SAFETY RISK FIELD AUDIT

PENDING REPORT – P&M


DEPARTMENT

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. 226+240 VUP Date 03.11.2022 Status PENDING

Observation: Reverse horn found not working on dumper (MP 28H 0743)

Corrective action Reverse horn needs to be provided on dumper

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch 215+500 Date 06.11.2022 Status PENDING

Observation: Grinding machine found without guards

Corrective action Ensure guards on machines

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp- Date 10.11.2022 Status PENDING

Observation: Observed in-adequate dust collection arrangements

Corrective action Proper dust collection methods to be provided

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp- Date 10.11.2022 Status PENDING

Observation: Lighting arrestor not provided on silos

Corrective action Lighting arrestor needs to be provided

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp- Date 10.11.2022 Status PENDING

Observation: Pull chord switches not provided on conveyor belt

Corrective action Pull chord arrangements to be fixed

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp- Date 10.11.2022 Status PENDING

Observation: Ladder found to be in damaged condition

Corrective action Ladder needs to be repaired

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp Date 10.11.2022 Status PENDING

Observation: Stability drawing and third party certificates not available

Corrective action Ensure availability of Stability drawing and third party certificates

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch.195+960 Date 11.11.2022 Status PENDING

Observation: Gas cutting set found without cylinder trolley, flash back arrestor,
regulators and without fire extinguisher

Corrective action Ensure safety arrangements during gas cutting operation

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch.195+960 Date 11.11.2022 Status PENDING

Observation: Gas cylinder found to be lying on ground

Corrective action Gas cylinder shall be stored in vertically upright position

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch.195+960 Date 11.11.2022 Status PENDING

Observation: Grinding machine found without guards.

Corrective action Ensure availability of guards on machines

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. No. 221+920 Date 16.11.2022 Status PENDING

Observation: Grinding machine found without guards.

Corrective action Ensure availability of guards on machines

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. 225+050 Date 19.11.2022 Status PENDING

Observation: Operator found to be using mobile phone during Motor Grader


operation
Corrective action Mobile phone shall not be used during working

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Nandi Camp Date 10.12.2022 Status PENDING

Observation: Observed stagnation of water

Corrective action Water stagnation to be avoided

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Nandi Camp Date 10.12.2022 Status PENDING

Observation: Access way found obstructed

Corrective action Access way should be kept clear of materials

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Nandi Camp Date 10.12.2022 Status PENDING

Observation: Observed fugitive dust formation

Corrective action Dust suppression method to be adopted

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. No. 231+700 - Date 15.12.2022 Status PENDING

Observation: Safety guard found in damaged condition of chop saw cutting machine

Corrective action Guard shall be in proper working condition

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Nandi Camp Date 18.12.2022 Status PENDING

Observation: Observed improper stacking of materials at workshop area

Corrective action Proper stacking of materials to be adopted

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Nandi Camp - Date 18.12.2022 Status PENDING

Observation: Workmen found traveling on hydra

Corrective action Proper arrangements to be made for workmen shifting

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Nandi Camp Date 18.12.2022 Status PENDING

Observation: Gas cylinder laying on ground

Corrective action Gas cylinder shall be stored in upright position with proper securing
arrangements
LOCATION: Nandi Camp Date 18.12.2022 Status PENDING

Observation: Observed improper disposal and storage of hazardous materials

Corrective action Proper storage and disposal of hazardous materials needs to be adopted

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch 210 Date 20.10.2022 Status PENDING

Observation: Cable jointed using masking tape

Corrective action Proper joining arrangement to be made available

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. 221+020 VUP Date 28.10.2022 Status PENDING

Observation: Improper joining of electrical cable found at site

Corrective action Proper joining of electrical cable to be ensured

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch.195+960 Date 11.11.2022 Status PENDING

Observation: Improper electrical connection found at site

Corrective action Ensure proper electrical connection

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp- Date 16.11.2022 Status PENDING

Observation: Observed improper electrical connection

Corrective action Proper electrical connection to be ensured

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp Date 16.11.2022 Status PENDING

Observation: Observed electrical board without cover

Corrective action Ensure availability standard electrical boards

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Nandi Camp Date 10.12.2022 Status PENDING

Observation: Observed Improper joining of electric cable

Corrective action Proper joining kit to be used

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. No. 231+700 Date 15.12.2022 Status PENDING

Observation: Observed Improper joining of electrical cable

Corrective action Ensure joining of electrical cable with proper joining kit

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. No. 231+700 Date 15.12.2022 Status PENDING

Observation: Non-standard electrical distribution board found used for electrical


connection

Corrective action Standard electrical distribution board to be used

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. No. 231+700 Date 15.12.2022 Status PENDING

Observation: Earth clamp found in damaged condition

Corrective action Earth clamp needs to be replaced

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. No. 221+348 Date 06.01.2023 Status PENDING

Observation: Electrical cable found routed through water

Corrective action Electrical cable shall be properly routed, either underground or overhead

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. 227+620 Date 07.01.2023 Status PENDING

Observation: Reverse horn not working on Motor Grader (WIPLMGR004)

Corrective action Reverse horn shall be repaired

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch.226 Date 08.01.2023 Status PENDING

Observation: Single insulated cable found used for electrical connections and observed
improper jointing on cable
Corrective action Proper jointing of electrical cable to be adopted, Double insulated cable
to be ensured

