Front Access/ Front and Rear
Align, Type 3R (nonwalk-in) Flat Roof, 208Y/120V 3-Phase 4-Wire,
1600 Silver Plated Copper, Minimum Interrupting Rating: 65kA,
Bus Bracing Rating: 65kA, Depth: 24 In

Catalog No SBAEENNX0C1B1
Designation MDP

Rafael F. Aguiar / Project Sales / Mobile: 939.717.5134

Martelec Corporation 03/19/2024 8:29 AM


Detail Bill of Material Page 2 of 3
Project Nam e: Primates Negotiation No: P05V0214X4K1
General Order No: Alternate No: 0000

Structure 1 1600 Amp Silver Plated CU Distribution Structure


Compartment 1 - Main Lugs Main Lugs
Compartment 2 - Breaker PD23PROV Breaker Provision
Compartment 3 - Breaker PD23PROV Breaker Provision
Compartment 4 - Breaker PD23PROV Breaker Provision
Compartment 5 - Breaker PD23PROV Breaker Provision
Compartment 6 - Breaker PD23PROV Breaker Provision
Compartment 7 - Breaker 250A, 3P PDG33G Breaker [400A Frame]
Mechanical (1) 2/0-500 kcmil
Thermal Mag Trip - Standard
Compartment 8 - Breaker 250A, 3P PDG33G Breaker [400A Frame]
Mechanical (1) 2/0-500 kcmil
Thermal Mag Trip - Standard
Compartment 9 - Breaker 225A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #4-4/0
Thermal Mag Trip - Standard
Compartment 10 - Breaker 200A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #4-4/0
Thermal Mag Trip - Standard
Compartment 11 - Breaker 200A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #4-4/0
Thermal Mag Trip - Standard
Compartment 12 - Breaker 150A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #4-4/0
Thermal Mag Trip - Standard
Compartment 13 - Breaker 200A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #4-4/0
Thermal Mag Trip - Standard
Compartment 14 - Breaker 100A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #14-1/0
Thermal Mag Trip - Standard
Compartment 15 - Breaker 100A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #14-1/0
Thermal Mag Trip - Standard
Compartment 16 - Breaker 100A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #14-1/0
Thermal Mag Trip - Standard
Compartment 17 - Breaker 100A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #14-1/0
Thermal Mag Trip - Standard
Compartment 18 - Breaker 400A, 3P PDG33G Breaker [400A Frame]
Mechanical (1) 2/0-500 kcmil
Thermal Mag Trip - Standard
Compartment 19 - Breaker 400A, 3P PDG33G Breaker [400A Frame]
Mechanical (1) 2/0-500 kcmil
Thermal Mag Trip - Standard
Compartment 20 - Breaker 600A, 3P PDG33G Breaker [600A Frame]
Mechanical (2) #2-500 kcmil
Thermal Mag Trip - Standard

Qty List of Materials


1 Type 3R (nonwalk-in) Flat Roof
1 Heater Package - (CPT, heater, thermostat, fused disconnect)
1 Silver Plated Copper Ground Bus
1 1600 Amp Silver Plated CU Distribution Structure
1 Main Lugs

Rafael F. Aguiar / Project Sales / Mobile: 939.717.5134

Martelec Corporation 03/19/2024 8:29 AM


Detail Bill of Material Page 3 of 3
Project Nam e: Primates Negotiation No: P05V0214X4K1
General Order No: Alternate No: 0000

Qty List of Materials


1 Mechanical (2) #2-500 kcmil
4 Mechanical (1) 2/0-500 kcmil
4 Mechanical (1) #14-1/0
5 Mechanical (1) #4-4/0
1 600A, 3P PDG33G Breaker [600A Frame], Trip 600 A, Thermal Mag, (2)
#2-500 kcmil, Mechanical
2 400A, 3P PDG33G Breaker [400A Frame], Trip 400 A, Thermal Mag, (1)
2/0-500 kcmil, Mechanical
4 100A, 3P PDG23G Breaker [225A Frame], Trip 100 A, Thermal Mag, (1)
#14-1/0, Mechanical
1 150A, 3P PDG23G Breaker [225A Frame], Trip 150 A, Thermal Mag, (1)
#4-4/0, Mechanical
3 200A, 3P PDG23G Breaker [225A Frame], Trip 200 A, Thermal Mag, (1)
#4-4/0, Mechanical
1 225A, 3P PDG23G Breaker [225A Frame], Trip 225 A, Thermal Mag, (1)
#4-4/0, Mechanical
2 250A, 3P PDG33G Breaker [400A Frame], Trip 250 A, Thermal Mag, (1)
2/0-500 kcmil, Mechanical
5 PD23PROV Breaker Provision

Eaton Selling Policy 25-000 applies.

All orders must be released for manufacture within 90 days of date of order entry. If approval drawings are required, drawin gs must be returned
approved for release within 60 days of mailing. If drawings are not returned accordingly, and/or if shipment is delayed for any reason, the price of the
order will increase by 1.0% per month or fraction thereof for the time the shipment is delayed.

Seller shall not be responsible for any failure to perform, or delay in performance of, its obligations resulting from the COVID-19 pandemic or any
future epidemic, and Buyer shall not be entitled to any damages resulting thereof.

Rafael F. Aguiar / Project Sales / Mobile: 939.717.5134

Martelec Corporation 03/19/2024 8:29 AM


Switchboards
Section Table of Contents
Switchboards
1.0 Switchboards 7
Section Table of Contents 8
1.1 Bill of Material 9
1.1.1 Separate Bills of Material by Product (Detailed) 10
1.2 Drawings 13
1.2.1 PRLX Switchboard - MDP - SBAEENNX0C1B1 14
1.3 Technical Documents 18
1.3.1 HEATER W/THERMOSTAT POWER 208Y/120V SERVICE 19
1.3.2 Pow-R-Line Xpert (PRLX) general purpose distribution switchboard design guide
21
1.3.3 Power Defense frame size 3 technical data sheet 27
1.3.4 Power Defense frame size 2 technical data sheet 29
1.3.5 Power Xpert Release (PXR) electronic trip unit guide 31
1.4 Instruction Data 32
1.4.1 Pow-R-Line Switchboard Instruction Manual 33
Bill of Material
Detail Bill of Material Page 1 of 3
Project Nam e: Primates Negotiation No: P05V0214X4K1
General Order No: Alternate No: 0000

Item No. Qty Product Description Unit Quote Price Extended Quote
1 Switchboards Pow-R-Line Xpert Switchboard, Front Access/ Front and Rear
Align, Type 3R (nonwalk-in) Flat Roof, 208Y/120V 3-Phase 4-Wire,
1600 Silver Plated Copper, Minimum Interrupting Rating: 65kA,
Bus Bracing Rating: 65kA, Depth: 24 In

Catalog No SBAEENNX0C1B1
Designation MDP

Rafael F. Aguiar / Project Sales / Mobile: 939.717.5134

Martelec Corporation 03/19/2024 8:29 AM


Detail Bill of Material Page 2 of 3
Project Nam e: Primates Negotiation No: P05V0214X4K1
General Order No: Alternate No: 0000

Structure 1 1600 Amp Silver Plated CU Distribution Structure


Compartment 1 - Main Lugs Main Lugs
Compartment 2 - Breaker PD23PROV Breaker Provision
Compartment 3 - Breaker PD23PROV Breaker Provision
Compartment 4 - Breaker PD23PROV Breaker Provision
Compartment 5 - Breaker PD23PROV Breaker Provision
Compartment 6 - Breaker PD23PROV Breaker Provision
Compartment 7 - Breaker 250A, 3P PDG33G Breaker [400A Frame]
Mechanical (1) 2/0-500 kcmil
Thermal Mag Trip - Standard
Compartment 8 - Breaker 250A, 3P PDG33G Breaker [400A Frame]
Mechanical (1) 2/0-500 kcmil
Thermal Mag Trip - Standard
Compartment 9 - Breaker 225A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #4-4/0
Thermal Mag Trip - Standard
Compartment 10 - Breaker 200A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #4-4/0
Thermal Mag Trip - Standard
Compartment 11 - Breaker 200A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #4-4/0
Thermal Mag Trip - Standard
Compartment 12 - Breaker 150A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #4-4/0
Thermal Mag Trip - Standard
Compartment 13 - Breaker 200A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #4-4/0
Thermal Mag Trip - Standard
Compartment 14 - Breaker 100A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #14-1/0
Thermal Mag Trip - Standard
Compartment 15 - Breaker 100A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #14-1/0
Thermal Mag Trip - Standard
Compartment 16 - Breaker 100A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #14-1/0
Thermal Mag Trip - Standard
Compartment 17 - Breaker 100A, 3P PDG23G Breaker [225A Frame]
Mechanical (1) #14-1/0
Thermal Mag Trip - Standard
Compartment 18 - Breaker 400A, 3P PDG33G Breaker [400A Frame]
Mechanical (1) 2/0-500 kcmil
Thermal Mag Trip - Standard
Compartment 19 - Breaker 400A, 3P PDG33G Breaker [400A Frame]
Mechanical (1) 2/0-500 kcmil
Thermal Mag Trip - Standard
Compartment 20 - Breaker 600A, 3P PDG33G Breaker [600A Frame]
Mechanical (2) #2-500 kcmil
Thermal Mag Trip - Standard

Qty List of Materials


1 Type 3R (nonwalk-in) Flat Roof
1 Heater Package - (CPT, heater, thermostat, fused disconnect)
1 Silver Plated Copper Ground Bus
1 1600 Amp Silver Plated CU Distribution Structure
1 Main Lugs

Rafael F. Aguiar / Project Sales / Mobile: 939.717.5134

Martelec Corporation 03/19/2024 8:29 AM


Detail Bill of Material Page 3 of 3
Project Nam e: Primates Negotiation No: P05V0214X4K1
General Order No: Alternate No: 0000

Qty List of Materials


1 Mechanical (2) #2-500 kcmil
4 Mechanical (1) 2/0-500 kcmil
4 Mechanical (1) #14-1/0
5 Mechanical (1) #4-4/0
1 600A, 3P PDG33G Breaker [600A Frame], Trip 600 A, Thermal Mag, (2)
#2-500 kcmil, Mechanical
2 400A, 3P PDG33G Breaker [400A Frame], Trip 400 A, Thermal Mag, (1)
2/0-500 kcmil, Mechanical
4 100A, 3P PDG23G Breaker [225A Frame], Trip 100 A, Thermal Mag, (1)
#14-1/0, Mechanical
1 150A, 3P PDG23G Breaker [225A Frame], Trip 150 A, Thermal Mag, (1)
#4-4/0, Mechanical
3 200A, 3P PDG23G Breaker [225A Frame], Trip 200 A, Thermal Mag, (1)
#4-4/0, Mechanical
1 225A, 3P PDG23G Breaker [225A Frame], Trip 225 A, Thermal Mag, (1)
#4-4/0, Mechanical
2 250A, 3P PDG33G Breaker [400A Frame], Trip 250 A, Thermal Mag, (1)
2/0-500 kcmil, Mechanical
5 PD23PROV Breaker Provision

Eaton Selling Policy 25-000 applies.

All orders must be released for manufacture within 90 days of date of order entry. If approval drawings are required, drawin gs must be returned
approved for release within 60 days of mailing. If drawings are not returned accordingly, and/or if shipment is delayed for any reason, the price of the
order will increase by 1.0% per month or fraction thereof for the time the shipment is delayed.

Seller shall not be responsible for any failure to perform, or delay in performance of, its obligations resulting from the COVID-19 pandemic or any
future epidemic, and Buyer shall not be entitled to any damages resulting thereof.

Rafael F. Aguiar / Project Sales / Mobile: 939.717.5134

Martelec Corporation 03/19/2024 8:29 AM


Drawings
Switchboard General Information
Pow-R-Line Xpert - Specifications
Quantity: 1
Alignment: Front Access/ Front and Rear Align
Service: 208Y/120V 3-Phase 4-Wire Minimum Interrupt Rating: 65 kA
Bus Specifications
Bus Amps: 1600 Bus Bracing Rating: 65kA
Neutral Amps: 1600
Bus Material: Silver Plated Copper Heat Test
Ground Bus Material: Silver Plated Copper Ground Bus Bolted To
Frame, (1) #6-350 kcmil Ground Lug
Incoming/Outgoing Information
Terminals, Mechanical, Top, (5) #4-500 kcmil
Incoming Qty & Size: Terminals, Mechanical, Top, (5) #4-500 kcmil
Structure Specifications
Non Service Entrance
Enclosure Type: Type 3R (nonwalk-in) Flat Roof
Enclosure: Outdoor Enlosure Configuration Per Euserc Dwg 354
Heater package - ( CPT, heater, thermostat, fused disconnect)
Special Notes
Qty Description Catalog Number
Enclosure properties
Struct # Description/Modifications
1 Top incoming main lugs on 50x chassis (Incoming Main Device/
MLO Section)
Switchboard Configuration is INVALID

The information on this document is PREPARED BY DATE


created by Eaton Corporation. It is RAFAEL AGUIAR 3/19/2024 Eaton SumterSC
disclosed in confidence and it is only to
be used for the purpose in which it is APPROVED BY DATE JOB NAME Primates
supplied. DESIGNATION MDP
VERSION TYPE DRAWING TYPE

9.0.34.3 Switchboards CustAppr


NEG-ALT Number REVISION DWG SIZE G.O. ITEM SHEET

P05V0214X4K1-0000 0 DwgA 1 of 4
1 Main Lugs

PD2-P 2
3 PD2-P
PD2-P 4
5 PD2-P
PD2-P 6
7
250
8
9 225 250
10 200 200 11

12 150 200 13

14 100 100 15

16 100 100 17

18 400
19 400
20 600
Front View
Struct
Depth
1
24 *
Width 45

Power Flow

Floor PlanRear

2.50
12.00

13

39
3.00

Total of 1 Structures, Total Weight of 900 Weight-Lbs. with Front Hinged Doors.
Total of 1 Structures, Total Width of 45 Inches with Front Hinged Doors.

