Air System Design Load Summary for CORRIDOR 4

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:55AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.8 C / 30.0 C HEATING OA DB / WB 12.0 C / 10.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 47 m 13052 - 47 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 580 m 7484 - 580 m 4699 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 47 m 4733 - 47 m 1615 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 422 m 10572 - 422 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 23475 W 16432 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 104 9025 13908 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 8% / 5% 5029 695 0% 0 0
>> Total Zone Loads - 67891 14603 - 6315 0
Zone Conditioning - 66148 14603 - 410 0
Plenum Wall Load 20% 0 - 0 0 -
Plenum Roof Load 70% 17463 - 0 0 -
Plenum Lighting Load 30% 7042 - 0 0 -
Return Fan Load 6958 L/s 0 - 6958 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 6958 L/s 644 - 6958 L/s -644 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 679 - 1% 63 -
>> Total System Loads - 91977 14603 - -171 0
Central Cooling Coil - 91977 14605 - 0 0
>> Total Conditioning - 91977 14605 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.50 Page 1 of 1