DRIVE IN PLACE OF ALTIVAR 11 (MOSCA TRANSPORT BELT DRIVE)
DISCONNECT THE 230 VOLTS INCOMING SUPPLY AND OUTGOING MOTOR
CONNECTIONS OF ALTIVAR11 NOTE THE CONTROL CONNECTIONS OF THE ALTIVAR11 READING FROM LEFT CONNECTORS 1. DRIVE STATUS FEED BACK TO PLC. 2. 24V +VE CONTROL POWER. 3. DUMMY 4. 24V -VE CONTROL POWER. 5. STRAP TIGHTENING MOTOR FEED BACK . 6. DUMMY 7. DUMMY 8. DRIVE ENABLE FROM PLC. 9. DUMMY 10. DUMMY 11. DUMMY 12. DUMMY NOW CONNECT THE 2.2KW MICROMASTER DRIVE WITH EXTERNAL 3PHASE SUPPLY THE FOLLOWING CHANGES TO BE DONE IN CONTROL SIDE OF MOSCA 1. CONNECTOR NO 1 AND 2 REMOVED WIRES SHOULD BE MADE SHORT FOR AVOIDING DRIVE ERROR INDICATION. OR CAN BE GIVEN TO “NO”OF MMV FAULT RELAY CONTACTS. 2. A SEPARATE 24V RELAY TO BE PROVIDED FOR STOP AND START ENABLING OF DRIVE . 3. 4 TH CONNECTOR REMOVED WIRE TO BE GIVEN IN RELAY A-ve 4. 8 TH CONNECTOR TO BE GIVEN TO THE A+ OF THE RELAY 5. 5TH WIRE NOT USED TO BE SECURED WITH TAPE. 6. ONE “NO” OF RELAY IS CONNECTED IN STOP LOOP OF MMV DRIVE. THE FOLLWING PARAMETERS TO BE CHANGED IN MMV DRIVE 1. P080---------POWER FACTOR 2. P081---------FREQUENCY 3. P082---------RPM 4. P083---------CURRENT 5. P084---------VOLTS 6. P085---------POWER 7. P002---------RAMP UP TIME------3.4 8. P070---------BRAKING RESISTOR DUTY CYCLE-------4 9. P075----------BRAKING CHOPPER ENABLE-------0(AN EXTERNAL BRAKING RESISTOR IS NOT CONNECTED. AFTER CHANGING THE PARAMETERS SWITCH OFF THE POWER AND ON AGAIN. NOW MOTOR CAN BE RUN USING MMV DRIVE. CHANGE THE FREQUENCY USING POT IF NECESSARY.(WE KEPT AT 50HZ)