Professional Documents
Culture Documents
Test Device: Excitation Curve
Test Device: Excitation Curve
Overall assessement OK
Asset
Ipn 800.0 A Object Location
Isn 1.0 A Manufacturer RITZ Company SEC
Rated burden 30.0 VA /0.80 Type ASG36-70 Country KSA
Operating burden 30.0 VA /0.80 Serial number 19/80325435 Station MOBILE SS
Standard IEC 61869-2 Core 2 Feeder M04
Application Protection Tap 2 Phase B
Class 5P Optional IEC-ID
Frequency 60.0 Hz Comment
Rct max 5.235 Ω ?
ALF 20.0
Ts
Burden
Burden cos φ: Z
V-meas I-meas
Excitation
Ls 0.006946 H Lm 120.1421 H Results at rated burden (30.00 VA) Results at operating burden (30.00 VA)
Kr 82.07 % ALF > 25.06 ALFi 24.13 ALF > 25.06 ALFi 24.13
Standard IEC 61869-2 εci (@ ALF=20) 0.106 % εci (@ ALF=20) 0.106 %
V-kn 649.48 V I-kn 0.0188 A Ts 4.109 s Ts 4.109 s
Ratio
Turns ratio 799.9677 Results at rated burden (30.00 VA) Results at operating burden (30.00 VA)
εt -0.0040 % Ratio 800.0 : 0.9989 Ratio 800.0 : 0.9989
Polarity OK ε -0.1135 % ∆φ 0.50 min ε -0.1135 % ∆φ 0.50 min
εc 0.1144 % εc 0.1144 %
Residual magnetism
Residual flux
Residual magnetism
Excitation curve
900.00
800.00
700.00
600.00
Voltage [V]
500.00 X1-X2
400.00
300.00
200.00
100.00
0.00
0.00 0.500 1.00 1.50 2.00 2.50 3.00
Ie [A]
1/2
Current ratio error in % at % of rated current at rated burden (30.00 VA)
VA/cos φ 1.00 % 5.00 % 10.00 % 20.00 % 50.00 % 100.00 % 120.00 % 200.00 %
30/0.8 -0.5362 -0.2639 -0.2073 -0.1665 -0.1310 -0.1135 -0.1096 -0.1001
15/0.8 -0.3847 -0.1752 -0.1358 -0.1072 -0.0814 -0.0684 -0.0657 -0.0594
7.5/0.8 -0.2770 -0.1226 -0.0914 -0.0719 -0.0533 -0.0437 -0.0417 -0.0371
3.75/1 -0.0837 -0.0573 -0.0451 -0.0370 -0.0292 -0.0244 -0.0233 -0.0207
20.0000
7.50 VA
0.0000
-20.0000 3.75 VA
-40.0000
Limits
-60.0000
-80.0000
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]
2/2