Professional Documents
Culture Documents
SYSTEM PROTECTION
Distributed Generation: Impact on
Protection
Content prepared by Dr Campbell Booth
University of Strathclyde
Overview
– Converter-interfaced sources
– Use of DC for distribution?
Protection solutions?
Distributed Generation Basics
Technologies
Small and Large scale combined heat and power units
Energy from waste units
Wind Farms
Tidal and wave energy units
Stand-by generators (diesel)
Operated radially
Designed for unidirectional power flow
Protected with over-current protection relays, reclosers
and fuses
11 kV
11 kV
Islanding operation
11 kV
Protection of Distribution Networks
132/33kV
Distance, differential (some), overcurrent
11kV/415V
Overcurrent, reclosers, sectionalisers, fuses, RCDs
Remember, majority of faults transient – fuses should only operate if
fault is permanent
Typically, faults are isolated very quickly by reclosers, multiple
reclose attempts are attempted, and if fault is permanent and
downstream of fuses, fuses ultimately melt while system is in
reclosed state
Reclose is then successful
If permanent fault between recloser and fuse, then recloser will lock-
out after pre-defined number of attempts
Automatic sectionalisers/smart links sometimes used
Protection of Distribution Networks
(HV/MV)
t t
Relay 1 Relay 2
tF2 Fault 2
tF1 Fault 1 tF2 Fault 2
I I
Source
A Fault 1 B Fault 2
SpurA8 SpurB5
SpurA9
SpurA10
Protection of distribution networks
(MV/LV)
Gers and Holmes
“Protection of
Transient fault
Electricity
Distribution
Recloser will
Networks”,
IEE Power & successfully reclose
Energy Series 47
Permanent fault
Recloser will reclose
multiple times (with
variable delays before
re-opening) and fuse will
melt before max
reclosures attempted
Sectionalisers/“smart
links” may be used
instead of, or to “save”
fuses
Protection of distribution networks
(MV/LV)
2
1
0
Fuse
A B C
Permanent Fault
Fault inception t
Protection of distribution networks
(MV/LV)
IDMT
PMAR Sectionaliser
Fuse
A B C
Transient Fault
Fault inception t
Protection of distribution networks
(MV/LV)
http://www.hubbellpowersystems.com/catalogs/switching/10D-Elec_Sect.pdf
Fault Behaviour – no DG
11kV 30MVA Source (Zsource= j4.03W) j1W impedance to fault (ZAB=j0.2W)
Operate
Operate (quickly) Don’t operate
(after a delay)
Source
(Grid)
A B C
V=IZ
Fault Behaviour – with DG
11kV 30MVA Source (Zsource= j4.03W) j1W impedance to fault (ZAB=j0.2W)
Operate
Operate (quickly) Don’t operate
(after a delay)
Source
(Grid)
DG fault
A contribution B C
14MVA
V
With DG at B
V=IZ No DG
Equivalent circuit – no DG
Grid
j4.03W
If Z from source to fault = j1W
(j0.2W for first feeder + j0.8 W for second
VA = 1263x1=1263V A feeder):
VB = 1263x0.8=1010V B V
With DG at B
V=I/Z No DG
j0.8W
Equivalent circuit – with DG
Grid DG
Z from sources to fault =
j4.23//j8.64 + j0.8 = j3.64W
VB = 1745x0.8=1396V B
V
With DG at B
0.8W
V=I/Z No DG
Protection issues - “blinding”
Fault current as measured at
upstream relay with no
downstream DG
If
Protection issues - “blinding”
Fault current as measured at Fault current as measured at
upstream relay with no upstream relay with significant
downstream DG downstream DG
t t
If If
Under very high DG penetrations and very low grid infeed, infeed from
grid could be markedly reduced, therefore increasing risk of feeder
protection “blinding” (slow or non-operation of relay at A for backup
scenario in this case).
0.8W
Infeed=500A
D
E
G59 – DG interface protection settings
Protection issues – generator tripping
on undervoltage
Source
(Grid)
Z=0.6W
Infeed=
4500A Fault current=5000A
(4500+500)A
A B C
VA=VD=5000x0.6=3000V
V=0 (less than 50% nominal)
VED=500x0.8=400V, therefore
VE=3400V
Infeed=500A
D
E
Protection issues - DG impact on
instantaneous (“high set”) protection
Protection issues - DG impact on
instantaneous (“high set”) protection
Operate? Operate (time delay) Operate (instant)
1 2 3
If
Protection issues - DG impact on
instantaneous (“high set”) protection
1 DG 2 3
If(at 2 and 3)
Protection issues - DG impact on
directional protection
Sensitive and fast acting Looks “up”
directional protection here into line
(Ithreshold=10% of rated – prevents R2
line current) operating
for this fault
DG on load side – R’1 R’2 (and possibly R1 and R2) might maloperate?
Even under load conditions – back-feed if DG>local load?
Protection
issues - DG
impact on
directional
protection Fault as shown:
R5’ operates after 1.7
(R6’ after 2.1)
R2 after 0.5
(R3 after 0.9)
Use of overcurrent
relays for protection
of ring mains
From NPAG: -
chapter 9
Protection
issues - DG
impact on
directional
protection
Additional DG
contribution may
result in
coordination
Use of overcurrent problems?
relays for protection R1’ will operate
of ring mains for this scenario?
From NPAG: -
chapter 9
Impact on section
switches/fuses/…?
IDMT
PMAR Sectionaliser
Fuse
A B C
Blinding/maloperation/impact on automation/auto-
reclose/sectionaliser logic?
Possible problems if DG penetration/fault contribution
is high?
Performance in islanded mode – if permitted?