Structure 1
Ship-Inches 45.00
Ship-MM 1143
Wdth-Inches 45.00
Wdth-MM 1143
Depth(Inner)-In. 24.00
Depth(Inner)-MM 609
Depth(Outer)-In. 37.00
Depth(Outer)-MM 939
Height-Inches 90.00
Height-MM 2286
Weight-Lbs.(Est.) 900
Weight-Kg.(Est.) 408
The information on this document is PREPARED BY DATE
created by Eaton Corporation. It is RAFAEL AGUIAR 3/19/2024 Eaton SumterSC
disclosed in confidence and it is only to
be used for the purpose in which it is APPROVED BY DATE JOB NAME Primates
supplied. DESIGNATION MDP
VERSION TYPE DRAWING TYPE

9.0.34.3 Switchboards CustAppr


NEG-ALT Number REVISION DWG SIZE G.O. ITEM SHEET

P05V0214X4K1-0000 0 DwgA 2 of 4
Switchboard Units Information
Str# Unit Description/Modifications Nameplate

1
1 Main Lugs -Incoming

2 Feeder Breaker - Chassis Mtd-PD23PROV Breaker Provision, PROVISIONS FOR BREAKER


ONLY
Neutral Terminal, (1) #6-350 kcmil

3 Feeder Breaker - Chassis Mtd-PD23PROV Breaker Provision, PROVISIONS FOR BREAKER


ONLY
Neutral Terminal, (1) #6-350 kcmil

4 Feeder Breaker - Chassis Mtd-PD23PROV Breaker Provision, PROVISIONS FOR BREAKER


ONLY
Neutral Terminal, (1) #6-350 kcmil

5 Feeder Breaker - Chassis Mtd-PD23PROV Breaker Provision, PROVISIONS FOR BREAKER


ONLY
Neutral Terminal, (1) #6-350 kcmil

6 Feeder Breaker - Chassis Mtd-PD23PROV Breaker Provision, PROVISIONS FOR BREAKER


ONLY
Neutral Terminal, (1) #6-350 kcmil

7 Feeder Breaker - Chassis Mtd-250A, 3P PDG33G Breaker [400A Frame], Trip(Ir) 250A., Thermal
Mag
Terminals, Mechanical, (1) 2/0-500 kcmil
Neutral Terminal, (1) #4-500 kcmil

8 Feeder Breaker - Chassis Mtd-250A, 3P PDG33G Breaker [400A Frame], Trip(Ir) 250A., Thermal
Mag
Terminals, Mechanical, (1) 2/0-500 kcmil
Neutral Terminal, (1) #4-500 kcmil

9 Feeder Breaker - Chassis Mtd-225A, 3P PDG23G Breaker [225A Frame], Trip(Ir) 225A., Thermal
Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil

10 Feeder Breaker - Chassis Mtd-200A, 3P PDG23G Breaker [225A Frame], Trip(Ir) 200A., Thermal
Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil

11 Feeder Breaker - Chassis Mtd-200A, 3P PDG23G Breaker [225A Frame], Trip(Ir) 200A., Thermal
Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil

12 Feeder Breaker - Chassis Mtd-150A, 3P PDG23G Breaker [225A Frame], Trip(Ir) 150A., Thermal
Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil

The information on this document is PREPARED BY DATE


created by Eaton Corporation. It is RAFAEL AGUIAR 3/19/2024 Eaton SumterSC
disclosed in confidence and it is only to
be used for the purpose in which it is APPROVED BY DATE JOB NAME Primates
supplied. DESIGNATION MDP
VERSION TYPE DRAWING TYPE

9.0.34.3 Switchboards CustAppr


NEG-ALT Number REVISION DWG SIZE G.O. ITEM SHEET

P05V0214X4K1-0000 0 DwgA 3 of 4
13 Feeder Breaker - Chassis Mtd-200A, 3P PDG23G Breaker [225A Frame], Trip(Ir) 200A., Thermal
Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil

14 Feeder Breaker - Chassis Mtd-100A, 3P PDG23G Breaker [225A Frame], Trip(Ir) 100A., Thermal
Mag
Terminals, Mechanical, (1) #14-1/0
Neutral Terminal, (1) #14-1/0

15 Feeder Breaker - Chassis Mtd-100A, 3P PDG23G Breaker [225A Frame], Trip(Ir) 100A., Thermal
Mag
Terminals, Mechanical, (1) #14-1/0
Neutral Terminal, (1) #14-1/0

16 Feeder Breaker - Chassis Mtd-100A, 3P PDG23G Breaker [225A Frame], Trip(Ir) 100A., Thermal
Mag
Terminals, Mechanical, (1) #14-1/0
Neutral Terminal, (1) #14-1/0

17 Feeder Breaker - Chassis Mtd-100A, 3P PDG23G Breaker [225A Frame], Trip(Ir) 100A., Thermal
Mag
Terminals, Mechanical, (1) #14-1/0
Neutral Terminal, (1) #14-1/0

18 Feeder Breaker - Chassis Mtd-400A, 3P PDG33G Breaker [400A Frame], Trip(Ir) 400A., Thermal
Mag
Terminals, Mechanical, (1) 2/0-500 kcmil
Neutral Terminal, (1) #4-500 kcmil

19 Feeder Breaker - Chassis Mtd-400A, 3P PDG33G Breaker [400A Frame], Trip(Ir) 400A., Thermal
Mag
Terminals, Mechanical, (1) 2/0-500 kcmil
Neutral Terminal, (1) #4-500 kcmil

20 Feeder Breaker - Chassis Mtd-600A, 3P PDG33G Breaker [600A Frame], Trip(Ir) 600A., Thermal
Mag
Terminals, Mechanical, (2) #2-500 kcmil
Neutral Terminal, (2) #4-500 kcmil

The information on this document is PREPARED BY DATE


created by Eaton Corporation. It is RAFAEL AGUIAR 3/19/2024 Eaton SumterSC
disclosed in confidence and it is only to
be used for the purpose in which it is APPROVED BY DATE JOB NAME Primates
supplied. DESIGNATION MDP
VERSION TYPE DRAWING TYPE

9.0.34.3 Switchboards CustAppr


NEG-ALT Number REVISION DWG SIZE G.O. ITEM SHEET

P05V0214X4K1-0000 0 DwgA 4 of 4
Technical Documents
Page: 1 of 1
Pow-R-Line Xpert (PRLX) Design Guide DG015001EN
Switchboard Effective February 2020
General Description 21.1-2

Application Considerations Compartmentalized Feeder Overcurrent Devices


and Definitions and Branch Devices To properly select and size overcurrent
devices for use in a switchboard, the
Compartmentalized molded case circuit allowable temperature rise must be taken
Eaton’s Pow-R-LineT family of distribution
breakers and fusible switches provide into account as to its effect on the tripping
switchboards incorporates new design
additional isolation. Individually mounted characteristics of the devices in question
concepts that fit the ever-increasing need
molded case circuit breakers and fusible per UL 891.
for applications on high short-circuit
switches through 1200 A are available in
systems, while retaining maximum
a compartmentalized, rear-access, rear- Accordingly, the NECT requires
flexibility, safety and convenience
connected switchboard. See Pow-R-Line iX overcurrent devices to be rated not less
throughout the line.
switchboards in this section for details. than 125% of the continuous load they
are protecting. To comply with this, an
Front-Access Standard Switchboard Height
80% derating factor must be used with
all over­current devices such as molded
Front-access switchboards align at the
Standard Pow-R-Line switchboard height case breakers and FDPW fusible switches
rear, enabling them to be placed against
is 90.00 inches (2286.0 mm). Contact unless they are tested and listed for
a wall (Type Pow-R-Line XpertE front
Eaton for special heights. application at 100% of the rating. All
accessible). If the main section is deeper
MagnumE type breakers and bolted
than others, due to physical size of the
pressure switches are 100% rated.
main device, the necessary offset in Group Mounting
lineup will occur in front, and the main
section will be accessible from the side Group-mounted circuit protective devices
are an assembly of units mounted on a Short-Circuit Rating
as well as from the front. Eaton also offers
front accessible switchboards that align panelboard type chassis. Units may be Standard bus and connectors on all
at the front and rear. molded-case breakers, fusible switches, switchboards are rated for use on
customer metering and surge protective systems capable of producing up to
devices. 65,000 A rms symmetrical short-circuit
Front- and Rear-Access A main molded case breaker or main
current at the incoming terminals.
Front- and rear-access switchboards align fusible switch, within the sizes listed for Increased bus short-circuit ratings equal
at the front and the rear. Bus maintenance panelboard design, can be included in to that of connected switchboard devices,
and cable entry and exit require rear the panel-mounted assembly in lieu of up to 200,000 A rms symmetrical, are
access. There are two types of rear- a separate, individually mounted unit. available in most Pow-R-Line Xpert
accessible switchboards. Both types use switchboards when approved main
the same incoming utility and/or main devices are installed. UL labeled
structures. The first type uses group- Space Only for Future Devices switchboard sections are marked with
mounted feeder devices with panel Group-Mounted Construction their applicable short-circuit rating.
construction (Type Pow-R-Line Xpert Where space only for future circuit
front and rear accessible). The second When air power circuit breakers are used
protective devices is required, the proper as feeder devices in a switchboard, these
type uses individually compartmentalized space and a blank filler plate will be
feeder devices with load side insulated devices may experience up to a 30-cycle
supplied. Connections and mounting (1/2 second) delay if the instantaneous
bus bar extensions (Type Pow-R-Line iX). hardware are not included. setting is turned off. Eaton has qualified
our low voltage switchboards when air
Individually Mounted Provision for Future Devices power circuit breakers are used as feeders
Larger overcurrent protective devices (and mains) to 30 cycles.This rating is not
Where provisions for future circuit recognized under the UL 891 standard.
(OCPD) may be individually mounted. protective devices are required, space for
In most cases, this means that the OCPD However, Eaton has witness tested the
the device, corresponding vertical bus, structure bussing with a qualified National
is mounted vertically in the switchboard device connectors and the necessary
and is connected via bus bar. All insulated RecognizedTesting Laboratory (NRTL)
mounting hardware will be supplied. at 30 cycles (1/2 second) up to 100 kAIC
case circuit breakers, power air circuit
breakers and bolted pressure contact symmetrical.
switches are individually mounted. Bus Bar System
Molded case circuit breakers 600 A and Standard bus in the switchboards is
above may be individually mounted tin-plated aluminum. Copper, silver-
when used as a main or as a feeder plated copper or tin-plated copper are
device feeding other OCPD within a also available.
section or adjacent sections.
Main bus and sub-main buses meet ULT
and NEMAT standards for temperature
rise on all Pow-R-Line switchboards.
Special density rated bus is available.

