Design Area Calc. Mode Occupancy Area of Total Water Pressure @ Min. Min. Min. Calculated Hose Margin To
Name (Model) Application Source Density Pressure Flow Heads Streams Source
DesignArea_1 Demand (HW) 55.7 3276.21 11.07 40.8 1.57 455 5 946.35 0.81
Contractor Information
Name of Contractor:
Address: City:
Name of Designer:
Design
Remote Area Name DesignArea_1
Occupancy Classification
Special Heads
Location
Source
Notes
Hoses
Inside Hose Flow / Standpipe Demand (l/min) 0
Sprinklers
Ovehead Sprinkler Flow (l/min) 2329.86
Other
Required Margin of Safety (bar) 0
Graph Labels
Values
Label Description
Flow (l/min) Pressure (bar)
S1 Supply point #1 - Static 0 12.07
S2 Supply point #2 - Residual 5678.12 9.31
D1 Elevation Pressure 0 0.47
D2 System Demand 3276.21 10.26
Open Heads
Required Calculated
Head Ref. Head Type Coverage K-Factor
Density Flow Pressure Density Flow Pressure
Overhead
h100 11.1 363.3 41 455.06 1.57 40.8 455 1.57
Sprinkler
Overhead
h101 11.1 363.3 41 455.06 1.57 41.1 458.44 1.59
Sprinkler
Overhead
h102 11.1 363.3 41 455.06 1.57 43.1 480.34 1.75
Sprinkler
Overhead
h103 11.1 363.3 41 455.06 1.57 42.8 477.21 1.73
Sprinkler
Overhead
h104 11.1 363.3 41 455.06 1.57 41.2 458.87 1.6
Sprinkler
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES