Nghi Son 2 BOT Thermal Power Plant Project

Design Query Sheet

DQ Sheet No DQ-NS2-DD09-P0ZEN-140016-A-WSP1
Document Title Method Statement for Calibration of Instrumentfor Calibration of Instrument
Document No NS2-DD09-P0ZEN-140016 Rev A
Status Description Approved except as noted (revise and resubmit) Status Code 2
These comments and/or approval by the Owner / Owners Engineer’s in no way relieves the Contractor from his obligations to ensure conformance with the requirements of
the Contract. Any Contract deviations found subsequent to approval are to be corrected by the Contractor to the satisfaction of the Owner / Owners Engineer’s.
Sl No Cl. No & page no Item description Comment details

1. Section 4, page 3 Responsibilities Owner /OE’s Comment dated 27-01-2020


HSSE responsibility will ensure that all the activities are carried out in accordance with the relevant safety regulations
at calibration workshop.

1.1 Contractors response dated DD-MM-YYYY

2. Section 5.5, page 5 Pre-Arrangement Owner /OE’s Comment dated 27-01-2020


Please check and request:
Test equipment control and traceability, all the equipment being used for the calibration shall be itself calibrated and
certified by a third party.

2.1 Contractors response dated DD-MM-YYYY

3. Section 7.1.3, page HART Type Owner /OE’s Comment dated 27-01-2020
9 Instrument Except the categories mentioned in section 7.1.1 and 7.1.2, need to review manufacturer’s instruction manual for
Verification specialized hand tools, equipment prepared before Verification/Calibration.

3.1 Contractors response dated DD-MM-YYYY

529828130.docx Page 1 of 3
Sl No Cl. No & page no Item description Comment details

4. Section 7.3.3, page Level/Flow Owner /OE’s Comment dated 27-01-2020


15 Indicator “Sheath length” for instrument is request following datasheet.

4.1 Contractors response dated DD-MM-YYYY

5. Section 7.3.3, page Level/Flow Owner /OE’s Comment dated 27-01-2020


15 Indicator It is stated that “No Verification/Calibration is required”, level/flow indicator also to be calibrated.

5.1 Contractors response dated DD-MM-YYYY

6. Calibration Owner /OE’s Comment dated 27-01-2020


certificate Validity of calibration certificate for some will be less than 12 months. Doosan to revise this statement by “12 months or
less as per instrument supplier recommendation”.

6.1 Contractors response dated DD-MM-YYYY

7. Calibration record Owner /OE’s Comment dated 31-01-2020


As per I&C design criteria: All instruments, analyzers, valves shall be calibrated prior to shipment of equipment.
Calibration has to be documented and testing certificates shall be included in delivery. Instrument shall be recalibrated at
site as well.
Doosan to confirm to provide Manufacturer’s calibration record in QCR.

7.1 Contractors response dated DD-MM-YYYY

8. Item 5.4.g Calibration sticker Owner /OE’s Comment dated 31-01-2020


Doosan to put detail the color code of calibration sticker after calibration is completed.
529828130.docx Page 2 of 3
Sl No Cl. No & page no Item description Comment details

For example:

8.1 Contractors response dated DD-MM-YYYY

9. Item 7.1.1.2 (l) Owner /OE’s Comment dated 31-01-2020


Doosan to detail “appropriate adjustment” in this clause. Usually, “linearity adjustment” shall be performed in this case,
and step (h)  step (k) shall be repeated until obtaining acceptable accuracy.

9.1 Contractors response dated DD-MM-YYYY

10. Item 7.1.3) Owner /OE’s Comment dated 31-01-2020


Doosan to separate the procedure for special flow transmitters like magnetic, untrasonic, vortex, corriolis. Usually, these
special transmitters will only be performed “zero” on site.

10.1 Contractors response dated DD-MM-YYYY

529828130.docx Page 3 of 3