EATON www.eaton.com
Pow-R-Line Xpert (PRLX) Design Guide DG015001EN
Switchboard Effective February 2020
General Description 21.1-3

Provision for Busway 2. Mounted adjacent to a service B. For testing purposes, means are also
structure and used as a bus transition required to disconnect the switchboard
Entrance and Exit compartment for running riser bus neutral bus from the grounded service
Busway connections to switchboard from the load-side of the service neutral conductor (single-phase,
sections include cutout and drilling in structure up to top outgoing bus three-wire; and three-phase, four-
the top of the switchboard with riser duct connection when distribution wire systems).To comply with this
connections from the switchboard device structures are not required. Auxiliary requirement, a removable link (solid
or bus, up to the point where the bus duct structures are the same depth and bar) is provided in the switchboard
enters the switchboard. No connections height as service structures. neutral bus.This link is generally
are furnished external to the switchboard. located near the point where the main
In addition to the above applications, feeders enter the switch­board or in the
In all transactions involving busway auxiliary structures may be mounted
attached to switchboards, it is essential area of the main disconnect device
adjacent to a distribution structure and where one is provided.
that information regarding orientation used as a structure for lighting panel or
of the busway with respect to the front other device that may be cable-connected To further comply with NEC and UL
of the switchboard be supplied to the to a branch circuit device in the distribution requirements, a separate bonding strap
coordinating assembly plant. structure. Dimensions are compatible with is connected from the neutral bus to
On Pow-R-Line Xpert switchboards, a the arrangements required. the switchboard frame. This bonding
solid bus bar is used to connect the bus connection is located on the line side of
the removable neutral link, maintaining
duct to the individually mounted main Switchboards Used as a service ground to the switchboard
device, main or sub-main switchboard
bus, or vertical main bus of panel- Service Equipment frame when the test link is removed.
mounted circuit protective device panels. Service equipment is the electrical See Figure 21.1-1.
Busway fed by group-mounted branch equipment that constitutes the main
devices are cable connected. control and means of power cutoff the
electric service (normally Power Company Ø1 Ø2 Ø3 N
Aluminum riser connections are supply) brought into the building.
standard. Copper- or silver-plated To Station
Where switchboards are to be used as Ground
copper is available as an option.
service equipment, certain NEC and UL
requirements apply that necessitate Neutral
Transitions modifications not normally supplied Link

Transition structures are required in switchboards.


for connecting switchboards to the The following is a summary of the
secondary of power center transformer Bonding
requirements that are pertinent to Strap
(fluid filled), motor control centers, the application of a switchboard for N
and for other special switchboard service equipment: Ø1
configurations such as “L” or “U” shaped
lineups. In some applications, an extra A. A switchboard with main lugs only Ø2
Equipment
structure complete with connections is (no main disconnect) must be Ground Bus Ø3
required; in others, where switchboard designed so that all circuits in the
depth and space permit, only the switchboard can be disconnected
connection conductors are required. from the supply source by the Switchboard Frame
Refer to Eaton for these applications. operation of no more than six
operating handles (breaker or switch). Figure 21.1-1. Neutral Link
Auxiliary Structures Switchboard equipped with main UL labeling will clearly indicate service
These are normally mounted adjacent disconnect devices are not subject to equipment listed switchboards.
to service structures or distribution the above six disconnect limitation, as
structures, and used where incoming the entire board can be de-energized
service or feeder conductors require with the main disconnect device.
additional space or facilities not included Ground fault protection of equipment
in the standard switchboard, such as: must be provided for solidly grounded
1. Mounted adjacent to a top connected wye electrical services of more than
service structure and used as a cable 150 V to ground, but not exceeding
pull structure where service conduc- 600 V phase-to-phase for each service
tors are brought in underground. disconnecting means rated 1000 A
Auxiliary structures are the same or more.
depth and height as the service
structure, and are wide enough to
accommodate the incoming cables.

EATON www.eaton.com
Pow-R-Line Xpert (PRLX) Design Guide DG015001EN
Switchboard Effective February 2020
General Description 21.1-4

Underwriters Laboratories Alternate Power Source Capabilities Seismic Qualification


Requirements and Labeling Multiple solutions are available to
The basic requirement for obtaining a accommodate alternate power sources
UL label on a switchboard, is that all the available. Due to the large number of
component devices (breakers, switches, customer and system requirements,
and so on) in the switchboard assembly details are not provided in this guide.
are UL listed. In addition, the switchboard Eaton offers solutions that include
must comply with all applicable main-main configuration and main-tie- Refer to Power Distribution Systems
provisions of UL 891. main configurations. Automatic transfer Design Guides for information on
equipment, including UL 1008 listed seismic qualification for this and other
Today’s modern electrical systems require transfer switches and other automatic Eaton products.
that switchboards offer a wide selection transfer schemes, are available.
of electrical devices, many of which do
not fall within the scope of UL listed
devices. Therefore, the conditions under Automatic Transfer Equipment
which a switchboard may be labeled For continuity of service, automatic
are limited. transfer equipment between two
incoming sources may be required.
Listed below are several important This equipment transfers the load upon
guidelines for consideration when a failure of the normal (or preferred) source
UL label is specified: to the standby (or alternate) source.
1. UL nameplates, where applicable, Upon restoration of the normal source,
are supplied for each vertical structure the load is automatically transferred
rather than one common nameplate back to it. To accomplish this, electrically
for the complete switchboard lineup. operated main protective devices
Where all of the component devices (and bus tie devices, if required) must
in the switchboard are UL listed and be employed. Additional relays also
all applicable provisions of UL 891 are are required to detect source voltage
met, each of the switchboard sections failure and to transfer control power,
may be labeled. when required. A manual selector switch
is usually provided to select the mode of
2. Individual vertical structures of a operation—automatic or manual transfer.
switchboard may be labeled where
they comply with UL requirements,
although other vertical structures in
the same switchboard lineup may
not meet the UL standards, and will
not be labeled.
3. All Pow-R-Line Xpert switchboards are
UL labeled when all mounted devices
are UL listed.

EATON www.eaton.com
Pow-R-Line Xpert (PRLX) Design Guide DG015001EN
Switchboard Effective February 2020
General Description 21.1-5

Product Overview
Pow-R-Line Xpert switchboards meet
NEMA Standard PB-2 and UL 891.

Construction Details
■ 6000 A main bus maximum
■ Front accessible—main sections
front- and/or side-access
■ Front- and rear-access; main sections
front- and/or side-access
■ Feeder devices group-mounted
■ Sections rear-aligned or front- and
rear-aligned

Main Devices, Individually Mounted


■ Power DefenseE molded case circuit
breakers, 400–2500 A,fixed-mounted
■ Insulated case circuit breakers,
Magnum SB, 800–5000 A, fixed
and drawout
■ Air power circuit breakers,
Magnum DS, 800–5000 A,
fixed or drawout
■ Air power circuit breakers with
current limiting fuses, Magnum DSL,
800–5000 A
■ Bolted pressure switches,
800–5000 A, fixed
■ Insulated case circuit breakers,
Series NRXE NF, 800–1200 A, fixed
and drawout
■ Insulated case circuit breakers,
Series NRX RF, 800–3000 A, fixed
and drawout
■ Fusible switches, 400–1200 A, fixed
Pow-R-Line Xpert Switchboard

Feeder Devices, Group-Mounted


■ Bolt-on Power Defense molded case Feeder Devices, Individually Mounted Selective Coordination
circuit breakers, 15–1200 A ■ Power Defense molded case circuit Selectively coordinated systems dictated
■ Drawout molded case circuit breakers, breakers, 800–2500 A, fixed by code and customer mandates may
70–1200 A ■ Insulated case circuit breakers, be achieved with Eaton switchboards to
Magnum SB, 800–5000 A, fixed either 0.1 or 0.01 seconds as mandated by
■ Fusible switches, 30–1200 A codes and/or customers. Refer to Power
and drawout
Distribution Systems Design Guides for
■ Air power circuit breakers, DS and additional details.
Magnum DS, 800–4000 A, fixed
and drawout Note: For selection and layout guidelines,
please reference Page 21.1-17.
■ Insulated case circuit breakers,
Series NRX NF, 800–1200 A, fixed
and drawout
■ Insulated case circuit breakers,
Series NRX RF, 800–3000 A, fixed
and drawout
■ Bolted pressure switches,
800–1600 A, fixed

EATON www.eaton.com
Pow-R-Line Xpert (PRLX) Design Guide DG015001EN
Switchboard Effective February 2020
General Description 21.1-6

Features
■ Eaton’s circuit breaker ratings up
to 200 kAIC c
■ Trip units that integrate Eaton’s Arcflash
Reduction Maintenance SystemE
reduces potential arc flash available b
a f
■ Integral ground fault protection
available in electronic trip units g
from 15–5000 A
■ Electronic trip units that integrate zone h
selective interlocking capabilities
available in molded case, insulated e i
case and air power circuit breaker d
■ Available with circuit breakers and
fusible switches on the same chassis

Type 1 Pow-R-Line Xpert Features

a Customer metering. f 250 A frame single mount.


b Utility metering compartment. g 600 A frame single mount.
c Surge protective device. h 250 A frame dual mount.
d Main breaker (Magnum SB). i 600 A frame dual mount.
e Cable pull and termination space.

Table 21.1-1. Pow-R-Line Xpert Group-Mounted Switchboards


The Single Chassis Design Voltage: 240–480–600 Vac, 250 Vdc
Provides Device Flexibility Mains: 400–6000 A
Main Device Type Amperes Short-Circuit
■ UL listed and labeled. Meets NEC and Symmetrical Rating (kA)
NEMA standards
Molded case circuit breakers 400–2500 14–200
■ Eaton microprocessor-based metering Insulated case circuit breakers, Magnum SB 800–5000 30–100
devices are standard when metering Insulated case circuit breakers, Series NRX NF 800–1200 65–85
is specified. Conventional metering is Insulated case circuit breakers, Series NRX RF 800–3000 65–100
available. Power Xpert Meter devices Air power circuit breakers, Magnum DS
can provide a communications Air power circuit breakers with CL fuses, DSL 800–5000 200
capability. See Advanced and Bolted pressure switches 800–5000 a 200
Electronic Metering Design Guides Fusible switches 400–1200 200
Main lugs only 400–6000 Rating determined by
for more information overcurrent protective
■ Optional integral surge protective device
device (SPD) is available in Pow-R-Line
Xpert switchboards, when specified. Feeder Device Type Amperes Short-Circuit
See Surge Protection (SPD) & Power Rating (kA)
Conditioning Products Design Guides
for more information Bolt-on, fixed-mounted molded case circuit breakers 15–2500 10–200
Drawout, molded case circuit breakers 70–600 10–200
■ Aluminum, copper or silver-plated Fusible switches 30–1200 200
copper bus Stacked—main with branch devices 400–2500 18–200
■ A full range of device modifications Magnum SB up to two high 800–2000 30–100
Magnum DS up to two high b 800–2000 30–100
is available
Series NRX NF up to two high and quad stack 800–1200 65
■ Available in NEMA Type 1 and 3R Series NRX RF up to two high 800–3000 65–100
enclosures, UL listed
a 5000 A bolted pressure switches are not UL listed.
b Third-party witness tested at 30 cycles.
Modifications
■ Ground fault protection on mains and
distribution devices
■ Coordination with other Eaton
divisions for busway and transformer
connections

EATON www.eaton.com
Molded case circuit breakers

Power Defense molded case circuit breakers


Frame size 3 (45–600 A)
Catalog number/product selection
Interrupting ratings
Catalog
designator F G K MA NA PA
UL/CSA kA rms kA rms kA rms kA rms kA rms kA rms
240 Vac 35 65 85 100 150 200
Frame size 3 configurator 480 Vac 25 35 50 65 85 100
600 Vac 14 18 25 35 50 65
250 Vdc BC 10/22 10/22 10/22 22/42 22/42 22/42
Shown: PD3 3-pole with
PXR 25 trip unit IEC lcu lcs lcu lcs lcu lcs lcu lcs lcu lcs lcu lcs
240 Vac 35 35 55 55 85 85 100 100 150 100 200 150
380–415 Vac 25 25 36 36 50 50 70 53 70 70 100 70
Dimensions and weights
440 Vac 25 20 30 22.5 35 35 50 40 70 50 100 50
Approximate dimensions in inches (mm) 480 Vac 20 20 25 20 35 22.5 50 30 65 40 85 40
Number 525 Vac 18 5 20 7.5 25 10 30 15 35 25 40 25
of poles Width Height Depth 660–690 Vac — — 8 4 10 5 15 7.5 20 10 20 10
2 5.47 (138.9) 10.13 (257.1) 4.30 (109.1) 250 Vdc BC 10/22 10/22 10/22 10/22 10/22 10/22 22/42 22/42 22/42 22/42 22/42 22/42
3 5.47 (138.9) 10.13 (257.1) 4.30 (109.1)
A UL current limiting. M interrupting rating only current limiting for the 400 A construction breakers.
4 7.22 (182.9) 10.13 (257.1) 4.30 (109.1)
B DC ratings available in thermal-magnetic breakers only. 250 Vdc is achieved using two poles in series.
C First rating listed is for 400 A frame, second rating is for 600 A frame.
Approximate shipping weight in lb (kg)
Breaker
type 2-Pole 3-Pole 4-Pole Terminals
PDG3 400 A 8.05 (3.65) 11.02 (5.0) 13.77 (6.25) AWG/ Metric
PDG3 600 A 10.43 (4.73) 12.36 (5.61) 16.27 (7.39) Maximum Terminal Number of kcmil (mm2) 3-Pole
breaker Breaker body Wire Wire conductors range per range per catalog
amperes frame type type class per phase conductor conductor number
Trip unit ratings Standard terminals
Continuous 300 400 Aluminum Cu/Al B, C 1 3–350 26.7–177 PDG3X3TA300 A
Poles current rating Trip units
350 400 Aluminum Cu/Al B, C 1 250–500 127–253 PDG3X3TA350 A
2-, 3-, 4-pole 100, 125, 150, 175, 200, 225, TFA, VFA
Thermal-magnetic 250, 300, 350, 400, 500, 600 400 400 Aluminum Cu/Al B, C 2 3/0–250 85–127 PDG3X3TA400 B
3-, 4-pole 125, 250, H250, B2N, E##, 400 600 Aluminum Cu/Al B, C 1 500–750 253–380 PDG3X3TA401H B
Electronic 400, H400, 600, D##, P## B 630 600 Aluminum Cu/Al B, C 2 2–500 33.6–253 PDG3X3TA630 B
adjustable range (45–600) A
A No accessories included.
A H as the leading character of the ampacity indicates a high
B Terminal shield included.
instantaneous version of the breaker for coordination purposes.
H ratings must use 600 A frame.
B All #s refer to protection and options. Refer to the MCCB catalog or Trip units
Power Defense poster for more information. Direct links are below. Description Specification

Additional information Trip unit


Interchangeable trip units Yes
Thermal-magnetic (T) Fixed thermal-adjustable magnetic
Molded case switch (K) Fixed magnetic
Motor circuit protector (M) Adjustable magnetic only (3-pole) PXR
electronic
Electronic
trip units
MCCB Time Power PXR 10 (B) adjustable LSI LSI, MLSI
catalog current Defense PXR 20 (E) current metering / comm opt. LSI, LSIG, ALSI, ALSIG
curve poster PXR 20D (D) current metering / comm std. LSI, LSIG, ALSI, ALSIG
PXR 25 (P) power metering / comm std. LSI, LSIG, ALSI, ALSIG, MLSI, MLSIG

Eaton
1000 Eaton Boulevard Follow us on social media to get the
Cleveland, OH 44122 latest product and support information.
United States
Eaton.com

© 2020 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. MZ012019EN / Z24189 All other trademarks are property
June 2020 of their respective owners.
Molded case circuit breakers

Power Defense molded case circuit breakers


Frame size 2 (15–225 A)
Catalog number/product selection
Interrupting ratings (2-, 3- and 4-pole)
Catalog
designator F G KA MA NA PA
UL/CSA kA rms kA rms kA rms kA rms kA rms kA rms
240 Vac 35 65 85 100 150 200
Frame size 2 configurator 480 Vac 25 35 50 65 85 100
600 Vac 14 18 22 25 30/25 C 35/25 C
250 Vdc B 2 10 10 10 22 22 22
Shown: PD2 3-pole with
PXR 25 trip unit A UL current limiting for 3- and 4-pole breakers.
B DC ratings available in thermal-magnetic breakers only. 250 Vdc is achieved using two poles in series.

