Gas Insulated MV Circuit Breakers Up To: 40.5 KV 4000 A 50 Ka
Gas Insulated MV Circuit Breakers Up To: 40.5 KV 4000 A 50 Ka
D I S T R I B U T I O N S O LU T I O N S
HD4
Gas insulated MV circuit breakers
up to: 40.5 kV; 4000 A; 50 kA
—
The HD4 medium voltage circuit
breakers use SF6 gas technology
to protect your asset, ideal for
all the application where a
smooth switching is a plus.
The HD4 are the best answer for
the most fields of application
like power distribution,
protection of cables, overhead
lines, transformers and
substations.
—
Table of contents
—
HD4:
its strengths, your benefits
—
Productivity
Maximizing your output
Easy to installing
• Withdrawable version available
– Circuit breaker can be easily racked out and in for
maintenance
– You’ll receive the complete circuit breaker ready to
be installed in your panel
—
Efficiency
Optimizing your investments
Affordable range
• Technical cooperation agreement
– Count on technical backup from ABB for
developing new panels based on certified ABB
design
Continuity of service
• Low maintenance
– High reliability and fewer downtimes since
modular actuator ESH only contains a limited
number of mechanical components
—
Reliability
Protecting your assets
Optimum interface
• Standardized product family up to 40.5 kV and 4000 A
– Common, simple accessories and interface are
available for the entire product family
Global availability
• You can count on ABB
– Our global presence means you can rely on us for any
type of support you may require
8 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Description
—
General information
HD4 medium voltage circuit
breakers use sulphur hexafluoride
gas (SF6) to extinguish the
electric arc and as the insulating
medium.
Breaking in SF6 gas takes place
without any arc chopping and
without generation of
overvoltages. These
characteristics ensure long
electrical life of the circuit breaker
and limited dynamic, dielectric
D I S T R I B U T I O N S O LU T I O N S 9
—
Available versions
HD4 circuit breakers are available in the fixed and
withdrawable version with front operating
mechanism.
The withdrawable version is available for
PowerCube modules and UniGear type ZS1, ZS2,
ZS3.2 switchgears..
—
Fields of application
HD4 circuit breakers are used in power distribution
to control and protect lines, transformer and
distribution substations, motors, transformers,
capacitor banks, etc.
Thanks to the SF6 autopuffer breaking technique,
the HD4 circuit breakers do not generate
operating overvoltages, and are therefore also
highly suitable for retrofitting, upgrading and
enlarging older installations where the motor,
cable, etc. insulating materials may be particularly
sensitive to dielectric stresses.
10 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Description
— —
Breaking technique Standards and approvals
The breaking technique of HD4 circuit breakers is HD4 circuit breakers comply with IEC 62271-100
based on compression and self-blast techniques to Standards. Additionally, HD4 breakers are
obtain top performances at all service current registered in the main naval registers and are
values, with minimum arc times, gradual arc therefore suitable for Marine applications.
extinction without chopping, and no restriking or They have undergone the following tests and
operating overvoltages. guarantee safety and reliability of the apparatus in
The HD4 series brings to medium voltage the service in all installations.
advantages of the “autopuffer” breaking technique • Type tests: heating, withstand insulation at
already used in high voltage. industrial and impulse frequency, short-time and
peak withstand current, mechanical duration,
making and breaking of short-circuit currents;
7
3
6
4
1
5
Circuit breaker Main contact Arcing contact Circuit breaker
closed separation separation open
• Individual tests: insulation with voltage at Key locks or padlocks enable opening and closing
industrial frequency in the main circuits and and/or racking-in and racking-out operations.
insulation of the auxiliary and control circuits, The closed door racking-out device only allows the
measurement of the main circuit resistance, circuit breaker to be racked in and out of the
mechanical and electrical operation. switchgear when the door is closed.
The HD4 circuit breakers are tested according to Anti-racking-in locks prevent circuit breakers with
the requirements of the IEC 62271-100 Standard different rated currents from being racked-in and
(classes E2, M2, C2). Versions approved according racked-out when the circuit breaker is closed.
to the GOST Standard are also available (please
contact us).
—
— ESH operating mechanism
Safety • Just one device for the whole series.
Safe distribution switchgear can be constructed • The same set of accessories for all the types of
with HD4 circuit breakers thanks to the full range HD4 circuit breaker.
of mechanical and electrical locks (available on • Fixed strikers to facilitate assembly or
request). replacement of accessories.
The locks have been designed to prevent incorrect • Accessory cabling with socket and plug.
operations and to allow the installations to be This is a stored energy mechanical actuator with
inspected while guaranteeing maximum operator manual and/or motor-operated loading of the
safety. closing spring; the opening spring is loaded by the
same actuator during the closing operation. The
opening and closing operations take place at
speeds that are independent from the operator
and the operating mode (manually using local or
remote push-buttons or by means of the opening
and closing shunt releases). When it is not
equipped with a geared motor for loading the
closing springs, the operating mechanism can
enable the following sequences:
• with c.-breaker open and closing spring loaded:
C-O
• with c.-breaker closed and closing spring
loaded: O - C - O.
When equipped with a geared motor for loading
the closing springs, the operating mechanism can
perform repeated re-closing operations thanks to
automatic reloading after each closing operation.
• Highly reliable operating mechanisms thanks to
a low number of components which are
manufactured using production systems for
large quantities
• Accessories common to the entire range
• Electrical accessories that can be easily and
quickly installed or replaced thanks to wiring pre-
engineered with plug-socket connectors
• Mechanical anti-pumping device is supplied as
standard
• Key lock with circuit breaker open
• Protective covering over the opening and closing
pushbuttons to be operated using a special tool
• Padlock device on the operating pushbuttons
12 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Description
—
Circuit breaker operating mechanism
A
K
B L
C M
D N
E
O
F
P
H Q
R
I
A Gas monitoring device with led J Lock that prevents racking-in when door is open
B Opening pushbutton K Mechanical operation counter
C Mechanical undervoltage override L Pressure switch
D Undervoltage release M Mechanical signalling device for circuit breaker open/closed
E Service releases (opening and closing) N Key lock removed when circuit breaker is open
F Operating mechanism locking electromagnet O Contacts for signalling spring charged/discharged
G Closing pushbutton P Signalling device for closing springs charged/discharged
H Open/closed auxiliary contacts Q Closing spring loading motor limit switch
I Protection circuit breaker for closing spring loading motor R Geared motor for closing spring charging
D I S T R I B U T I O N S O LU T I O N S 13
—
Additional Service
—
ABB Power Care
ABB Power Care allows you to better manage the services that the customers can select, according
electrification system, ensuring operational to their needs, when the service contract is
continuity and optimizing the financial resources activated. The services offered range from the
available. Depending on the profile of each possibility of dedicated access to a full range of
company, ABB can offer a wide range of assistance support services for each type of equipment. All
services, allowing customers to choose those best services are provided by qualified and certified
suited to the needs of the installation. The ABB ABB personnel.
