P.013554-IOCL CGD in BOKARO: Contractors Document Review Sheet
P.013554-IOCL CGD in BOKARO: Contractors Document Review Sheet
No. Reference, Para, etc. PMC Comments dated 22.09.2020 Contractor Response
Vendor to note that review of Contractor's document by IOCL/ PMC shall not
relieve the Contractor of his responsibility for correct Design, Engineering and
Construction. The sole responsibility of the correctness of Design,
Engineering & Construction shall lie with the Contractor irrespective of the fact
G2 General Agreed
that the Drawings/Documents submitted are reviewed or not reviewed by
IOCL/ PMC. The contractor shall correct all faulty design & construction
detected at any stage of work without any cost & time implication to Company/
Company Representative.
E1 Electrical Project title and code to be mentioned.(It is for CGS or CNG composite tender) Complied
This document shall be submitted along with below, for our review and
approval.
1. data sheet for UPS, Battery,
E2 Electrical 2. Sizing calculation of Battery, Charger Complied
3. Panel GA drawings
4. UPS DB drawing.
5. UPS system SLD and wiring diagram.
1 of 2
No. Reference, Para, etc. PMC Comments dated 22.09.2020 Contractor Response
A Approved
B Approved subject to incorporation of comments
C Not approved
D For Information