Dimensions and weights C First rating listed is for thermal-magnetic breakers, second rating is for breakers with PXR electronic trip units.

Approximate dimensions in inches (mm) Terminals


Maximum Breaker Terminal Number of AWG/kcmil Metric (mm2) 3-pole
Number breaker frame body Wire Wire conductors range per range per catalog
of poles Width Height Depth amperes A type type class per phase conductor conductor number
1 1.38 (35.1) 6.00 (152.4) 3.50 (88.9) Standard terminals
2 2.75 (69.9) 6.00 (152.4) 3.50 (88.9)
100 15–100 Steel Cu/Al B, C 1 14–1/0 2.08–53.5 PDG2X3T100
3 4.12 (104.6) 6.00 (152.4) 3.50 (88.9) BC
4 5.49 (139.5) 6.00 (152.4) 3.50 (88.9)
225 60–225 Aluminum Cu/Al B, C 1 4–4/0 21.2–107 PDG2X3TA225
DC
Approximate shipping weight in lb (kg)
Alternate terminals
Breaker 50 15–50 Aluminum Cu/Al B, C 1 14–4 2.08–21.2 PDG2X3TA50 C
type 1-Pole 2-Pole 3-Pole 4-Pole
PDG2 225 A 2.00 (0.91) 3.00 (1.36) 4.21 (1.82) 5.69 (2.46) 100 60–100 Aluminum Cu/Al B, C 1 14–1/0 2.08–53.5 PDG2X3TA100 C
150 60–150 Aluminum Cu/Al B, C 1 14–4/0 2.08–107 PDG2X3TA150 C
Trip unit ratings 225 175–225 Aluminum Cu/Al B, C 1 6–300 13.3–152 PDG2X3TA225K
DE
Continuous
Poles current rating Trip units A The “Breaker frame” column provides information on the C No accessories included.

1-pole 15, 20, 25, 30, 35, 40, 45, TFF, VFF ampere ratings for which the terminal may be used (field D PDF2 225 A breakers with Digit 14 designation of
Thermal-magnetic 50, 60, 70, 80, 90, 100, 110, installation); in some cases the range is limited by proper “J” are equipped with PDG2X3TA225K terminals.
125, 150 fit of the terminal onto the breaker conductor. The column PDF2 150 A breakers with Digit 14 designation of
“Standard on Amperes” provides information on what “J” are equipped with PDG2X3TA225 terminals.
2-, 3-, 4-pole 15, 20, 25, 30, 35, 40, 45, TFF, VFF terminal is used during factory configuration per Digit 14
Thermal-magnetic 50, 60, 70, 80, 90, 100, 110, of the breaker catalog number. The two may not match. E Terminal shield included.
125, 150, 175, 200, 225
B Factory standard terminals and non-aluminum terminals for
3-, 4-pole 60, 100, 150, 225, B2N, E##,
100 A and below are the same terminals.
Electronic adjustable range (15–225) D##, P## A
A All #s refer to protection and options. Refer to the MCCB catalog or
Trip units
Power Defense poster for more information. Direct links are below.
Description Specification
Additional information
Trip unit
Thermal-magnetic (T) Fixed thermal-fixed magnetic
Molded case switch (K) Fixed magnetic
Motor circuit protector (M) Adjustable magnetic only (3-pole)
Electronic PXR
electronic
PXR 10 (B) adjustable LSI LSI, MLSI
MCCB Time Power trip units
catalog current Defense PXR 20 (E) current metering / comm opt. LSI, LSIG
curve poster PXR 20D (D) current metering / comm std. LSI, LSIG
PXR 25 (P) power metering / comm std. LSI, LSIG, MLSI, MLSIG

Eaton
1000 Eaton Boulevard Follow us on social media to get the
Cleveland, OH 44122 latest product and support information.
United States
Eaton.com

© 2020 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. MZ012018EN / Z24189 All other trademarks are property
June 2020 of their respective owners.
Molded case circuit breakers

Power Xpert Release (PXR) electronic trip units


MCCB PXR 25 trip unit

Breaker health

ARMS LCD display

Fully programmable
Metering capability
ZSI verification
and testing Enhanced GF
protection
Versatile
communication
Cause of trip LEDs

USB for
PXPM interface

MCCB PXR 10 MCCB PXR features


Features PXR 10 PXR 20 PXR 20D PXR 25

Protection types LSI LSI/LSIG LSI/LSIG LSI/LSIG


Status indication ● ● ● ●
USB secondary injection testing ● ● ● ●
Programmable by USB port (PXPM) ● ● ● ●
Independent instantaneous adjustment ● ● ● ●
Adjustable L, S, I, G pickup and time ● ● ●
Cause of trip indication ▲ ● ● ●
MCCB PXR 20 Load alarm indication with 2 levels ● ● ●
Programmable load alarm levels ● ●
Ground fault protection and alarm ● ● ●
Arcflash Reduction Maintenance SystemE (ARMS) ● ● ●
Available PD3, PD4, PD5, PD6 to meet
NEC 240.87 requirements
Zone selective interlocking (ZSI) with indication ● ● ●
Programmable relays ● ● ●
Modbus RTU communication ● ● ●
CAM module communication ● ● ●
MCCB PXR 20D Rotatable LCD display ● ●
Breaker health and diagnostic monitoring ▲ ● ●
Current metering accuracy 2.0% 0.5% 0.5%
Voltage metering accuracy 0.5%
Power and energy metering accuracy 1.0%

● Standard ● Optional ▲ Available through USB port (PXPM)

Eaton
1000 Eaton Boulevard Follow us on social media to get the
Cleveland, OH 44122 latest product and support information.
United States
Eaton.com

© 2020 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. PA012024EN / Z24120 All other trademarks are property
May 2020 of their respective owners.
Instruction Data
Effective May 2021
Instruction Manual IM01500001E Supersedes February 2020

Pow-R-Line switchboards

Contents
Description Page
Safety measures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Pre-installation: receiving, handling, and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Pre-installation preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Considerations for seismic qualified installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electrical connection of switchboard sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Energizing switchboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

Safety measures Eaton’s liability for any errors or omissions in this document is
limited to the documentary correction of errors. Eaton will not be
This publication contains instructions on the installation of Eaton responsible in any event for errors or omissions in this document
brand Pow-R-Line® low-voltage distribution switchboards. Any person or for any damages, incidental or consequential (including monetary
or persons who designs, purchases, installs, operates, or maintains losses), that might arise from the use of this document or the
new systems using these products must understand the equipment, information contained in it. Information in this publication is not
its markings, and its limitations. intended for use as a training manual for non-qualified personnel.
Hazardous voltages in distribution switchboards and all other The information or statements in this publication concerning the
electrical equipment pose a potential hazard to life and property. suitability, capacity, or performance of the switchboard(s) may not
Please follow instructions, labeling, and applicable codes and cover all configurations of this custom-built product. Eaton has
standards for installation, maintenance, and operation of this made all reasonable efforts to ensure that the instructions in this
equipment and its components. Only “Qualified Persons” should document are adequate and free of material errors and omissions.
install and/or service this equipment. NFPA 70T—National Electrical Eaton will, if necessary, explain issues that may not be covered by
CodeT defines a “Qualified Person” as “One who has skills and the document. The information contained in the instruction leaflet is
knowledge related to the construction and operation of electrical subject to change without notice.
equipment and installations and has received safety training on the
hazards involved.” Introduction
Standard symbols have been established for recognition of potentially This instruction manual is designed to supplement other industry
hazardous situations and conditions. Please review and understand standards including all local, state, and federal codes and safety
the critical warning symbols shown below. These symbols will appear regulations, such as OSHA, NFPA 70 (National Electrical Code),
on safety labels affixed to the product. Installers should always read NFPA 70E (Standard for Electrical Safety Requirements for Employee
and understand these labels before working on equipment. Workplaces), NEMAT PB2.1—General Instructions for Proper
Handling, Installation, Operation and Maintenance of Deadfront
Symbol Meaning
Distribution Switchboards Rated 600 V and Less, other workplace
electrical installation requirements, and all safety rules.
The addition of either symbol to a “Danger” or
“Warning” safety label indicates that an electrical Safety
hazard exists that will result in personal injury if the
instructions are not followed. Due to the weight and size of switchboards and dangers from
electrical hazards, every precaution should be taken to maintain
safe working conditions when handling this equipment. Due to
the custom nature of switchboards and the site variables, every
This is the safety alert symbol. It is used to alert
you to potential personal hazards. Obey all safety potential situation cannot be anticipated. Safety must always be

! messages that follow this symbol to avoid possible


injury and death.
the overriding factor.
Always follow all instructions and all safety guidelines published
by OSHA and other industry and local, state, and federal agencies.

DANGER
“DANGER” INDICATES AN IMMINENTLY HAZARDOUS SITUATION THAT,
IF NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.

WARNING
“WARNING” INDICATES A POTENTIALLY HAZARDOUS SITUATION THAT,
IF NOT AVOIDED, CAN RESULT IN DEATH OR SERIOUS INJURY.

CAUTION
“CAUTION” INDICATES A POTENTIALLY HAZARDOUS SITUATION THAT,
IF NOT AVOIDED, CAN RESULT IN MINOR OR MODERATE INJURY.

CAUTION
“CAUTION” USED WITHOUT THE SAFETY ALERT SYMBOL INDICATES
A POTENTIALLY HAZARDOUS SITUATION THAT, IF NOT AVOIDED, CAN
RESULT IN PROPERTY DAMAGE.

2 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Pre-installation: receiving, Use of lifting means
handling, and storage Lifting means are bolted to each switchboard shipping length.
Lifting a switchboard by crane is the recommended method for
Receiving moving this equipment.
Upon delivery, use the packing list to confirm the number of items
against what was received to ensure that the shipment is complete.
Any discrepancies should be noted on the freight bill before signing. Lifting means
Report any shortages or damage to the freight carrier immediately.
Immediately upon receipt of the switchboard, the plastic covering
should be carefully removed and a thorough inspection of each
section should be made to detect any damage incurred during
shipment. Any damage should be noted on the bill of lading (freight
bill) and the consignee receiving the equipment should notify
the freight carrier. FAILURE TO NOTIFY THE FREIGHT CARRIER
OF DAMAGE IN A TIMELY MANNER MAY RESULT IN THE
CONSIGNEE ASSUMING THE COSTS ASSOCIATED WITH
REPAIR OR REPLACEMENT OF DAMAGED EQUIPMENT.
After inspection, it is recommended that a plastic covering be used
to protect the equipment from dust, dirt, moisture, and damage until
ready for installation.
The switchboard should remain attached to its shipping skid until it
has been moved into its final installation position. Figure 1. Typical indoor lifting means

Handling

WARNING Lifting means


SWITCHBOARD IS TOP-HEAVY. USE CARE IN HANDLING.

Switchboards are top-heavy. Switchboard sections may weigh


more than 2000 pounds. Before moving or lifting, verify that the
equipment used to handle the switchboard is within safe limits of
its lifting capacity.
Switchboard shipping lengths will vary. Each shipping section is
bolted with lag bolts to heavy wooden skids that extend beyond all
sides of the switchboard.