Power Care platform is based on an array of
The array of ABB Power Care package consists of five areas and four levels of service, in which each
area is geared to different customer needs and the degree of ABB support offered increases in step
with the levels.
ABB Power Care Base level Level 1 Level 2 Level 3
Includes training and retraining of personnel. The Services for skills List of training Training courses Training courses Ongoing training
purpose of the courses on products and development courses on on products on applications
applications is to provide all participants with the products
necessary knowledge and skills on ABB
equipment, while the ongoing training services
help maintenance managers to develop a strategy
for the ongoing training of staff tailored to their
duties.
Provides rapid assistance in emergency Emergency Dedicated Technical support Emergency Assessment and
situations. Dedicated access provides a direct line maintenance access within defined response within management of
in the case of request for “call based” service, services times defined times spare parts
while technical support and emergency services
ensure that the customer receives adequate
support within defined times. The contract may
also include the management of strategic spare
parts in the installation.
Allows the condition of the equipment to be Services for diagnosis Initial evaluation Assessment of the Equipment Remote
ascertained and safety aspects to be monitored, and assessment of and conditions and monitoring monitoring of
as well as the definition of the measures conditions documentation risk probability of equipment
necessary to contain risks. In this area, the ABB of the installed the equipment (*)
package includes periodic inspections or the base
installation of a monitoring system for the
evaluation of the conditions of the equipment.
Includes support services for the personnel of the Support for personnel Report on the Online manuals Online support File storage
installation so that they are able to carry out of the installation state of the life and instructions for personnel of
extraordinary operations without any problems cycle of the the installation
by being able to browse the online product installed base
documentation, to chat with ABB experts or to
have dedicated online access to the ABB platform
that hosts the files/documentation for the
equipment of the installation.
ABB offers technical advice and preventive Maintenance MV Annual Maintenance of Maintenance of Maintenance of
maintenance operations to keep the equipment services measurement of protection and circuit breakers switchgear
in good condition, while minimizing the risk of in the partial control units
outage and serious failures of the electrical installation discharges
equipment. LV Periodic Services for Advanced Advanced
technical products services for services for
evaluation products switchgear (*)
—
Additional Service
—
Quality System
Complies with UNI EN ISO 9001 Standards,
certified by an independent organisation.
—
Test Laboratory
Complies with UNI CEI EN ISO/IEC 17025
Standards, accredited by an independent
organisation.
—
Environmental Management
System
Complies with UNI EN ISO 14001 Standards,
certified by an independent organisation.
—
Health and Safety Management
System
Complies with OHSAS 18001 Standards, certified
by an independent organisation.
16 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Selection and ordering
—
General characteristics
of fixed circuit breakers (12 kV)
—
General characteristics
of fixed circuit breakers (17.5 kV)
—
Selection and ordering
—
General characteristics
of fixed circuit breakers (24 kV)
—
General characteristics
of fixed circuit breakers (36 kV)
Rated short-time 20 20 20 – – 20 20
Ik [kA]
withstand current (3 s) – – – 25 25 25 25
– – – 31.5 31.5 31.5 31.5
40 40 40 – – – –
50 50 50 – – 50 50
Making capacity Ip [kA]
– – – 63 63 63 63
– – – 80 80 80 80
[O-0.3s-CO-15s-CO]
Operation sequence
[O-0.3s-CO-3min-CO] • • • • • • •
Opening time [ms] 45 45
Arcing time [ms] 10-15 10-15
Total breaking time [ms] 55-60 55-60
Closing time [ms] 80 80
H [mm] 730/1060 (6) 790/1123 (6) 790/1123 (6)
Maximum overall
dimensions without W [mm] 880/955 (6)
748/805 (6)
748/805 (6)
insulating screens H
D [mm] 695 833 833
between phases (4) D
W Pole centre distance I [mm] 350 275 275
Weight [kg] 124 128 128 175 175 180 190
Standardised table of dimensions TN 7241 TN 7268 TN 7315
Absolute SF6 gas pressure (2) [kPa] 380 450 450
Operating temperature [°C] - 5 ... + 40 - 5 ... + 40
Tropicalizzazione IEC: 60068-2-30, 60721-2-1 • •
Electromagnetic compatibility IEC 62271-1 • •
(1) Rated normal current defined in free air Fixed HD4 36 kV circuit breaker Fixed HD4 36 kV circuit breaker
(2) Rated service value with 350 mm pole centre distance: with 275 mm pole centre distance:
(3) For these versions, with 275 mm pole centre distance, special insulating Ir = 630-1250-1600 A; Ir = 1250-1600 A;
partitions are provided (on request) Isc = 16-20 kA. Isc = 25-31.5 kA;
(4) For the dimensions of the insulating partitions (available on request), see Ir = 2000-2500 A;
the standardised table in chapter 5 Isc = 20-25-31.5 kA.
(5) Operation sequence: O - 0.3 min - CO - 3 min - CO
(6) The second distance refers to the circuit breaker with truck (available on
request)
20 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Selection and ordering
—
General characteristics of withdrawable circuit breakers
for UniGear type ZS1 switchgear (12 kV) (4)
(1) Rated normal current with circuit breaker in UniGear type ZS1 switchgear and 40 °C ambient temperature outside the switchgear
(2) Rated service value
(3) The circuit breaker can reach rated currents higher than 3150 A with appropriate forced ventilation of the switchgear (for further information, consult the technical catalogue of the
UniGear type ZS1 switchgear).
(4) In the standard fitting, the truck locking electromagnetic (-RL2) is included to prevent circuit breaker racking-in with auxiliary circuits not connected (plug not inserted in the
socket).
(5) Rated current in switchgear with forced ventilation; with natural ventilation the rated current is 2300 A.
D I S T R I B U T I O N S O LU T I O N S 21
—
General characteristics of withdrawable circuit breakers
for UniGear type ZS1 switchgear (17.5 kV) (4)
(1) Rated normal current with circuit breaker in UniGear type ZS1 switchgear and 40 °C ambient temperature outside the switchgear
(2) Rated service value
(3) The circuit breaker can reach rated currents higher than 3150 A with appropriate forced ventilation of the switchgear (for further information, consult the technical catalogue of the
UniGear type ZS1 switchgear).
