Nghi Son 2 BOT Thermal Power Plant Project

Design Query Sheet

DQ Sheet No DQ-NS2-DH01-P0ZEN- 740006-A-WSP1


Document Title Inspection and Test Plan for GRP Piping Installation Works
Document No NS2-DH01-P0ZEN- 740006 Rev A
Status Description Disapproved (revise and resubmit) Status Code 3
These comments and/or approval by the Owner / Owners Engineer’s in no way relieves the Contractor from his obligations to ensure conformance with the requirements of
the Contract. Any Contract deviations found subsequent to approval are to be corrected by the Contractor to the satisfaction of the Owner / Owners Engineer’s.
Sl No Cl. No & page no Item description Comment details

1 General Codes & Standards Owner /OE’s Comment dated 26-06-2019 Commented by: Owner/OE’s
Please specify approved construction drawing reference number.
Please provide details of section of Standards referring to.
Please submit installation manual for GRP piping for review.

1.1 Contractors response dated DD-MM-YYYY

2 Item 2.1 Fit-up inspection Owner /OE’s Comment dated 26-06-2019 Commented by: Owner/OE’s
Please specify what acceptance & rejection criteria is.

2.1 Contractors response dated DD-MM-YYYY

3 Item 3 Acceptance Owner /OE’s Comment dated 26-06-2019 Commented by: Owner/OE’s
criteria
Please specify what acceptance & rejection criteria is.

3.1 Contractors response dated DD-MM-YYYY

529829462.docx Page 1 of 2
Sl No Cl. No & page no Item description Comment details

4 Form 1 to 5 General Owner /OE’s Comment dated 26-06-2019 Commented by: Owner/OE’s
Please specify what the Codes & Standards are referring to.

4.1 Contractors response dated DD-MM-YYYY

5 2 Installation Owner /OE’s Comment dated 26-06-2019 Commented by: Owner/OE’s


Please add “Barcol hardness test” with status of Owner is “RW” status.
Please add “tightening flange joint (if any)” with status of Owner is “RW” status.

5.1 Contractors response dated DD-MM-YYYY

6 3 Final inspection Owner /OE’s Comment dated 26-06-2019 Commented by: Owner/OE’s
Please add “Hydro test package review” with status of Owner is “R” status.
Please add “Inside cleaning after hydrostatic test” with status of Owner is “RW” status.
Please add “Sand, soil backfilling” with status of Owner is “RW” status.

6.1 Contractors response dated DD-MM-YYYY