Figure 2. Typical outdoor lifting means

DO NOT pass cables or chains through the holes in the lifting


means. Use cables or chains with hooks or shackles rated for the
load and weight of the switchboard shipping length to be lifted.
Prepare a sling and a spanner or spreader (see Figure 3 and
Figure 4). Eaton does not provide chain, cables, shackles, hooks,
spanner, or spreader.

EATON www.eaton.com 3
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

Chains/cables must be securely attached to hooks, eyes, and shackles,
and the spanner/spreader. Prior to lifting, check the security of the
rigging assembly. Use the crane to bring the assembly taut without
raising the switchboard from the floor.
Check the security of the rigging again. Make any necessary
adjustments before moving the equipment.
Slowly lift equipment to the minimum height from the floor required
to safely relocate it. Move the equipment to approximately 2 inches
above its resting place. Safely make a visual inspection of the
rigging. If necessary, return the switchboard to its original resting
place to make any modifications necessary to the rigging.

Forklifts
Spreader bar A forklift may be used for handling switchboards. Only personnel
trained for that equipment should operate forklifts.
Be sure that the ground surface is solid, and follow all safety
recommendations for operating the forklift. Be aware of wet
or slick floors and surfaces that can affect stopping and turning.
Check labeling on the switchboard packaging material for
additional information.
Verify that the forklift load and lifting ratings are within safe limits
for the weight of the switchboard being lifted.
Do not lift switchboard from the front. Damage to components,
such as breakers, fusible switches, and metering, can result.

CAUTION
SWITCHBOARD IS TOP-HEAVY. USE CARE IN HANDLING.

Figure 3. Front view

Switchboard

Forks Secure
under entire switchboard
switchboard to forklift
with safety
strap here

Figure 5. Forklift

Note: Always use caution when moving switchboards, which are top-heavy
equipment.

The forks or blades of the forklift must run through the entire
switchboard shipping length and be extended to the outermost
sides of the wooden shipping skids (see Figure 5).
Secure the switchboard with a safety strap, belt, or leash approved
for this purpose. Take care in positioning the strap to ensure stability
of the equipment and confirm that it is not in an area that will
damage components.
Slowly lift equipment to the minimum height from the floor required
to safely relocate it.

Figure 4. Side view

4 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Rollers Pre-installation preparation
Rollers should only be used on solid and flat surfaces, such as a The permanent location of switchboards must be on a smooth, solid,
finished floor. Only use rollers that are suitable for this purpose. and level (no more than ±0.125 inches per every 3 feet) foundation.
Alignment is verified in the factory prior to shipment.
Storage
An uneven foundation can cause misalignment of sections, units,
Switchboards that cannot be immediately installed and energized doors, and other parts.
should be stored in an indoor dry, clean, and heated environment.
If a housekeeping pad is used, check factory drawings and verify
Do not store in areas where conditions such as dampness, changes handle height rules relative to the National Electrical Code (NECT)
in temperature, cement dust, or a corrosive atmosphere are present. and utility meter heights where applicable.
Should the storage area be prone to moisture condensation, take When embedded anchors or channel sills are used, materials
precaution by making sure that the switchboard is covered, and and attachments must be adequate to support the structure(s).
install temporary heating equipment. Approximately 250 watts per Switchboard sections must be aligned and level over the length
vertical section are required for average conditions. of the installation.
Switchboards should be placed on solid, level surfaces for storage. From manufacturer’s drawings, determine the layout of the electrical
Switchboard sections must remain in an upright position at all times. distribution equipment for each location. Verify and confirm that
Laying switchboard sections on their back or side can result in the available equipment space and equipment location(s) are in
permanent damage to components and the switchboard structure. compliance with the minimum working space clearances per
Outdoor switchboards are not weather resistant until completely the NEC.
and properly installed and energized. Additionally, using temporary Refer to the manufacturer’s switchboard drawings for available
heating as described above should keep an un-energized outdoor conduit area in each section before installing the finished grade
switchboard dry internally. flooring (see Figure 6). Conduits must be installed in conduit
area shown to ensure compliance with NEC wire bending
space requirements.
Note: Conduit areas may vary in each section of a multi-section
switchboard lineup.

24.00
(609.6)
2.50 12.00 2.50
(63.5) (304.8) (63.5)

2.50 30.00
(63.5) (762.0)
3.00 3.00
(76.2) (76.2)

Dimensions in inches (mm)

Figure 6. Conduit space drawing—floor plan

Note: Used for reference only. See drawings for actual space.

The preferred method of anchoring the switchboard is by fastening


the switchboard to steel channels that are properly and permanently
embedded in a concrete floor or by using anchors designed for
this purpose.
Conduits, floor, and/or wall openings, such as busway or other
penetrations, should be located relative to the space shown on
the manufacturer’s drawings.
Refer to the NEC for installations in damp locations for
additional requirements.
The entire area around the switchboard should be thoroughly
cleaned of all debris.

EATON www.eaton.com 5
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

Considerations for seismic
qualified installations
Switchboards that are “seismic qualified” require additional
considerations. Because electrical equipment is installed as part of
a system, pre-engineering layouts are critical in seismic applications.
When Eaton switchboards are marked as “seismic qualified,”
anchoring the switchboard is critical. Experienced engineers in
seismic requirements should select methods and techniques of 1 2
attachment and tested anchoring systems. Embedded concrete 3 4
anchors or steel attachments must be adequate to resist the forces 5 6
established by the local building code. Bolts of the proper grade of 7 8
steel must be correctly sized and torqued. The embedded anchors 9 10
must be correctly installed in accordance with the method specified 11
by the anchor manufacturer. Refer to seismic instructions in 12
TD01508002E provided by Eaton for more information.
13
Consult applicable local building codes and regulatory agencies for
other specific requirements for seismic installations. Contact Eaton 1 *
* 2
for additional information.

Installation Figure 7. Switchboard A—front view


Use caution and appropriate equipment and practices when moving
switchboard into its final position. Note: Switchboard A has a shipping split between sections 1 and 2. This is
depicted by “*” within the circle between sections.

CAUTION
SWITCHBOARD IS TOP-HEAVY. USE CARE IN HANDLING.

Determine the switchboard orientation with the use of


manufacturer’s drawings and markings on the switchboard sections.
Switchboards may be shipped either in individual sections or in
two or more sections joined by the manufacturer (see Figure 7
and Figure 8).

1 2
3 4
5 6
7 8
9 10
11
12
13

1 2

Figure 8. Switchboard B—front view

Note: Switchboard B, without an asterisk, ships with sections bolted together.

The drawing supplied with the switchboard will indicate the correct
orientation of sections by section number. Each section will have a
label with the ULT listing mark designating “Deadfront Distribution
Switchboard Section ___ of ___.” The manufacturer will fill in the
blanks prior to shipment. An example: The first section of a three-
section switchboard will read “Section 1 of 3.” Section 2 of 3
would be mounted adjacent per the manufacturer’s drawings
(see Figure 9).

Deadfront
switchboard
section

___ of ___

Figure 9. Label illustration

6 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Multi-section switchboards are designed to be front- and rear-aligned
or rear (only) aligned. Drawings provided by the manufacturer and WARNING
located in the switchboard will show footprint details. Orientation, SWITCHBOARD IS TOP-HEAVY. USE CARE IN HANDLING.
as shown on the drawings, must be maintained (see Figure 10
and Figure 11).
Exercise caution while maneuvering top-heavy switchboard sections
into place. Switchboard sections must always remain in the upright
position during installation. Use care when moving the switchboard
so as not to damage the section, including the structural base and
frame. Some switchboards house sensitive components that can be
damaged by rough handling.
Prior to moving the switchboard sections into their permanent
position, make note of all obstacles including conduit stubs.
Implement a plan for safe transition and appropriate means to
Switchboard front view accommodate these obstructions. Take note of conduits entering
through the bottom of the switchboard, the rear of the switchboard,
and at the top of the switchboard to ensure appropriate clearances
Figure 10. Example of front- and rear-aligned switchboard from chassis, structure, cross bus, ground, neutral, and components.
Provide space for a minimum 1/2-inch clearance from the back of
the switchboard and any wall for front-accessible switchboards
installed indoors.
Refer to the NEC for required switchboard clearances.
When unpacking the switchboard, exercise care not to scratch or
mar the finish. Repair all scratches with touch-up paint, which is
available from Eaton. Remove shipping skids and all packaging
material. Remove any temporary shipping braces or spacers.
Remove lifting angles and associated hardware. Plug lifting angle
Switchboard front view holes with hole plugs supplied by the manufacturer (see Figure 12).

Figure 11. Example of rear-aligned (only) switchboard

Sections may contain factory cross bus and/or cable to connect


power between switchboard structures and other components.
Installers should note the location and orientation of all splice plates
and/or cables as reference for installation once sections are joined.
If supplied, remove splice plates and associated hardware, again
Example of hole
noting the orientation for reinstallation once switchboard is in place. plugs installed
If additional hardware is needed to complete these connections,
extra hardware will be provided. For shipping purposes, it will
typically be secured inside one of the structures. Keep bus and
hardware in a clean and protected environment to guard against
damage until reinstallation. Protect any factory-installed cables (wire)
used to connect components between sections from damage when Figure 12. Hole plugs installed
moving switchboard sections into place.
Where two or more switchboard sections are to be joined together,
An outdoor multi-section switchboard will ship with uninstalled
they should first be aligned and all sections leveled.
intermediate roof cap(s) for each joint between sections. Remove
roof cap(s) prior to moving sections into their permanent positions. Once aligned and leveled, attach switchboard sections together.
Retain roof cap(s) and associated hardware for reinstallation.
Keep roof caps and associated hardware in a clean and protected
environment to guard against damage while awaiting reinstallation.
There are two roof designs for outdoor switchboards: the flat roof
design and the sloped roof design.
The standard outdoor switchboard uses a flat roof design, which
does not require any sealant when the intermediate roof cap is
correctly installed in the field.
The optional sloped roof outdoor design also uses an intermediate
roof cap design. When a break occurs between sections for shipping
purposes, the intermediate roof cap on the optional outdoor sloped
roof design shall have a 3/16-inch minimum bead of silicone sealant
(RTV 732) applied to the underneath side of the roof cap. Each roof
cap should have two continuous beads of sealant from end to end.
Each bead must be located between the row of mounting holes and
the outer edge of the roof cap. A tube of sealant is provided with
every outdoor switchboard for customer’s use.
Use caution and appropriate equipment and practices when
moving switchboard into its final position.

EATON www.eaton.com 7
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

Attaching switchboard sections
The manufacturer has provided hardware with the equipment to join
switchboard sections. The hardware includes 3/8 x 1 inch carriage
bolts and 3/8 inch hex nuts with captive Belleville-type washer
(see Figure 13).
Holes are provided on the side of each switchboard section for this
purpose. Three holes are located on the side of each section toward
the front and back. Switchboards with deep designs, including rear-
connected switchboards, may have an additional three holes for
attachment on the center vertical section support (see Figure 14).

Carriage bolt and hex nut


with Belleville washer

Figure 13. Hardware


Bolt sections together
using fasteners supplied
by the manufacturer

Figure 15. Joining switchboard sections

Join sections by using the carriage bolts and hex nuts with captive
Belleville-type washer through the holes provided (see Figure 15).
Section connection While maintaining the level and alignment of the structures, torque
with carriage bolt each connection to the values shown in Appendix A, Table 2.
and hex nut with
Belleville washer If switchboard sections are outdoor type, reinstall roof cap(s).
Visually inspect the roof cap to ensure a reliable, permanent
watertight fit prior to energizing the switchboard.
Once the switchboard structures are attached, visually inspect the
board for foreign objects and visually inspect the structure for proper
clearances of live parts.

Figure 14. Switchboard section connection

8 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Electrical connection of
switchboard sections
Several methods may be used to make electrical connections
within switchboards. More than one of these methods may be
used in a section and/or switchboard lineup. These include bus splice Spacer
plates, factory-installed cable, and busway connections. Consult the
manufacturer’s drawings for details for each switchboard section.
Remove structure deadfront covers and side sheets as needed
to access switchboard chassis and components. Retain all cover
mounting hardware and covers for reassembly. Protect hardware
and parts from moisture, debris, and damage.