(4) In the standard fitting, the truck locking electromagnetic (-RL2) is included to prevent circuit breaker racking-in with auxiliary circuits not connected (plug not inserted in the
socket).
(5) Rated current in switchgear with forced ventilation; with natural ventilation the rated current is 2300 A.
22 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Selection and ordering
—
General characteristics of withdrawable circuit breakers
for UniGear type ZS1 switchgear (24 kV) (4)
Rated short-time 20 20 – 20 20 20
Ik [kA]
withstand current (3s) 25 25 – 25 25 25
– – 31.5 31.5 31.5 31.5
40 – – 40 40 –
50 50 – 50 50 50
Making capacity Ip [kA]
63 63 – 63 63 63
– – 80 80 80 80
Operation sequence [O-0.3s-CO-15s-CO] •
Opening time [ms] 35-60
Arcing time [ms] 10-15
Total breaking time [ms] 45-75
Closing time [ms] ≤85
H [mm] 736 792 821 821
(1) Rated normal current with circuit breaker in UniGear type ZS1 switchgear and 40 °C ambient temperature outside the switchgear
(2) Rated service value
(3) The circuit breaker can reach rated currents higher than 3150 A with appropriate forced ventilation of the switchgear (for further information, consult the technical catalogue of the
UniGear type ZS1 switchgear).
(4) In the standard fitting, the truck locking electromagnetic (-RL2) is included to prevent circuit breaker racking-in with auxiliary circuits not connected (plug not inserted in the
socket).
(5) Rated current in switchgear with forced ventilation; with natural ventilation the rated current is 2300 A.
D I S T R I B U T I O N S O LU T I O N S 23
—
General characteristics of withdrawable circuit breakers
for UniGear type ZS3.2 switchgear (40.5 kV)
Rated short-time 25 25 25 25
Ik [kA]
withstand current (3s) 31.5 31.5 31.5 31.5
63 63 63 63
Making capacity Ip [kA]
80 80 80 80
Operation sequence [O-0.3s-CO-15s-CO] •
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 1575
—
Selection and ordering
—
General characteristics of withdrawable circuit breakers
for PowerCube units (12 kV)
—
General characteristics of withdrawable circuit breakers
for PowerCube units (17.5 kV)
—
Selection and ordering
—
General characteristics of withdrawable circuit breakers
for PowerCube units (24 kV)
—
General characteristics of withdrawable circuit breakers
for PowerCube units (36 kV) and UniGear type ZS2
switchgear (36 kV)
(1) Rated normal current with circuit breaker in UniGear ZS2 switch-gear and 40 °C ambient temperature outside the switchgear
(2) Rated service value
(3) Switchgear with forced ventilation
28 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Selection and ordering
—
General characteristics of withdrawable circuit breakers
for UniSec (12 -17.5 - 24 kV) type units WBC
—
Standard equipment
The basic versions of the circuit breakers are
always three-pole and fitted with:
• manual operating mechanism
• mechanical signalling device for closing springs
charged/discharged
• mechanical signalling device for circuit breaker
open/closed
• closing pushbutton
• opening pushbutton
• operation counter
Terminals for fixed circuit breaker.
• 12 to 36 kV series: set of 14 auxiliary contacts for
circuit breaker open/closed; five closing contacts
(circuit breaker open signalling) and seven
opening contacts (circuit breaker closed
signalling) are available for use by the customer
if the apparatus is equipped with all the
electrical applications
• 40.5 kV series: set of 10 auxiliary contacts for
circuit breaker open/closed; three closing
contacts (circuit breaker open signalling) and
four opening contacts (circuit breaker closed
signalling) are available for use by the customer
if the apparatus is equipped with all the Circuit breaker racking-out/racking-in lever.
electrical applications
• lever for manually charging the closing springs
(the quantity must be defined according to the
number of pieces of apparatus ordered).
Moreover:
• for fixed circuit breaker
-- connection terminals (not available for low-end
circuit breakers)
-- terminal board for auxiliary circuits;
• for withdrawable circuit breaker
-- isolating contacts
-- cord with connector (plug only) for auxiliary
circuits
-- lock to prevent racking-in of circuit breaker
with different rated current
-- racking-in/out lever (the quantity must be Tulip isolating contacts for withdrawable circuit breaker.
—
Selection and ordering
—
Table of availability of accessories
closed.
1A 1B 1C 2 3A 3B 4 5 6A 6B 7 8 9 10
Fixed circuit breakers
HD4 12 • • • • • • • • • – • – – •
HD4 17 • • • • • • • • • – • – – •
HD4 24 • • • • • • • • • – • – – •
HD4 36 • • • • • • • • • – • – – •
Withdrawable circuit
breakers for UniGear
type ZS1 switchgear
HD4/P 12 • • • • • • • • • – • • • •
HD4/P 17 • • • • • • • • • – • • • •
HD4/P 24 • • • • • • • • • – • • • •
Withdrawable circuit
breakers for UniGear
36 type ZS3.2 switchgear
HD4/Z 40,5 • • • • • • • • • • – (1) •
Withdrawable circuit
breakers for PowerCube
modules
HD4/W 12 - HD/P 12 • • • • • • • • • – • • • •
HD4/W 17 - HD/P 17 • • • • • • • • • – • • • •
HD4/P • • • • • • • • • – • • • •
HD4/W 36 (5) • • • • • • • • • – • • • •
Withdrawable circuit
breakers for UniSec
switchgear
HD4/SEC 24 • • • • • • • • • – • • • •
Two-level pressure switch plus SF6 control device with three LEDs (2).
Mechanical isolation interlock with the switchgear door.
-RLE1 operating mechanism locking magnet.
Electric signalling of springs discharged.
Electric signalling of springs charged.
Insulating partitions.
