225 kV Guinea-Mali Power Interconnection Project

Lot n ° P6: 225/30 kV Beyla and Nzérékoré substations


International Bidding Document / PART 2 - Project Owner s Requirements
Section VII. Specifications

DATA SHEET

20 MVA 225/30/11 kV transformer

Item Designation Units Specified Value Guaranteed value


63 Transformation Report A 100-200 / 1-1
64 Precision power VA 10
65 Class and accuracy limit factor according to - 5P20
IEC
Built-in current transformers
in LV bushings:
66 Manufacturer
67 Transformation Report A 250-500 / 1-1-1
68 Precision power VA 10
69 Class and accuracy limit factor according to 3x5P20
IEC
Built-in current transformers
in the LV Neutral crossing:
70 Manufacturer
71 Transformation Report A 300 / 1-1
72 Precision power VA 10
73 Class and accuracy limit factor according to - 5P20
IEC
Transformers incorporated in the
bushings for supplying the heating
resistor of the image relay
Thermic:
74 Manufacturer
75 Transformation Report A
76 Precision power VA
77 Class and accuracy limit factor according to -
IEC
Characteristics of the re-switch
load:
78 Manufacturer
79 Type Vacuum cut
80 Number of Taps 25
81 Insulation voltage kV 145
82 Voltage V DC 127
83 Maximum intensity in continuous service A
84 Type of command
85 Power consumed by the actuating motor W

86 Full designation of the tap changer

short-circuit operation
87 HV / LV short-circuit voltage at 75 ° C
(Base 20 MVA)
Lower socket %
Main Tap % 8
Top grip %

Page VII-27