Splice plates
Splice plates are short pieces of bus bar that join the main
bus running horizontally through multiple section switchboards.
Depending on the configuration and alignment of the switchboard,
the splice plates used for the main cross bus may vary. These plates
may either be flat or “Z” shaped (see Figure 16 and Figure 17).
Figure 17. Spacer and level (no more than ±0.125 inches per
every 3 feet) foundation

Splice plates are used to attach the main horizontal bus between
switchboard sections or shipping splits. While maintaining the
correct phase orientation and sequence, install splice plates with the
carriage bolts and hex nuts with captive Belleville washers supplied
by the manufacturer. Refer to Appendix A, Table 2 for torque values.
Carriage bolts must align with the corresponding rectangular holes
in the fixed horizontal bus and the splice plates. If multiple splice
plates are used, install in the same sequence as shipped from the
manufacturer. The neutral (when furnished) and ground bus should
be connected in the same manner.
Inspect splices plates and main fixed horizontal bus prior to
installation. If there is any suspected damage, contact the
manufacturer immediately for replacements. NEVER ENERGIZE
ANY SWITCHBOARD WITH DAMAGED BUS OR COMPONENTS.
To accommodate future serviceability, the manufacturer
View "A" recommends that the head of the carriage bolt be mounted from
Typical view when more the rear of the switchboard for FRONT-ACCESSIBLE switchboards
than one bar per phase with the hex nut with Belleville washer positioned to the front.
For REAR-ACCESSIBLE switchboards, the manufacturer
recommends that the head of the carriage bolt be mounted from
Figure 16. Splice plates the front of the switchboard with the hex nut and Belleville washer
positioned to the rear.
For larger amperage switchboards, multiple splice plates are to be Repeat the process until all holes in the horizontal bus are connected
used on the same phase. Maintain the orientation by phase and with bolts and nuts for each shipping split. Inspect connections to
sequence of the splice plates. The orientation of the splice plates ensure that there is no foreign material at the connection point and
must remain identical to the way they were shipped from the that all connections are properly aligned and bolts are seated.
manufacturer. Clearances must be maintained. If you are unsure
about the correct orientation or have questions about the installation, Torque all connections to torque requirements on labels affixed to
contact Eaton before installing the splice plates. each switchboard and as shown in Appendix A, Table 2.

EATON www.eaton.com 9
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

IFS switchboard factory cabling Installation of incoming switchboard connections
Some switchboards use cable/wire for some connections in lieu
of bus. Cabling is typical in Integrated Facility SystemE (IFSE) DANGER
type switchboards that incorporate lighting and appliance branch
circuit panelboards and dry-type distribution transformers within DE-ENERGIZE SWITCHBOARD—HAZARDOUS VOLTAGE. WILL CAUSE
a switchboard lineup. SEVERE INJURY OR DEATH.
Eaton’s selection of wire and cable follows UL 891 switchboard
procedures, National Electrical Manufacturers Association (NEMA), DO NOT work on electrical equipment while it is energized. Verify
Federal Specification standards, and the National Electrical Code that power entering the equipment is de-energized at the source.
standards for IFS switchboards. Power is normally brought into a switchboard either by cable or by
The manufacturer identifies each phase conductor by means of busway (bus duct).
color-coded tape with markings “Factory Installed” in IFS Remove structure covers as needed to access switchboard chassis
switchboards. Markings are affixed to both the line and the load and components. Retain all cover mounting hardware and covers
ends of the conductors. Markings follow the industry-accepted for reassembly. Protect hardware and parts from moisture, debris,
phase colors (see Figure 18 and Table 1). and damage.
Note: As a minimum, all switchboard connections are rated for use with
75 °C or higher rated conductors. When wire is used with temperature ratings
above 75 °C, it shall be sized based on the ampacity of wire rated 75 °C.

Factory Wire/cabling
Installed
When cable connections are used, either mechanical set screw or
compression lugs are typically supplied (see Figure 19). See factory
drawing for specific lug terminations and wire ranges. Some utilities
make their own service entrance connections. In these cases, the
Figure 18. Typical phase “A” 240 Vac wire label manufacturer typically supplies lug landing provisions or a landing
pad in lieu of lugs. These are designed to the specific utility’s
requirements. Refer to the manufacturer’s drawings for specifics
Table 1. Wire label color codes covering this connection.
240 Vac systems Systems above
and below nominal 240 Vac nominal
Phase A Black Phase A Brown
Phase B Red Phase B Orange
Phase C Blue Phase C Yellow
Neutral White Neutral Gray
Ground Green Ground Green

Standard one-hole
Conductors installed by the manufacturer have been cut and
compression-type lug
stripped to predetermined lengths for connection between
components. When conductors are intended to run between
components in two different sections that are joined by the Mechanical set
manufacturer, the manufacturer will connect both the line and screw lug
the load ends of the conductors.
Note: The National Electrical Code restricts the field installation of conductors
that run horizontally through switchboard vertical sections. Refer to the NEC
for specifics.

When there is a shipping split between sections that are cabled, the
factory connects one end of the conductors. The remainder of the
conductors are coiled and secured in the section with the connection. Optional two-hole
compression-type lug
Factory drawings included in the switchboard clearly indicate the
required field connections for the coiled conductors.
Inspect conductors/cables for damage. Any damaged conductors
Figure 19. Screw and compression lugs
must be replaced. Contact manufacturer for replacement.
Factory color-coded markings indicate phasing/neutral and are Unless a switchboard specifically restricts entry to a single means
marked on both the line and the load ends of the conductors. or area, cables may enter through the top, bottom, side, or back of
Using the factory drawings, the installer connects conductors the main incoming section. These restrictions are typically required
to the component(s) indicated on the drawings, keeping phases to conform to wire bending space requirements of the NEC. Consult
correctly oriented. Care should be taken in forming insulated the manufacturer’s drawings for conduit entry data.
cables to ensure that no insulation is forced permanently against
edges of any metal parts.
Torque both line and load connections to values indicated on
the switchboard labeling. Refer to Appendix A, Table 2 for
torque values.

10 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Once the conductors are pulled inside the main section, the Power cable lashing
cables should be formed in the space provided. Clearly identify and
segregate conductors by phase and neutral. Care should be taken A. Cabling to lugs mounted directly on OCPD devices should follow
in forming insulated cables to ensure that no insulation is forced the instructions provided for those devices. Additional cable
permanently against the edges of any metal parts. lashing (Type B) may be required as indicated in C below.
Using appropriate tools, the installer must strip the conductor B. Cable lashing (Type A) is required when the system short-circuit
insulation sufficiently to fill the entire barrel of the connector with current rating (SCCR) is 100 kA or higher, the OCPD frame size
bare, uninsulated conductor. Conductor must be stripped without is at least 1200 A, and the OCPD trip size is 800 A or lower.
damage to the conductor strands. Bare strands should be of equal Additional cable lashing (Type B) may be required as indicated in
length (flush) on the end cut. C below.
Do not strip off more insulation than needed. Exposure of bare C. Cable lashing (Type B) is required when the system SCCR is
conductor outside the lug can compromise clearances. 65 kA or higher and the cable length inside the enclosure is
The connector and conductor should be free of all foreign debris. longer than 48 inches, excluding cable lengths in chassis side
wiring gutters. Type B lashing should repeat throughout the length
Never clip cable/wire strands in order to fit within connectors. If of the conductors. Type B lashing is not required within 36 inches
cable/wire does not match the rating of the connector, contact of the location where the conductors exit the enclosure.
the manufacturer.
Mechanical set screw lugs are the most common. Use an
Rear of structure
antioxidant compound, if required. Insert bare conductor into lug
so the bare conductor fills the full length of the lug body. Tighten
lug, and then torque to levels indicated on the switchboard label.
If compression lugs are used and supplied with the switchboard, the
lugs will be mounted on the incoming lug pad. Remove lugs from
the pad. Use an antioxidant compound, if required. Use a crimping
tool approved for that specific lug manufacturer and lug size. Follow
instructions provided by the manufacturer of the crimp tool.
Once the lug is affixed to the conductor, reinstall the lug on the lug
pad using the existing hardware. Torque hardware using information
provided on the switchboard labeling. Refer to Appendix A, Table 2
for torque values.

Chassis side
wiring gutters

Figure 20. Top view

Rope requirements
• 3/8" diameter

• Nylon, twisted

• Size = #12

• 3 strand

• Tensile strength ≥ 3340 lb/1515 kg

• Working load ≥ 278 lb/126 kg

Figure 21. Cable lashing

EATON www.eaton.com 11
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

Busway
A switchboard may include one or more provisions for connection Recommended Busduct
to Eaton brand busway. Busway can feed the switchboard, be fed hardware for bolting flange
from the load side of an overcurrent device within the switchboard, to flange extensions
Phase Bus
or both. Extension Switchboard
CL ground bus
Switchboards with busway connection(s) contain flange connection 92.00 connection
“tie-bar(s)” assembled in the appropriate section. The tie-bars (2336.8)
will accept the corresponding busway flange extension. Consult 90.50
0.375 Hardware
(2298.7)
switchboard and busway drawings for specifics. The tie-bars are a hex head bolt
transition between the switchboard conductors and the busway flange flat washer
extension, and are assembled as part of the switchboard section. and keps nut.
tighten bolt with
20 lb ft torque

View of three-phase
four-wire busduct centered
in switchboard
X
5.00
CL CL Busduct (127.0)
CL

Rear of enclosure
Y 3.00
Tie-Bar (76.2)

Side view of busduct aligned


from rear of switchboard

Dimensions in inches (mm)

Figure 24. Busway/busduct

The bus assembly is completely formed and drilled for connections,


including phase bussing and neutral, if needed. Additionally,
Figure 22. Downward elbow right flange grounding connections are supplied.
Busway typically enters a switchboard section through the top.
However, busway may attach from the bottom, back, or side of the
switchboard in special configurations (see Figure 24).
Temporary bracing may be provided to support the busway assembly
in the switchboard during shipment. All temporary bracing must be
removed after connections are completed.
The switchboard structure should NOT be used to support any
busway run or flange and extension.
Bolts and hex nuts with captive Belleville washers are supplied by
the manufacturer with the switchboard to connect the switchboard
installed flange and the busway flange. Follow instructions shipped
11.62 with the switchboard and with the busway flange.
(295.2)
minimum When a busway connection is supplied on an outdoor switchboard,
sealing the busway connection is critical. Upon completing the
necessary bus connection, the installer is responsible for sealing the
connection point where the busway flange connects to the chimney
top cover or side/rear cover. A tube of RTV 732 silicone sealant and
Dimensions in inches (mm) a roll of gasketing material are provided with the switchboard for
this purpose.
Figure 23. Standard flange For installation instructions on busway runs, please refer to
NEMA publication BU 1.1-2000, General Instructions for Handling,
The switchboard flange has a corresponding piece shipped with the Installation, Operation and Maintenance of Busway Rated 600 V
busway run. The busway installer attaches the two flange pieces or Less.
together prior to energization (see Figure 22 and Figure 23).

12 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Pre-energizing procedures and inspection Circuit breakers
Before energizing any switchboard, perform a comprehensive Some circuit breaker types provide the ability to adjust trip settings.
inspection to make certain that the switchboard is ready to be When shipped, settings are typically at the minimum rating. There
energized. This includes the following steps: are two types of trip units included in this group: adjustable thermal-
magnetic and electronic trip units.
1. Verify that the switchboard is not energized.
Thermal-magnetic trip units may have an adjustable magnetic
2. Visually inspect the switchboard and remove all foreign setting. Use the engineering study recommendations, if available,
materials, such as tools, scraps of wire, and other debris to adjust to the proper setting. Low magnetic settings feeding high
from all switchboard sections. inrush loads, such as motors, could nuisance trip on startup. For
3. Remove and discard all packing materials and temporary specifics on breaker types, consult the circuit breaker instruction
shipping braces from the switchboard. leaflets shipped with the switchboard.
4. Any accumulation of dust and dirt should be removed with a Electronic trip units have several settings depending on the
vacuum cleaner. Use a lint-free cloth to remove dust and dirt breaker ordered. Electronic trip units may include long-time (L),
on other surfaces. Never use compressed air, as this may blow short-time (S), instantaneous (I), and ground fault (G) settings.
contaminants into electrical and/or electronic components. Never These trip units are available in combinations LS, LSI, LSG, and LSIG.
use solvents or other chemicals to clean surfaces or components. Check the electrical drawings, engineering study, or the engineer’s
recommendations for these trip unit settings. For details on each
5. Visually inspect all ventilation points to ensure that there is no type, refer to the Eaton circuit breaker and electronic trip unit
blockage or debris. Remove any debris that is present. instruction leaflets shipped with the switchboard.
6. Verify that all field bus and wire connections have the proper For breakers with Power XpertT Release (PXR) electronic trip
torque per instructions on the switchboard and on components. units, secondary injection testing can be performed and breaker
7. All factory connections are made using calibrated power tools. reports can be generated by the customer via Eaton’s Power Xpert
However, vibrations do occur in transit and handling. Verify Protection Manager (PXPM) software. A USB cable connection from
factory connections by checking at least 10% of the total factory a host PC to perform these tests will power the trip unit when the
connections for tightness. If this spot check reveals loose trip unit is not otherwise powered. The software and help guides
connections, proceed to check all factory connections. will provide complete instructions for testing long-time, short-time/
These connections include bus hardware connections, circuit instantaneous operations, and optional ground fault operation among
breaker and switch terminals, contactors, metering, and other other functions of the circuit breakers.
connections, including the incoming terminals. For breakers with non-PXR electronic trip units such as 210+, 310+,
8. Visually inspect switchboard insulators, bus bar, and conductors 520 or 1150, a portable test kit is available from Eaton. An auxiliary
for damage. DO NOT ENERGIZE IF DAMAGE IS FOUND. power module is included in the test kit. This auxiliary power module
Contact Eaton. powers the electronic trip unit when the trip unit is not otherwise
powered. The kit includes complete instructions and test times for
9. If fusible switch type overcurrent devices are used, verify that
testing long-time, short-time/instantaneous operations, and optional
proper fusing has been selected and installed. Eaton does not
ground fault operation of the circuit breakers.
typically supply switchboards with these fuses.