11 12A 12B 13A 13B 14 15 16 17 18 19A 19B-C 20 21
Fixed circuit breakers
HD4 12 • • • • • • • – • – • • –
HD4 17 • • • • • • • – • – • • –
HD4 24 • • • • • • • – • – • • •
HD4 36 • • • • • • • – • – • • •
Withdrawable circuit
breakers for UniGear
type ZS1 switchgear
HD4/P 12 • • • • • • • (4) • • • • –
HD4/P 17 • • • • • • • (4) • • • • –
HD4/P 24 • • • • • • • (4) • • • • –
Withdrawable circuit
breakers for UniGear
36 type ZS3.2 switchgear
HD4/Z 40,5 • • • - - • • • – • (3) • – •
Withdrawable circuit
breakers for PowerCube
modules
HD4/W 12 - HD/P 12 • • • • • • • – – • • • –
HD4/W 17 - HD/P 17 • • • • • • • – – • • • –
HD4/P • • • • • • • – – • • • –
HD4/W 36 (5) • • • • • • • • – – • • –
Withdrawable circuit
breakers for UniSec
switchgear
HD4/SEC 24 • • • • • • • • – – • • –
—
Selection and ordering
supplementary
shunt opening
release -MBO2
shunt opening
release -MBO1
D I S T R I B U T I O N S O LU T I O N S 33
shunt closing
release -MBC
34 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Selection and ordering
Under-voltage
release -MBU
—
Selection and ordering
6 Auxiliary and signalling contacts Auxiliary contacts –BGB1 and –BGB2 conform to
6A Auxiliary contacts –BGB1,-BGB2 for all 12 kV to the following standards/regulations/directives:
36 kV fixed and withdrawable series • IEC 62271-100
Electrical signalling of circuit breaker open/closed • IEEE C37.54
can be obtained with a set of 14 auxiliary contacts • EN 61373 cat.1 class B / impact and vibration test
for the fixed version and 14 auxiliary contacts for • Germanish Loyd regulation / vibrations
the plug-in version. envisaged by the shipping registers
Note • UL 508
The following contacts are available for the fixed • EN 60947 (DC-21A DC-22A DC-23A AC-21A)
and plug-in circuit breaker with the standard set of • RoHS Directive
fourteen auxiliary contacts and the maximum
number of electrical accessories: General characteristics
• five closing contacts for signalling circuit breaker Insulation voltage to standard 660 V AC
VDE 0110, Group C 800 V DC
open
Rated voltage 24 V ... 660 V
• seven opening contacts for signalling circuit
Test voltage 2 kV for 1 min
breaker closed.
Maximum rated current 10 A - 50/60 Hz
The auxiliary contacts of fixed circuit breakers are
Breaking capacity Class 1 (IEC 62271-1)
always wired to the terminal box.
Please refer to the following circuit diagrams: Number of contacts 5
6B Auxiliary contacts -BB1-BB2-BB3 for the 7 Transient contact -BGB4 with momentary
40.5 kV withdrawable series only closing during circuit breaker opening
Electrical signalling of circuit breaker open/closed This contact closes momentarily (for about 30 ms)
includes, as standard equipment, a set of 10 when the circuit breaker opens. The transient
auxiliary contacts for the 40.5 kV withdrawable contact is activated by the main operating shaft,
version. thus the indication is only provided when the main
Set of 10 circuit breaker open/closed auxiliary contacts of the circuit breaker effectively open.
contacts. Three closing contacts (circuit breaker
open signalling) and four opening contacts (circuit
breaker closed signalling) are available if the
apparatus is equipped with all the electrical
applications.
A set of 15 auxiliary contacts for signalling circuit
breaker open/closed can be supplied on request.
Four closing contacts (circuit breaker open
signalling) and four opening contacts (circuit
breaker closed signalling) are available if the
apparatus is equipped with all the electrical
applications.
Un Rated voltage
Cosϕ Power factor
Icu Breaking capacity
Ps Inrush power input (inrush duration is given between brackets)
Pc Continuous service power consumption
T Time constant
38 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Selection and ordering
8 Position contact of withdrawable circuit 9 Electrical signalling contacts for circuit break-
breaker -BGT3 er connected and isolated (-BGT1; -BGT2)
Only supplied for withdrawable circuit breakers for These contacts are an alternative to the
UniGear ZS1 and ZS2 switchgear and PowerCube withdrawable circuit breaker position contact
modules from 12 to 36 kV. (-BGT3) and are recommended when there are no
This contact is installed in the truck. It is in the position contacts on the roof of the circuit breaker
closed state when the truck is fully racked-in or compartment (for signalling circuit breaker racked-
fully racked-out and is in the open state when the out or racked-in). Contacts -BGT1, -BGT2 are
truck is being racked-in/racked-out. supplied as standard equipment when locking
It is used in conjunction with the locking magnet in magnet -RLE1 is installed in the operating
the operating mechanism (-RLE1) to prevent mechanism and position contact –BGT3 has not
remote closing during movement in the been requested. Contacts -BGT1 and BGT2 have
compartment. the same general and electrical characteristics as
It is supplied as standard equipment when locking auxiliary contacts “7b. -BB1, -BB2, -BB3”.
magnet -RLE1 is installed in the operating
mechanism and truck-mounted contacts are not
required (-BGT1, -BGT2). It cannot be supplied
when truck-mounted contacts are required (-BGT1;
-BGT2).
D I S T R I B U T I O N S O LU T I O N S 39
General characteristics
10 Spring-loading geared motor -MAS
Insulation voltage to standard 660 V a.c. The geared motor automatically loads the closing
VDE 0110, Group C 800 V d.c. spring of the circuit breaker’s operating
Rated voltage 24 V ... 660 V a.c. mechanism after the circuit breaker has closed
Test voltage 2 kV 50 Hz (for 1 min) each time and until the yellow “spring loaded”
Rated overcurrent 10 A indicator appears. If a power cut occurs when
Number of contacts 5 loading is in progress, the geared motor stops and
Contact run 6 mm ... 7 mm automatically starts loading the springs again
Activation force 26 N when the power returns. Loading can always be
Resistance 3 mΩ
completed in the manual mode (as it is during
Storage temperature –20 °C ... +120 °C
maintenance work) by means of the dedicated
lever supplied. Check the power available in the
Operating temperature –20 °C ... +70 °C
supply circuit to find out whether several motors
Contact overtemperature 20 K
for loading the closing springs can operate at the
Number of cycles 10.000
same time. To prevent excessive power
Unlimited breaking capacity if used with 10 A fuse in series
consumption, especially when the installation is
put into service, it is advisable to load the springs
Electrical characteristics by hand before energizing the auxiliary circuits.