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. 198+160 FLO Date 11.01.2023 Status PENDING

Observation: Non standard return path of welding machine is found

Corrective action Standard return path to be provided

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. 198+160 FLO Date 11.01.2023 Status PENDING

Observation: Non standard electrical joint is found for electrical use

Corrective action Standard electrical joints must be provided at working site for electrical
connections
LOCATION: Ch. 198+160 FLO Date 11.01.2023 Status PENDING

Observation: Observed nonstandard electrical connections and improper cable joint

Corrective action standard electrical DB to be provided and proper routing of cables to be


ensured
LOCATION: P&M Workshop Date 14.01.2023 Status PENDING

Observation: Non-standard earth clamp used for welding activity

Corrective action Standard earth clamp to be used

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. 226+700 Date 20.01.2023 Status PENDING

Observation: Reverse horn found not working on Motor grader (WIPL-MGR001)

Corrective action Reverse horn should be in working condition

WAGAD INFRAPROJECTS PVT LTD


Labour camp -
LOCATION: Ch. 189 Date 21.01.2023 Status PENDING

Observation: Observed improper routing of electrical cables

Corrective action Proper routing of electrical cable to be followed

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Date Status PENDING

Observation: Observed improper joining of electrical cables

Corrective action Ensure proper joining of electric cables

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch 206+400 Date 22.01..2023 Status PENDING

Observation: Reverse horn found not in working condition of roller (WIPL/VTR001)

Corrective action Reverse horn should be in working condition

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant- Date 25.01.2023 Status PENDING

Observation: Area around conveyor belt not barricaded

Corrective action Area around conveyor belt to be barricaded for restricting the movement

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant Date 25.01.2023 Status PENDING

Observation: Limit switches, interlocking arrangements found not provided for pugmill

Corrective action Interlocking arrangements to be provided

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant- Date 25.01.2023 Status PENDING

Observation: Pullcord switches not provided on conveyor belts

Corrective action Pullcord switches to be provided on conveyor belts

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant Date 25.01.2023 Status PENDING

Observation: Pullcord switches not provided on conveyor belts

Corrective action Pullcord switches to be provided on conveyor belts

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant Date 25.01.2023 Status PENDING

Observation: Pullcord switches not provided on conveyor belts

Corrective action Pullcord switches to be provided on conveyor belts

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant- Date 25.01.2023 Status PENDING

Observation: Handrailing not available on ladder

Corrective action Handrailing to be provided

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant- Date 25.01.2023 Status PENDING

Observation: Rotating parts found not guarded

Corrective action All rotating parts to be guarded

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant- Date 25.01.2023 Status PENDING

Observation: Nip point found without guarding

Corrective action All rotating parts to be guarded

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant- Date 25.01.2023 Status PENDING

Observation: Rotating parts found not guarded

Corrective action All rotating parts to be guarded

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant Date 25.01.2023 Status PENDING

Observation: Improper loading ramp found provided

Corrective action Proper loading ramp with barricading and delineation to be provided

WAGAD INFRAPROJECTS PVT LTD


LOCATION: WMM plant Date 25.01.2023 Status PENDING

Observation: Dust suppression arrangements not provided on loading hopper

Corrective action Dust suppression arrangements to be provided

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. 197+500 Date 03.02.2023 Status PENDING

Observation: Shifting of material found without tagline and 6 nos of workmen found
without PPEs

Corrective action Ensure availability of tagline/guide rope during material shifting and
availability of job specific PPEs
LOCATION: Ch. 197+500 Date 03.02.2023 Status PENDING

Observation: Welding machine found without.


1. VRD
2. Earthing

Corrective action Ensure availability of VRD and earthing on welding machine

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. 197+500 Date 03.02.2023 Status PENDING

Observation: DG found without,


1. Enclosure or covering
2. Rotating parts not guarded
3. Earthing not provided
4. Insulation not available on battery terminal
5. Observed oil leakage

Corrective action Ensure use of standard DG

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Ch. 197+500 Date 03.02.2023 Status PENDING

Observation: TPI details not available for Chain pully block

Corrective action Ensure availability of valid TPI certification for all lifting tools and tackles

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp Date 01.01.2023 Status PENDING

Observation: Non-standard electrical distribution board used

Corrective action Standard electrical boards to be used

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp Date 01.01.2023 Status PENDING

Observation: Reverse horn not working in dumper Reg no: RJ 03 GA3820.

Corrective action Reverse horn should be in working condition

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp Date 01.01.2023 Status PENDING

Observation: Improper routing of cable is observed

Corrective action Proper routing of electrical cable to be ensured

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp Date 01.01.2023 Status PENDING

Observation: Improper storing of gas cylinder( Gas cylinder found kept with oil)
observed.

Corrective action Gas cylinder shall be properly stored

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp Date 01.01.2023 Status PENDING

Observation: Poor housekeeping observed.

Corrective action Proper storing of materials to be adopted

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp Date 01.01.2023 Status PENDING

Observation: Non-standard electrical distribution board used

Corrective action Standard electrical boards to be used

WAGAD INFRAPROJECTS PVT LTD


LOCATION: Vadakara Camp Date 01.01.2023 Status PENDING

Observation: TPI certificate of air compressor not available

Corrective action Ensure availability of TPI certification on compressors