Overcurrent devices
Overcurrent devices are typically shipped in either the open (OFF)
or “tripped” position. Manually close, and then open these devices
to ensure that they are functioning properly. At the completion of
this process, be sure that the overcurrent device is in the OFF or
“tripped” position.
Inspect overcurrent devices for any visible damage. If damage is
found, DO NOT ENERGIZE the switchboard. Contact Eaton.

Circuit breaker with Circuit breaker with


adjustable magnetic electronic trip unit
trip unit

Figure 25. Circuit breakers

EATON www.eaton.com 13
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

Overcurrent devices with ground fault protection Current transformers
This switchboard may contain overcurrent devices with ground fault Switchboards containing metering and monitoring equipment may
protection (GFP). The National Electrical Code may require ground contain current transformers (CTs) integral to the switchboard.
fault protection for this installation. Other GFP applications may be Ensure that the load side of the CTs are connected or are shorted
used, including multi-level. Refer to the switchboard drawings and together with terminal block shorting means. Remove shorting
electrical construction drawings for usage and placement within means for normal CT operation with metering equipment. For
the switchboard. additional information and instructions, refer to the instruction
GFP may be installed integral to overcurrent device(s) or as a leaflet shipped with the switchboard.
separate system. Separate systems typically are connected to
Preparing switchboard for insulation/megger testing
a shunt tripping mechanism on an overcurrent device.
Visibly inspect connections on GFP systems, neutral sensors, and
ground connections. Refer to manufacturer’s instructions for details. CAUTION
Prior to shipment, the manufacturer has preset the GFP at minimum FAILURE TO SHORT OR DISCONNECT DURING SWITCHBOARD TESTING
set points. Adjust settings per engineered electrical plan drawings. If WILL RESULT IN FAILURE OF ELECTRONIC COMPONENTS.
this information is not readily available, contact the design engineer
or other qualified persons responsible for the specifics of the Devices installed with control power fusing
installation and system design.
Devices that require control power fusing can be easily damaged
Prior to testing the GFP system, remove the neutral disconnect beyond repair if not disconnected during the testing phase.
link(s) on the switchboard to isolate the neutral of the system from These devices include, but are not limited to, customer metering
the supply and ground. equipment, electronic circuit breaker trip units, motor operators,
Confirm that the neutral connection has been run from the supply and communication equipment.
to the service equipment per the National Electrical Code.
All GFP systems shall be performance tested when first installed WARNING
on site. The test shall be conducted in accordance with instructions
outlined in NEC Article 230.95. This testing shall be conducted by DISCONNECT POWER AT SOURCE BEFORE REMOVING OR INSTALLING
a qualified person(s). A written record of this testing shall be made FUSES. HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH.
and shall be available for the Authority Having Jurisdiction (AHJ).
The interconnected system shall be investigated in accordance with Prior to testing the switchboard, turn off all control power devices
the following instructions. Determine the location of the sensors in the switchboard to prevent damage to components. The control
around the bus of the circuit protected by the GFP system. This can power may be turned off by using the control power switch or by
be accomplished visually with knowledge of which bus is involved. removing the fuses. Components that use power supplies include
Identify all grounding points of the system to verify that ground customer metering and certain breaker accessories, and these must
paths do not exist that would bypass the ground fault sensors. The be isolated before testing.
installed system is to be tested for correct response by application The following label will appear on the equipment:
of full-scale current into the equipment to duplicate a ground fault
condition, or by equivalent means. It is recommended that this be
performed by a qualified testing organization. Record the test date
and results on the form provided in Appendix C of this instruction
manual. Those in charge of the site’s electrical installation should
retain the completed form and make it available to the AHJ.
Due to the varied types of devices and GFP systems available,
detailed testing instructions can vary. For detailed instructions,
identify the specific type of device and GFP system provided. Then
refer to the separate instructions for that specific type of device.

CAUTION
DO NOT TEST A CIRCUIT BREAKER WHILE IT’S IN SERVICE
AND ENERGIZED.

CAUTION
TESTING OF A CIRCUIT BREAKER THAT RESULTS IN THE TRIPPING
OF THE CIRCUIT BREAKER SHOULD BE DONE ONLY WHEN THE
SWITCHBOARD IS DE-ENERGIZED.

14 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Pre-energizing switchboard insulation testing
CAUTION
Exercise extreme care to prevent the equipment from being
FAILURE TO DISCONNECT CONTROL POWER DURING SWITCHBOARD connected to the power source while tests are being conducted.
TESTING WILL RESULT IN FAILURE OF ELECTRONIC COMPONENTS.
Prior to energizing the switchboard, perform a Megger or DC test
of the switchboard’s insulation. With the neutral isolated from the
Failure to disconnect control power during switchboard ground and the switches and/or circuit breakers open, conduct
testing will result in failure of electronic components and electrical insulation resistance tests from phase to phase, phase to
void manufacturer’s warranty. ground, phase to neutral, and neutral to ground. Retain results for use
to compare to results produced in the future. A form for recording test
Surge protective devices (SPDs) results is provided in the appendix of this document. Prior
Prior to testing the switchboard, disconnect line and neutral to testing, remove all control power fusing and connections to
connections to all SPD units in the switchboard. Keep hardware products, which will be damaged in this test. See above.
in a clean and protected environment to guard against damage
until reinstallation.
WARNING
TO PREVENT DAMAGE TO GROUND FAULT CONTROL CIRCUITS,
CAUTION METERING CIRCUITS, OR OTHER CONTROL CIRCUITS WHEN
FAILURE TO DISCONNECT LINE AND NEUTRAL DURING TESTING MEGGERING SWITCHBOARD, ISOLATE CIRCUITS FROM SWITCHBOARD
WILL CAUSE THE TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) SYSTEM BEFORE BEGINNING THE MEGGER OPERATION. BE SURE TO
AND SPD SURGE PROTECTION SYSTEM TO FAIL AND WILL VOID THE RECONNECT THOSE CIRCUITS AFTER MEGGER TESTS ARE COMPLETED.
WARRANTY ON THE DEVICE.
NOTE: SOME GROUND FAULT CIRCUITS MAY NOT BE FUSED;
Failure to disconnect line and neutral during testing will THEREFORE, ISOLATION OF THOSE CIRCUITS REQUIRES
900P241H01
cause the SPD surge protection system to fail and will void the 900P241H02
DISCONNECTING WIRING FROM BUS BARS.
warranty on the device. After testing, reinstall all connections.
FOR USE ON SWITCHBOARDS FOR USE testing.
DO NOT USE AC dielectric ON PRL1A/2A/3A/3E PANELS
The following label will AND
appear on the equipment:
POW-R-LINE 4 PANELS

WARNING
Warning Warning
DO NOT USE AC DIELECTRIC/MEGGER TESTING.

A test resulting in TO
readings
AVOID at or above 1 megaohm
EQUIPMENT is satisfactory.
DAMAGE
TO AVOID EQUIPMENT
DAMAGE DO NOT HI-POT OR Post-testing DO NOT HI-POT OR MEGGER
MEGGER THIS DEVICE THIS DEVICE
After testing, and with the switchboard de-energized, reconnect all
CONTROL DISCONNECT LOCATED BEHIND DOOR
WITH LABEL WHICH IDENTIFIES LOCATION OF
devices, control fusing, and disconnects
DISCONNECT removed
ALL PHASE prior to testing.
AND NEUTRAL
"ON-OFF" SWITCH. Reattach SPDs. SUPPLY CONNECTORS TO THE SURGE
PROTECTIVE DEVICE.
TURN SWITCH "OFF" AND DISCONNECT NEUTRAL AT Securing the switchboard 900P241H02 R1
SURGE PROTECTIVE DEVICE.
900P241H01 R1
Reinstall all side covers, deadfront plates, doors, and trim parts
on the switchboard using hardware supplied by the manufacturer.
Take caution that conductors are not pinched between parts when
installing the deadfront, cover plates, side sheets, and filler plates.
All parts should be aligned and secured when installed. Do not leave
holes or gaps in the deadfront construction. Clean up any debris in
and around the switchboard.

EATON www.eaton.com 15
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

Energizing switchboard Maintenance
It is essential to maintain the equipment in satisfactory condition.
WARNING To ensure continued quality service, a systematic maintenance
HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH. schedule is vital. Facility operation and local conditions vary to such
an extent that the schedule must be prepared to suit the conditions.
The maintenance schedule for individual devices, such as circuit
breakers, meters, fusible switches, and so on, should be based upon
WARNING recommendations contained in the individual instruction leaflet for
each device. Inspection and test operations should be coordinated
ONLY THOSE PROFESSIONALS TRAINED AND QUALIFIED ON with an overall testing program to result in the least operating
ELECTRICAL DISTRIBUTION SWITCHBOARDS SHOULD INSTALL AND/OR inconvenience and system shutdowns.
SERVICE THIS EQUIPMENT.

Extreme hazards can exist when energizing electrical distribution DANGER


equipment and switchboards. Take all precautions necessary to HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH.
protect people and property when energizing the equipment. Short DE-ENERGIZE SWITCHBOARD PRIOR TO SERVICING.
circuits and ground faults may exist as a result from inadequate
installation. Short circuits and ground faults within the switchboard
can cause catastrophic damage, injury, and death.

1. Prior to energizing the switchboard, turn OFF all overcurrent WARNING


devices and loads internal to the switchboard plus mains in ONLY THOSE PROFESSIONALS TRAINED AND QUALIFIED ON
downstream equipment. ELECTRICAL DISTRIBUTION SWITCHBOARDS SHOULD INSTALL AND/OR
2. Verify and follow the sequence of energizing circuits and loads. SERVICE THIS EQUIPMENT.
Verify phase sequencing on loads, such as motors, that can be
damaged or destroyed by incorrect phase connections. Prior to performing any maintenance on the switchboard,
3. If provided, use remote operators to close and energize first de-energize the switchboard at the source. Use lockout/
switchboard, overcurrent devices, and loads. tagout precautions as prescribed in OSHA, NFPA 70E, and
other safety manuals.
4. Beginning with the main(s), turn ON each overcurrent device.
The switchboard should be given a thorough maintenance
check annually.
Exercise extreme care to prevent the equipment from being
connected to the power source while tests are being conducted.

16 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Switchboard insulation resistance testing Switchboard insulation resistance testing
Maintenance before cleaning Maintenance after cleaning
Prior to cleaning, perform an initial Megger or DC test of the After cleaning, perform a second Megger or DC test of the
switchboard insulation, between phases and ground. Inspect for switchboard insulation between phases and ground.
symptoms that may indicate overheating or weakened insulation. Prior to testing, remove all control power fusing and connections
Record test readings. Refer to NEMA publication AB-4, Guidelines to products, which will be damaged in this test. This includes
for Inspection and Preventative Maintenance of Molded-Case Circuit all components with control wire fusing, TVSS, SPDs, metering
Breakers Used in Commercial and Industrial Application. equipment, and so on.
Prior to testing, remove all control power fusing and connections
to products, which will be damaged in this test. This includes
all components with control wire fusing, TVSS, SPDs, metering WARNING
equipment, and so on. TO PREVENT DAMAGE TO GROUND FAULT CONTROL CIRCUITS,
METERING CIRCUITS, SPD, OR OTHER CONTROL CIRCUITS, WHEN
MEGGERING SWITCHBOARD, ISOLATE CIRCUITS FROM SWITCHBOARD
WARNING SYSTEM BEFORE BEGINNING THE MEGGER OPERATION. BE SURE TO
TO PREVENT DAMAGE TO GROUND FAULT CONTROL CIRCUITS, RECONNECT THOSE CIRCUITS AFTER MEGGER TESTS ARE COMPLETED.
METERING CIRCUITS, SPD, OR OTHER CONTROL CIRCUITS, WHEN
MEGGERING SWITCHBOARD, ISOLATE CIRCUITS FROM SWITCHBOARD NOTE: SOME GROUND FAULT CIRCUITS MAY NOT BE FUSED;
SYSTEM BEFORE BEGINNING THE MEGGER OPERATION. BE SURE TO THEREFORE, ISOLATION OF THOSE CIRCUITS REQUIRES
RECONNECT THOSE CIRCUITS AFTER MEGGER TESTS ARE COMPLETED. DISCONNECTING WIRING FROM BUS BARS.