Rated Breaking
Un
current capacity
220 V a.c. Cosj = 0.7 2.5 A 25 A
380 V a.c. Cosj = 0.7 1.5 A 15 A
500 V a.c. Cosj = 0.7 1.5 A 15 A
660 V a.c. Cosj = 0.7 1.2 A 12 A
1 ms 10 A 12 A
24 V d.c. 15 ms 10 A 12 A
50 ms 8A 10 A
200 ms 6A 7.7 A
1 ms 8A 10 A
60 V d.c. 15 ms 6A 8A
50 ms 5A 6A
200 ms 4A 5.4 A
1 ms 6A 8A
15 ms 4A 5A
110 V d.c.
50 ms 2A 4.6 A
200 ms 1A 2.2 A
1 ms 1.5 A 2A
15 ms 1A 1.4 A
220 V d.c.
50 ms 0.75 A 1.2 A
200 ms 0.5 A 1A
40 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Selection and ordering
11 Thermal magnetic protection -FCM1 of the 12 Signalling for closing spring loaded/dis-
closing spring loading motor charged
Thermal magnetic protection of the closing spring Contact for signalling closing spring loaded/
loading motor is supplied as part of the standard discharged -BGS2.
equipment for 24 V DC rated voltage while it is This consists of a microswitch, which allows
available on request for other voltage values. It is remote signalling of the state of the closing spring
always supplied with electrical signalling of of the circuit breaker operating mechanism.
thermal magnetic protection tripped. One of the following signals can be selected:
electrical
signalling of
spring loaded/
discharged
spring loaded/
discharged
mechanical
indicator
D I S T R I B U T I O N S O LU T I O N S 41
13 Locks and interlocks 14 “Circuit breaker open” key lock (different keys
or the same keys)
13 A Opening pushbutton lock (with or without The locking action is performed by a special
padlock). circular lock.
Locks the opening pushbutton with a 4 mm Can be supplied with different keys or the same
diameter padlock (not part of the standard keys (for several circuit breakers). To apply the key
equipment). The padlock is only supplied on lock, press the opening pushbutton, turn the key
request. and remove it. Local manual closing and remote
electrical closing are inhibited once the key has
13 B Closing pushbutton lock (with or without been removed.
padlock).
Locks the closing pushbutton with a 4 mm
diameter padlock (not part of the standard
equipment). The padlock is only supplied on
request.
42 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Selection and ordering
locking magnet
on operating
mechanism
D I S T R I B U T I O N S O LU T I O N S 43
17 Interlock for fixed circuit breaker (for fixed 18 Mechanical isolation interlock with the door
apparatus converted to plug-in by the of Unigear ZS1, ZS2 switchgear and the
customer) PowerCube enclosure
This device can be useful when fixed circuit This device prevents the circuit breaker from being
breakers are converted into withdrawable ones by racked-in when the switchgear door is open. It is
the customer. only intended for circuit breakers used in UniGear
It allows the customer to create a mechanical lock ZS1 and ZS2 switchgear and in PowerCube
that inhibits racking-out/racking-in when the modules (which must be equipped with a
circuit breaker is closed and prevents the circuit dedicated actuator on the door).
breaker from closing during movement.
Note. The device must be requested when the
order is placed since it must be assembled in the
factory.
—
Selection and ordering
—
Characteristics of electrical accessories
—
Specific product characteristics
—
Resistance to vibrations
HD4 circuit breakers are unaffected by
mechanically generated vibrations.
For the versions approved by the naval registers,
please contact us.
—
Tropicalization
HD4 circuit breakers are manufactured in
compliance with the strictest regulations for use in
hot-humid-saline climates.
All the most important metal components are
treated against corrosive factors according to
atmospheric corrosivity class C5 of standard BS
EN 12500.
Galvanisation is carried out in accordance with UNI
ISO 2081 Standards, classification code Fe/Zn 12,
with a thickness of 12x10-6 m, protected by a
conversion layer mainly consisting of chromates in
compliance with the UNI ISO 4520 Standards.
D I S T R I B U T I O N S O LU T I O N S 47
—
Altitude
The insulating property of air decreases as the
altitude increases, therefore this must always be
taken into account for external insulation of the
apparatus (the internal insulation does not
undergo any variations as it is guaranteed by the
SF6 gas).
The phenomenon must always be taken into
consideration during the design stage of the
insulating components of apparatus to be
installed over 1000 m above sea level In this case a
correction coefficient must be considered, which
can be taken from the graph to the side, built up
on the basis of the indications in the IEC 62271-1
Standards.
The following example is a clear interpretation of
the indications given above.
Graph for determining the Ka correction factor according to the altitude, Example (IEC):
—
Specific product characteristics
— —
Environmental protection Anti-pumping device
The ESH operating mechanism on HD4 circuit
programme breakers (in all versions) is fitted with a mechanical
HD4 circuit breakers are manufactured in
anti-pumping device which prevents re-closing due
accordance with the ISO 14000 Standards
to either electrical or mechanical commands.
(Guidelines for environmental management).
Should both the closing command and any one of
The production processes are carried out in
the opening commands be active at the same
compliance with the Standards for environmental
time, there would be a continuous succession of
protection in terms of reduction in energy
opening and closing operations.
consumption as well as in raw materials and
The anti-pumping device avoids this situation,
production of waste materials. All this is thanks to
ensuring that each closing operation is only
the medium voltage apparatus manufacturing
followed by a single opening operation and that
facility environmental management system.
there is no closing operation after this. To obtain a
Assessment of the environmental impact of the life
further closing operation, the closing command
cycle of the product, obtained by minimising
must be released and then relaunched.
energy consumption and overall raw materials of
Furthermore, the anti-pumping device only allows
the product, became a concrete matter during the
circuit breaker closure if the following conditions
design stage by means of targeted selection of the
are present at the same time:
materials, processes and packing.
• operating mechanism springs fully charged
This is to allow maximum recycling at the end of
• opening pushbutton and/or opening release
the useful life cycle of the apparatus.
(-MBO1/-MBO2) not enabled
• main circuit breaker contacts open.
D I S T R I B U T I O N S O LU T I O N S 49
— —
Spare parts Ordering
Replacement can only be carried out by trained For availability and ordering of spare parts, please
personnel and/or in our workshops: contact our Service, specifying the circuit breaker
• opening springs serial number.
• closing springs
• complete pole
• basic operating mechanism
• bushings, terminals and insulating protections.
—
Overall dimensions
Ur 12 kV
630 A
Ir
1250 A
27
16 kA
205
Isc 25 kA
31.5 kA
586
541,5
63
27
260,5
248,5
21,5
43
Isc
31.5 kA
623
27
63
266,5
231,5
21,5
43
472 13
117 2XM8 depth 16
598 10,5 M12 depth 25
111,5
618
270 34
332
D I S T R I B U T I O N S O LU T I O N S 51
310
50 kA
310
28
80
HD4 15.5 32
655
622
TN 7163 YU
12 kV
8
YU
Ur
17.5 kV
306.5
266.5
Ir 2000 A Q6
0 8
25 kA
Ø 13
31.5 kA
Isc
43
40 kA
472 Ø 10.5 35
50 kA 2.5
20
598 322
618 385
561
3150 A
670 min.