NOTE: SOME GROUND FAULT CIRCUITS MAY NOT BE FUSED; DO NOT USE AC dielectric testing.
THEREFORE, ISOLATION OF THOSE CIRCUITS REQUIRES
DISCONNECTING WIRING FROM BUS BARS.
WARNING
DO NOT USE AC dielectric testing. DO NOT USE ALTERNATING CURRENT (AC) DIELECTRIC/MEGGER
TESTING. DAMAGE TO COMPONENTS WILL OCCUR.
WARNING
A test resulting in readings at or above 1 megaohm is satisfactory.
DO NOT USE ALTERNATING CURRENT (AC) DIELECTRIC/MEGGER
TESTING. DAMAGE TO COMPONENTS WILL OCCUR. Compare these test readings with prior readings and retain with
previous testing for future comparisons. Trends of lowered insulation
resistance are signs of potential problems. A Switchboard Inspection
Cleaning Log form is provided in Appendix B to record readings.
While the switchboard is de-energized, remove dust and debris from
bus bars, connections, supports, and enclosure surfaces. A vacuum Bus and cable connections
cleaner with a long nozzle will be of assistance. Wipe clean with a
lint-free cloth. Do not use solvents to clean equipment, as damage 1. Inspect bus bar and cables for visible damage.
to surfaces can occur. 2. Visually inspect connections for overheating and damage.
Should the switchboard be exposed to adverse conditions, such as 3. All bus bar and cable connections should be checked and
airborne contaminants, more frequent inspections and cleaning may torqued in accordance with labeling on the switchboard.
be required. Refer to Appendix A, Table 2 for torque values.
4. Inspect for broken wire strands and pinched or damaged
WARNING insulation on cable connections.
DO NOT USE COMPRESSED AIR TO CLEAN OR BLOW OUT DEBRIS OR Insulation
DUST IN SWITCHBOARDS.
All bus bar and structure insulation in the switchboard, including bus
supports, bus shields, bus bracing, insulating barriers, and so on,
Use of compressed air to clean or blow out debris in switchboards should be visually checked for damage. Replace damaged parts.
may imbed the contaminants within overcurrent devices, metering The life of insulation material is dependent on keeping the material
equipment, and other components. Damage to insulation and other dry and clean.
surface materials can occur. Do not use compressed air in cleaning.

EATON www.eaton.com 17
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

Overcurrent devices Ventilation
Maintenance instructions and field-testing for overcurrent devices Check all grills and ventilation ports for obstructions and
are included with the instruction leaflet for each device within a family. accumulations of dirt. Clean ventilation ports, if necessary. For
One instruction leaflet per frame or family type was included with switchboards installed outdoors, inspect the air space under the
this installation booklet inside the switchboard. Refer to the leaflet switchboard to be sure that it is clean and clear of debris, leaves,
on each device. If leaflets are missing, contact Eaton for replacement. and obstructions.

Circuit breakers Records


Visually inspect circuit breakers for signs of discoloration, cracking, It is essential to maintain the equipment in satisfactory condition.
scorching, overheating, or broken parts. Exercise the breaker operating Maintain a permanent record of all maintenance activities and
mechanism, making sure it is opening and closing. A breaker testing for future reference (see Appendix B).
showing signs of any one of these issues should be replaced.
Refer to NEMA publication AB-4, Guidelines for Inspection and The condition of each switchboard should be recorded as a guide
Preventative Maintenance of Molded-Case Circuit Breakers Used for anticipating the need for any replacement parts or components
in Commercial and Industrial Applications. or special attention at the next regular maintenance period. It is
recommended that a series of inspections be made at quarterly
Fusible overcurrent devices intervals until the progressive effects of local conditions can be
analyzed to determine a regular schedule.
Visually inspect the switching mechanism and fuse connections.
Visually inspect the fusible devices for signs of discoloration, cracking, Switchboard events and service interruptions
scorching, overheating, or broken parts. Replace any worn parts or
the entire switch. Short-circuits, ground faults, and overloads

Fuse replacement
WARNING
DO NOT ATTEMPT TO RE-ENERGIZE SWITCHBOARD OVERCURRENT
DANGER DEVICES AFTER ELECTRICAL EVENTS, SUCH AS SHORT CIRCUITS,
HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH. GROUND FAULTS, AND OVERLOADS, UNTIL THE CAUSE OF THE EVENT
DE-ENERGIZE BOARD PRIOR TO SERVICING FUSIBLE DEVICES. HAS BEEN IDENTIFIED AND CORRECTED.

Be sure the switch mechanism is turned to the OFF position before A thorough assessment, identification, and correction of the
attempting to remove fuses. Visually inspect the switch contacts, event origin must be completed. An additional assessment of the
blades, and mechanism to ensure that the mechanism is in the conductor insulation and other insulating materials should be made.
OPEN/OFF position. Replace all damaged insulation materials, conductors, and over-
Check fuses to ensure that they are of the proper class, ampere, current devices. Original switchboard parts, insulators, insulation
voltage, and interrupting rating. Ensure that non–current-limiting material, and overcurrent devices must be replaced with renewal
fuses are not used as replacements for current-limiting fuses. parts from Eaton (see “Renewal parts,” page 19).
Never attempt to defeat rejection mechanisms that are provided Do not attempt to re-energize switchboard overcurrent
to prevent the installation of the incorrect class of fuse. components after electrical events, such as short circuits,
ground faults, and overloads, until the cause of the event
Meters, controllers, surge equipment, and other devices has been identified and corrected.
Individual devices should be maintained according to the specific After the event has been rectified, test equipment per the
instructions supplied for each device. Remove dust and dirt from maintenance process described in this publication.
exterior with a dry lint-free cloth. Unless specifically instructed in
the individual device instruction leaflet, do not attempt to open Physical damage
sealed cases or containers. Any physical damage to the switchboard that occurs after the
switchboard is installed must be corrected. A thorough inspection,
WARNING which includes the exterior enclosure and deadfront, plus interior
components in the damaged portion of the switchboard, should be
NEVER USE COMPRESSED AIR TO CLEAN OR BLOW OUT DEBRIS OR conducted. Replace all damaged parts and components. Ensure that
DUST IN SWITCHBOARDS. there are no gaps in the switchboard enclosure that could cause
exposure to live parts. Contact Eaton for renewal parts and assistance.
Secondary wiring After the physical damage has been corrected, test equipment per
Check all wiring connections for tightness, including those at the the maintenance process described in this publication.
current and potential transformers, if present, and at all terminal
blocks. Check all secondary wiring connections to ensure that
they are properly connected to the switchboard ground bus,
where indicated. Look for broken wire strands and pinched or
damaged insulation.

18 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Water damage Renewal parts
Switchboards can be complex assemblies with unique parts to fit
DANGER the specific application and need. The manufacturer offers expertise
with renewal part identification. To ensure safety and to maintain
WET SWITCHBOARDS PRESENT A HAZARDOUS CONDITION AND MAY UL listing, it is essential that only new parts and components
CAUSE INJURY OR DEATH. DE-ENERGIZE POWER TO ALL EQUIPMENT from Eaton be used.
BEFORE SERVICING.
When ordering renewal parts or when requesting information on
the switchboard, it is essential to include as much information
DO NOT WORK ON SURFACES OR FLOORS WHERE THERE IS as possible.
STANDING WATER.
Each switchboard will have a nameplate and other identification
marks with details that will help expedite information requests and
DANGER orders. The following may be required to help identify parts and
information requests:
DO NOT WORK ON SWITCHBOARDS OR ENTER AREAS THAT HAVE
STANDING WATER. DE-ENERGIZE ALL EQUIPMENT IN AREAS WITH • GO or General Order Number
STANDING WATER. • Item number
• Description of the equipment
DO NOT WORK ON WET ENERGIZED ELECTRICAL EQUIPMENT.
• Supply voltage
Major accumulation of water or moisture on any part of the
switchboard can cause catastrophic damage to the switchboard. If a • Equipment ratings
switchboard has been submerged by more than 2 inches or where • Catalog number or style number of part, if available
running or standing water has had contact with current-carrying
parts, it has sustained significant damage. • Description of the part
• Drawing numbers
WARNING • Rating of part(s)
SWITCHBOARD COMPONENTS, INCLUDING CIRCUIT BREAKERS, Electrical distribution equipment has a limited life span. As such,
FUSIBLE SWITCHES, METERING, AND SO ON, SUBJECTED TO WATER OR the manufacturer cannot guarantee the availability of obsolete
MOISTURE MAY BE RENDERED UNSAFE. REPLACEMENT IS REQUIRED. equipment or parts. Equipment replacement may be recommended.

The switchboard and its components may be damaged beyond


repair and may need replacement.

1. Do not attempt to clean or repair water-damaged equipment


or components.
2. De-energize the switchboard at its source.
3. Do not energize.
4. Contact Eaton for replacement.

Minor accumulations of moisture, such as condensation, over


a short period of time, may be corrected using heat.
De-energize switchboard.
Apply approximately 250 watts per vertical section for a sufficient
period of time until the moisture disappears, and then remove all
heat sources and materials used for drying.
Inspect for damage to components and any corrosion. If any damage
or corrosion is present, contact Eaton. DO NOT RE-ENERGIZE
SWITCHBOARD.
After the switchboard has dried completely, remove all materials and
tools from the equipment. Inspect all connections for damage and
torque. Reinstall all covers, fillers, deadfront assemblies, and side
sheets. Conduct switchboard insulation resistance testing described
in this publication.

EATON www.eaton.com 19
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

Appendices
Appendix A Appendix B

Table 2. Torque values for copper or aluminum Switchboard maintenance, testing, and inspection logs
bus bar connections Refer to the “Maintenance” section of this document on page 16
Bolt size Torque (lb-in) Torque (lb-ft) for detailed information.
#10 30 2.5
1/4" 65 5.4 DANGER
5/16" 130 10.8 HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH.
3/8" 240 20.0 DE-ENERGIZE SWITCHBOARD PRIOR TO SERVICING FUSIBLE DEVICES.
1/2" 600 50.0 ONLY “QUALIFIED PERSONS” SHOULD INSTALL AND OR SERVICE THIS
EQUIPMENT.
Note: For other torque values, refer to the instruction leaflet for the
specific component.

WARNING
TO PREVENT DAMAGE TO GROUND FAULT CONTROL CIRCUITS,
METERING CIRCUITS, SURGE PROTECTIVE DEVICE (SPD), OR OTHER
CONTROL CIRCUITS, WHEN MEGGERING SWITCHBOARD, ISOLATE
CIRCUITS FROM SWITCHBOARD SYSTEM BEFORE BEGINNING THE
MEGGER OPERATION. BE SURE TO RECONNECT THOSE CIRCUITS AFTER
MEGGER TESTS ARE COMPLETED.

NOTE: SOME GROUND FAULT CIRCUITS MAY NOT BE FUSED;


THEREFORE, ISOLATION OF THOSE CIRCUITS REQUIRES
DISCONNECTING WIRING FROM BUS BARS.

WARNING
DO NOT USE ALTERNATING CURRENT (AC) DIELECTRIC/MEGGER
TESTING. DAMAGE TO COMPONENTS WILL OCCUR.

20 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Table 3. Initial insulation resistance test record
Date All overcurrent devices open
Phase-to-phase connections Phase-to-ground connections Neutral-ground
A-B A-C B-C A—Ground B—Ground C—Ground connection

Date All overcurrent devices closed


Phase-to-phase connections Phase-to-ground connections Neutral-ground
A-B A-C B-C A—Ground B—Ground C—Ground connection

Notes:

Date All overcurrent devices open


Phase-to-phase connections Phase-to-ground connections Neutral-ground
A-B A-C B-C A—Ground B—Ground C—Ground connection

Date All overcurrent devices closed


Phase-to-phase connections Phase-to-ground connections Neutral-ground
A-B A-C B-C A—Ground B—Ground C—Ground connection

Notes:

Date All overcurrent devices open


Phase-to-phase connections Phase-to-ground connections Neutral-ground
A-B A-C B-C A—Ground B—Ground C—Ground connection

Date All overcurrent devices closed


Phase-to-phase connections Phase-to-ground connections Neutral-ground
A-B A-C B-C A—Ground B—Ground C—Ground connection

Notes:

Date All overcurrent devices open


Phase-to-phase connections Phase-to-ground connections Neutral-ground
A-B A-C B-C A—Ground B—Ground C—Ground connection

Date All overcurrent devices closed


Phase-to-phase connections Phase-to-ground connections Neutral-ground
A-B A-C B-C A—Ground B—Ground C—Ground connection

Notes:

EATON www.eaton.com 21
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021 

Table 4. Switchboard inspection log
Date Checklist 3 Notes and actions taken
Cleaning
Bus and cable connections
Insulation inspection
Overcurrent device inspection
Meters
Controllers
Surge protective devices
Other protective devices
Secondary/control wiring
Clean ventilation

Date Checklist 3 Notes and actions taken


Cleaning
Bus and cable connections
Insulation inspection
Overcurrent device inspection
Meters
Controllers
Surge protective devices
Other protective devices
Secondary/control wiring
Clean ventilation

Date Checklist 3 Notes and actions taken


Cleaning
Bus and cable connections
Insulation inspection
Overcurrent device inspection
Meters
Controllers
Surge protective devices
Other protective devices
Secondary/control wiring
Clean ventilation

Note: Refer to the “Maintenance” section on page 16.

22 EATON www.eaton.com
Pow-R-Line switchboards Instruction Manual IM01500001E
 Effective May 2021

Appendix C

Table 5. Ground fault test record form


Ground fault test records should be retained by those in charge of the building’s electrical installation
in order to be available to the Authority Having Jurisdiction.
Test date Circuit breaker number Results Tested by

EATON www.eaton.com 23
Instruction Manual IM01500001E Pow-R-Line switchboards
Effective May 2021

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

© 2021 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. IM01500001E / Z25103 All other trademarks are property
May 2021 of their respective owners.

You might also like