3600 A
15
Isc 25 kA
310
28
62
31.5 kA
40 kA 20 40
655
20
622
YU
50 kA
468.5
40
YU
20
20
HD4 8
TN 7165
266.5
4 x Ø18
Ø13
Ur 24 kV
43
Ir 2500 A
602 Ø10.5 115 2
3150 A
20
322 35
728
3600 A 385
748 603
Isc 25 kA
31.5 kA
Insulating partitions (only for 24 kV)
40 kA to be provided by the customer
(a special kit is available on request).
52 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Overall dimensions
27
Isc 16 kA
20 kA
670
310
25 kA
695
623
27
63
468
231
43
302,5
27
Ir 630 A
1250 A
Isc 16 kA
310
20 kA
27
695
25 kA
623
63
468
302,5
231
310
310
80
HD4
28
TN 7174 15.5 32
622
655
Ur 24 kV YU
8
Ir 2000 A YU
Isc 25 kA 8
306.5
266.5
31.5 kA Q6
0
40 kA Ø 13
43
20
728 322
35
385
748 561
1250 A
Ø 22
729.5
1600 A 28
712
639. 5
Isc 16 kA
539
10
20 kA
* 106 0
342.5
21
302.5
755
2x Ø 10.5 120
881 363.5 270
43
901 695.4 37
*4.9
* 348
*Ø 13
* 855 * Ø 13 * 200
* 355 *85
*4
* 915 *40
* 955 * 516.4
54 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Overall dimensions
HD4
with truck
(on request)
TN 7268
Ir 2000 A
20 kA
Isc 25 kA
31.5 kA
10
30 203 119 9
12 kV
Ur
17.5 A
630 A
98,5
Ir
1250 A
16 kA
205 ±1
35
586
Isc 25 kA
619 ±2
619
622,5
541
31.5 kA
260 ±1
154 ±1
19,5
340
4
21,5
4
503 25 320
531 370
501 416 53
492
456 ±2 437 0 + 2
150 150 558
661
608
55
56 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Overall dimensions
10
Ir 1250 A
Isc 40 kA
HD4/P
Ø 79
68
Ø 122
TN 7350 67.5
310 ±1
12 kV
Ur
691
17.5 kV
688
686
668.5
Ir 1600 A
63
543
25 kA
53.5
31.5 kA
280 ±1
Isc 40
40 kA (*)
245
164.5 ±1
89
21
50 kA (*)
Ø 19.5
20
(*) Also suitable for
550 4
21.5
29 359
4
PowerCube PB2.
4
626 ±2
416
653
36 551 ±1.5 53
682
68
Ø 122
67.5
50 kA (*)
310 ±1
(*) Also suitable for
PowerCube PB2.
691
688
686
669
63
543
53.5
280 ±1
40
245
164.5 ±1
89
21
Ø 19.5
20
4
550
21.5
359
4
29
4
626 ±2
416
653 36 551 ±1.5 53
682
D I S T R I B U T I O N S O LU T I O N S 57
10
Ir 2500 A
25 kA
31.5 kA
Isc
40 kA
Ø 109
Ø 152
67.5
50 kA
310 ±1
(*) Also suitable for
688
691
686
668.5
PowerCube PB3.
58
63
43.5
280 ±1
30
245
89
21
164.5 ±1
Ø 19.5
750 4
21.5
4
4
4
29 359
806 ±2
416
853
36 554 ±1.5 53
882
10
Ir 3150 A (*)
25 kA
31.5 kA
Isc
40 kA
50 kA
Ø 109
Ø 152
67.5
(*) 3150 A with forced
310 ±1
switchgear ventilation
(consult the UniGear type
730
732
730
43.5
30
280 ±1
245
89
164.5 ±1
21
Ø 19.5
4
21.5
750 29 359
4
806 ±2 416
853 36 554 ±1.5 53
882
58 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Overall dimensions
20
44
630 A
Ir
1250 A
16 kA(*)
Isc 20 kA
25 kA
310 ±1
(*) 630 A only.
35
772,5
766,5
768
717
645
63
325 ±1
254,5
125
198 ±2
461 ±1
4
610 ±2
697 53
653
746 ±1,5
681
Isc 31.5 kA
20
Ø 92.6
310 ±1
28
Ø 35
792
776
718
682
63
8
329 ±1
25.5
293
125
10
202 ±1
550 4
Ø 19.5
21.5
610 ±2 460
653 36 710 ±1.5 53
682
D I S T R I B U T I O N S O LU T I O N S 59
20
144 232 19
Ir 1600 A
16 kA
20 kA
Isc
25 kA
Ø 79
31.5 kA
Ø 122
67.5
310 ±1
(*) Also suitable for
PowerCube PB5. 58
817.5
814
807
733
63
700
43.5
345 ±1
30
310
125
11
198 ±1
806 ±2 4
4
4
457
853
882 36 699 ±1.5 53
20
Ur 24 kV 19
144 232
Ir 2000 A
16 kA
20 kA
Ø 79
Isc
25 kA
31.5 kA
Ø 122
67.5
310 ±1
58
HD4/P
814
817.5
807
TN 7356 (**)
733
Ur 24 kV
63
700
Ir 2500 A (*)
43.5
20 kA
345 ±1
Isc 25 kA 30
310
125
198 ±1
31.5 kA 11
750
21.5
4
4
457
4
882
60 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Overall dimensions
10
12 kV
Ur
35
17.5 kV
630 A
Ir
1250 A
16 kA
310 ±1
Isc 25 kA 28
688
31.5 kA
691
692
640
280 ±1
89
165 ±1
550 +2
19,5
21,5
359 0
4
626
653 416
681 539
587 ±1,50 53
210 ±1 210 ±1
586,5
55
D I S T R I B U T I O N S O LU T I O N S 61
10
Ur
17.5 kV
Ir 1250 A
40 kA
Isc
Ø 35
Ø 79
50 kA
67.5
310 ±1
28
688
688
691
636
63
16
280 ±1
245
89
165 ±1
4
Ø 19.5
626 ±2
21.5
4
4
29 359 40
653
416
682 36 551 ±1.5 53
640
Ir
2000 A
16 kA
Isc 25 kA
67.5
310 ±1
31.5 kA
28
698
691
668.5
635.5
63
8
Ø 122
Ø 79
280 ±1
245
89
165 ±1
4
Ø 20
550
4
21.5
4
29 359 40
626 ±2
653 36 551 ±1.5 53
682 640
62 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Overall dimensions
10
Ir 3150 A
31.5 kA
Isc 40 kA
Ø 109
50 kA
Ø 152
67.5
310 ±1
742
730
730
732
58
63
43.5
280 ±1
30
245
164.5 ±1
89
21
Ø 19.5
750 29 359
21.5
4
806 ±2 416
853
36 554 ±1.5 53
882
D I S T R I B U T I O N S O LU T I O N S 63
Withdrawable circuit breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
HD4/W
842 788
TN 7402 708
275 275 119 23
Ur 36 kV
67.5 144 232 19
20
Ir 1250 A
20 kA
Isc
25 kA
Ø 35
380
78
941.5
949
952
833
63
60
44
480
198
345
10
125
198
805 4
4
457
836
36 699 53
853
882
Withdrawable circuit breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
HD4/W
842
TN 7316 730
Ur 36 kV 706 18
23
275 275
Ir 1250 A
Ø 35
Isc 31.5 kA
380
953
956
973
484
125
202
805 4
456
836
30 701 57
853
882
64 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Overall dimensions
Withdrawable circuit breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
HD4/W
842 788
TN 7317 708
119 23
275 275
Ur 36 kV 19
20
67.5 144 232
1600 A
Ir 2000 A
2500 A (*)
Ø 122
Ø 79
20 kA
Isc 25 kA
380
31.5 kA 78
949
903.5
833
63
60
44
480
345
125
10
198
21.5
750
Ø 20
4
4
805 457
836 36 699 53
853
882
HD4/Z withdrawable circuit breakers for UniGear type ZS3.2 - 40.5 kV switchgears
HD4/Z/40,5 kV 840 245
280 280
TN 7227
Ur 40.5 kV
385
1250 A
2÷5
1600 A
Ir
2000 A
2500 A (*)
25 kA
328
Isc
31.5 kA
ØA
type
27
15
Ø 20
100
50
900
23 23
30 40
550
43 43
485
22
Ø 16
Ø 18
120
85
80
32.5 45 103
ØA 140 150
100
25 230 200
1250-1600 A 35 mm 718 503
2000-2500 A (*) 79 mm 760 582
D I S T R I B U T I O N S O LU T I O N S 65
25
630 A 229
Ir
1250 A
45°
1
16 KA
Isc 68
20 kA
79
310 ±1
739
35
A
644,5
734,5
435,5 ±2
63
36 8
325 ±1
254
653 25 320
19
4
681 370
382 4
650 414
210 ±1 210 ±1 687 ±1,5 53
19,5
36,3
25
55
DETAIL A
SCALE 1 : 2
66 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Electric circuit diagram
Electromagnetic effect Conductors in shielded Motor (general symbol) Closing position contact
cable (two conductors (limit switch)
shown)
Earth (general symbol) Resistor Change-over break before Lamp (general symbol)
(general symbol) make contact
D I S T R I B U T I O N S O LU T I O N S 67
68 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Electric circuit diagram
D I S T R I B U T I O N S O LU T I O N S 69
70 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Electric circuit diagram
Caption
= Number of diagram figure -BGK = Contact operated by the key lock preventing
electrical opening with earthing truck
* = See note indicated by the letter connected (compulsory accessory for earthing
-BCR = Overcurrent release with microprocessor type trucks with making capacity)
PR512 outside the circuit breaker (see note D) -BGS1 = Limit contacts of the spring charging motor
-BER = Device for continuous control of shunt opening -BGS2 = Contact for signalling closing springs loaded-
release coil continuity (see note E discharged
-BGB1, = Circuit breaker auxiliary contacts -BGT1 = Contacts electrically signalling circuit breaker in
-BGB2 the connected position (see note G)
-BGB4 = Auxiliary passage contact (with momentary -BGT2 = Contacts electrically signalling circuit breaker in
closing during circuit breaker opening) the isolated position (see note G)
-BGB5 = Contacts for electrical signalling of -BGT3 = Circuit breaker position contact, open during
undervoltage release energised/de-energised the isolating travel
D I S T R I B U T I O N S O LU T I O N S 71
-BGT5 = Position contacts signalling circuit breaker in -TB1, = Rectifiers for -MBO1 and -MBO2 releases
the racked-out position (these are contacts -TB2
signalling circuit breaker isolated located in the -RF = Filter (only provided with 220V d.c. voltage
enclosure, in the fixed part: see contacts -BGT2 supply)
in diagram 1VCP400036 figures 5-6)
-RLE1 = Locking magnet. If de-energized it mechanically
-BPS = Pressure-switch with two intervention thresholds: prevents circuit breaker closing
– intervention for low gas pressure.
-RLE2 = Locking magnet. If de-energized it mechanically
Contact 11-12-14 changes over, in relation to
prevents circuit breaker racking-in and isolation
the position indicated in the diagram, when the
(it is possible to limit its consumption by
gas pressure drops from level A to a value below
connecting a delayed pushbutton in series to
level B. If rated pressure is restored, this
enable the operation)
contact changes over again when, starting from
a value below level B, the value of level D is -XDB = Circuit breaker circuit connector
reached. -XDB1 = Switchgear terminal board (outside the circuit
– intervention for insufficient gas pressure. breaker)
Contact 21-22-24 changes over when the gas
-XDB2... = Accessory connectors
pressure at level A reaches a value below level C.
-XDB62
If rated pressure is restored, this same contact
changes over again when, starting from a value
below level C, the value of level B is reached. Rated absolute Pressure Pressure Pressure
-FCM1 = Thermomagnetic circuit breaker for protection service value level level level
of the spring-charging motor (see note F) [kPa] (A*) [kPa] (B) [kPa] (C) [kPa] (D)
-MAS = Motor for loading closing springs (see note C) 380 310 280 340
-MBC = Shunt closing release 430 360 330 390
-MBO1 = First shunt opening release (see note E) 480 410 380 440
-MBO2 = Second shunt opening release (see note E)
(*) According to circuit breaker rating plate
-MBO3 = Opening solenoid for microprocessor release
PR512 outside circuit breaker (see note D).
-MBU = Instantaneous undervoltage release or
undervoltage release with electronic time-delay
device (see note B)
-KFI = Integrated circuit for gas pressure control,
including:
-PFG = Green lamp indicating normal gas
pressure
-PFR = Red lamp indicating insufficient gas
pressure
-PFY = Yellow lamp indicating low gas pressure
-KFA1 = Auxiliary relay to double the -BP
pressure-switch contacts with
intervention for low gas pressure
-KFA2 = Auxiliary relay to double the contacts of
pressure switch -BPS with intervention
for insufficient gas pressure
-XDB5 = Connector
-KFT = Undervoltage release electronic time-delay
device (see note I)
-QAB = Main circuit breaker
-SFC = Pushbutton or contact for circuit breaker
closing
-SFO = Pushbutton or contact for circuit breaker
opening
-SFL1 = Contact for circuit breaker closing lock
72 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
Electric circuit diagram
Description of figures
Fig. 1 = Closing spring charging motor circuit (see Fig. 14 = Gas pressure control circuit. It includes:
note C). – intervention for insufficient gas pressure with
Fig. 2 = Shunt closing release (antipumping is carried lock on circuit breaker closing and opening by
out mechanically). means of the -KFA2 relay auxiliary contacts
(provide the locking magnet in fig. 3)
Fig. 3 = Locking magnet on operating mechanism. If
– 3 lamps for local indication of normal, low and
energized, mechanically prevents circuit
insufficient gas pressure
breaker from closing. Exclusion from
– contacts for remote indication of normal, low
permanent service of the magnet that
and insufficient gas pressure.
provides a locking action upon circuit-
For -BPS pressure switch intervention values see
breaker closing is only permitted with a delay
the caption.
of at least 0.5 s.
Fig. 20 = Contact operated by the key lock “in closed
Fig. 4 = Locking magnet. If de-energized it
position” to prevent electrical opening of the
mechanically prevents circuit breaker racking-
earthing truck with making capacity “racked-in”
in and isolation (it is possible to limit its
(compulsory accessory for earthing trucks with
consumption by connecting a time-delay
making capacity when the -MBO1 shunt opening
pushbutton in series for enabling the
release is provided).
operation) (see note H).
Fig. 21 = Thermomagnetic circuit breaker for protection
Fig. 5 = Instantaneous undervoltage release (see note
of the spring-charging motor (see note F).
B)
Fig. 22 = Contact for electrically signalling closing springs
Fig. 6 = Undervoltage release with electronic time-lag
charged.
device (see notes B and I).
Fig. 23 = Contact for electrically signalling closing springs
Fig. 7 = First shunt opening release circuit with
discharged.
possibility of continuous control of the winding
(see note E). Fig. 24 = Contact for electrically signalling under-voltage
release energized (see note B).
Fig. 9 = Second shunt opening release circuit with
possibility of continuous control of the Fig. 25 = Contact for electrically signalling under-voltage
winding (see note E). release de-energized (see note B).
Fig. 10 = Opening solenoid for microprocessor release Fig. 26 Contact for electrically signalling motor
PR512 outside circuit breaker (see note D) protection circuit breaker closed.
Fig. 11 = Gas pressure control circuit. It includes: Fig. 27 Contact for electrically signalling motor
– contacts for remote indication of normal, low protection circuit breaker open.
and insufficient gas pressure. Fig. 30 Auxiliary passing contact with momentary
For -BPS pressure switch intervention values closing during circuit breaker opening
see the caption. (intervention of -MBO1, -MBO2, -MBO3 and
Fig. 12 = Integrated gas pressure monitoring circuit. -MBU).
It includes: Fig. 32 Circuit breaker auxiliary contacts available.
– intervention for insufficient gas pressure with Fig. 51 Contact for electrically signalling circuit breaker
circuit breaker opening by means of the in the racked-in and isolated positions located
-MBO2 release and lock on closing and on the circuit breaker, supplied on request (see
opening by means of a -KFA2 relay auxiliary note G).
contact (provide the locking magnet in fig. 3)
– 3 lamps for local indication of normal, low and
insufficient gas pressure
– contacts for remote indication of normal, low
and insufficient gas pressure.
For pressure switch pressure values please refer
to circuit breaker electrical diagram.
D I S T R I B U T I O N S O LU T I O N S 73
Incompatibility
Non si possono fornire contemporaneamente sullo stesso D) Consult diagram 401530 for connections between
contattore i circuiti indicati con le seguenti figure: the auxiliary circuits of the circuit breaker and the
5 - 6 - 14 ∣ 9 - 10 - 12 - 14 ∣ 11 - 12 - 14 ∣ 22 - 23 ∣ 24 - 25∣ overcurrent release with microprocessor type PR512
26 - 27 ∣ 5 - 6 - 20 ∣ 9 - 10 - 12 - 20 installed in the switchgear.
E) The circuit for controlling continuity of the shunt
opening release winding must only be used for this
function.
At a power supply lower than 220 V, connect the
“Control Coil Continuity” device, or a relay or a
signalling lamp which consumes a current not
Notes exceeding 20 mA.
At a power supply equal to or higher than 220 V,
connect a delay or signalling lamp which consumes a
A) The circuit breaker is only fitted with the accessories
current not exceeding 10 mA.
listed in the order confirmation. To make out the
Other uses might jeopardise release functionality.
order, please consult the catalogue of the apparatus.
F) The -FCM1 circuit breaker in fig. 21 must always be
B) The undervoltage release can be provided for power
provided when there is a 24 kV d.c. spring charging
supply with voltage branched on the supply side of
motor.
the circuit breaker or from an independent source.
In case of opening caused by a fault in the motor,
Either the instantaneous undervoltage release or the
before carrying out manual resetting, recharge the
one with electronic delay device can be used (delay
springs by means of the special handle.
can be selected between 0.5 … 3 s; see note G).
Circuit breaker closing is only possible with the G) The contacts (-BGT1 and -BGT2) shown in fig. 51 for
release energised (the closing lock is made signalling the circuit breaker status are located on
mechanically). the circuit breaker (moving part) and are available on
The contact in fig. 24 or the one in fig. 25 is available request. However, application of these contacts on
on request. the enclosure is usually foreseen (fixed part): see
A delay of 50 ms between the moment of consent of diagram 1VCD400036.
the undervoltage release and energisation of the H) When fig. 4 is requested, the contact of pack -BGB1
shunt closing release must be inserted when there is to terminals 5-6 in fig. 32 is not available.
the same power supply for the shunt closing and When figs. 26-27 are requested, the -BGB2 contact to
undervoltage releases and automatic circuit breaker terminals 1-2 of fig. 32 is not available.
closing on return of the auxiliary power supply is When fig. 30 is required, the contact of pack -BGB2
required. This can be carried out by means of a to terminals 5-6 of fig. 32 is not available.
circuit outside the circuit breaker, including a I) Make one of the following bridges to select the delay
permanent closing contact, the contact indicated in required (see diagram 1VCD400062):
fig. 24 and a time-delay relay. 0.5 s: terminals 6-7
C) Check the power available on the auxiliary circuit to 1 s: terminals 6-8
verify the possibility of starting several motors for 1.5 s: terminals 6-9
charging the closing springs at the same time. To 2 s: terminals 6-10
avoid excessive consumption, it is necessary to 3 s: no bridge.
charge the springs manually before supplying the
auxiliary circuit with voltage.
74 H D 4 - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—