Professional Documents
Culture Documents
Typical transmission
The flow of electrical power from generating station to consumer is called an Electric Power system
consisting of generating station, transmission network and distribution system. A typical
transmission along with distribution scheme is as shown below.
This scheme shows a generating station (generating 11kV power) which is located too far away
from cities and towns. The generated power is stepped up to 132kV, 220kV or more and transmitted
with the help of transmission lines and towers. Some of the factors like voltage levels, resistance and
inductance of lines, line performance, interference with neighbouring circuits, strength of supports,
sag calculations, tension etc have to be considered while designing transmission lines. During
maintenance or failures, an additional line runs parallel along with transmission lines called
duplicate line.
From substations, power is distributed to local distribution centres with the help of distributors.
From distributors, the power is transferred directly to the loads like factories or industries called
primary distribution. And for light loads it is further stepped down to 230V or 400V using
distribution transformers. This is called secondary distribution.
Following voltage levels are commonly used for transmission and distribution
1. For Generation: 6.6kV, 11kV,22kV or 33kV
2. For primary transmission 66kV,132kV,220kV upto 1200kV
3. For secondary transmission: 11kV, 22Kv or 33kV
4. For primary distribution: 6.6kV or 11kV
5. For secondary distribution: 230V and 400V
1. Reduction in current
Power transmitted is given by
P=√3VIcosф
Where V is the transmission voltage
I is the load current
cosф is the load power factor
Hence load current is given by
𝑃
I=
√3Vcosф
From above equation it is clear that for constant power factor the load current is inversely
proportional to the voltage. As voltage increases, current gets reduced, thus reducing the size of the
conductor for transmitting same amount of power.
2. Reduction in losses
Power loss in a line is given by
2
2
P
𝑤 = 3𝐼 R = 3 [ ] R
√3Vcosф
𝑃2 𝑅
=
𝑉2 𝑐𝑜𝑠2 ф
From the above expression, it is observed that power loss is inversely proportional to transmission
voltage i.e., greater the transmission voltage lesser the loss in the line.
𝑃2 𝜌𝑙
∴𝑊 =
𝑉 2 𝑊cos2 𝜙
𝑃 2 𝜌𝑙
𝑎=
𝑉 2 𝑊𝑐𝑜𝑠 2 𝜙
Volume of conductor material required
= 3 × area of conductor × length of line
= 3×a×𝑙
3×𝑃2 𝜌𝑙 2
Volume =
𝑤𝑣 2 cos2 𝜙
Assuming VS=VR, then power transmitted is proportional to square of voltage which increases
power handling capacity of line.
7. Equipments required for HVAC is simple and can be adopted without need of high
technology.
8. The total line cost/MW/km decrease with increase in voltage.
9. Lines can be easily tapped and extended.
10. Operation of HVAC system is simple and can be adopted easily.
The main objective of designing a high voltage transmission line is to transmit electrical energy at
the lowest cost with required reliability and satisfactory performance both from the point of its
electrical and mechanical considerations.
From economical point of view, the length of transmission line should be ‘l’ but due to sag, it
requires more conductor material and extra height of supporting poles which increases the overall
cost but if sag is too low then the wire gets subjected to an extra tension and maximum stress due to
factors like temperature, wind pressure etc. But without sufficient sag it is possible that conductor
will undergo mechanical failure hence it is necessary to design sag value considering all severe
conditions.
Definition of sag
Sag: the difference in levels between points of support and the lowest point on the conductor is
called sag.
Calculation of sag and tension
Two cases are considered. They are:
i. The supports supporting the conductor are located at equal level.
ii. The supports supporting the conductor are located at unequal level.
Consider a conductor supported A & B which are at same level as shown in figure.
7
Taking moments of these two forces about point P and equating them we get,
𝑥
𝑇 ∗ 𝑦 = 𝑤𝑥 ∗ [moment = force ∗⊥ distnace from fixed axis]
2
𝑊𝑥 2
∴ 𝑦= ------------------------------- 1
2𝑇
The equation shows that the trajectory is parabolic in nature. At the support A and B, the vertical
distance y from the origin O indicates the sag S.
𝐿
∴ At A or B, 𝑥 = 𝑙 = 2 and y=S
Substituting in equation 1
𝑤 𝐿 2 𝑤𝐿2
𝑆= ( ) = ------------------------------- 2
2𝑇 2 8𝑇
where L is the total span length, and
T is the tension in conductor.
The sag at any point P of the conductor is
Sag at P = S-y
𝑤𝐿2 𝑊𝑥 2
= -
8𝑇 2𝑇
𝑤
∴ Sag at P = 8𝑇 [𝐿2 − 4𝑥 2 ] -----------------------3
In hilly areas or at rivers it is not possible to have supports at equal levels, then it becomes
necessary to use supports at unequal levels as shown in figure
∴ L= 𝑥1 + 𝑥2 -----------------------------------------------3
If 𝑥1 & 𝑥2 are known, then sags S1 and S2 can be obtained using equations 1 & 2, by
subtracting equation 1 from 2.
𝑤
∴ S2-S1 = 2𝑇 (𝑥22 − 𝑥12 )
𝑤
= 2𝑇 (𝑥2 − 𝑥1 )(𝑥2 + 𝑥1 )
From figure it is also seen that distance h which is difference in levels is also the difference
between 2 sags S1 and S2.
∴ S2-S1= h -----------------------------------------------5
Now from equations 4 & 5
𝑤
h = 2𝑇 (𝑥2 − 𝑥1 ) 𝐿
2𝑇ℎ
∴𝑥2 − 𝑥1 = --------------------------------- 6
𝑤𝐿
Solving equations 3 and 6 simultaneously, we get
𝐿 𝑇ℎ
𝑥1 = − -------------------------------------7
2 𝑤𝐿
𝐿 𝑇ℎ
𝑎𝑛𝑑 𝑥2 = + ----------------------------------------8
2 𝑤𝐿
Considering density of ice to be 915kg/m3 and if d and D are in mts, then area in m2 i.e., volume of
ice in m3/metre length of conductor. Then total weight of ice can be obtained as,
𝜋
Eight of ice/unit length = wi =915 * [𝐷2 − 𝑑2 ] kg/m ---------------3
4
Since the wind flow horizontally, its pressure on conductor is considered to be acting perpendicular
to conductor. Thus force due to wind acts at right angles to the projected surface of the conductor as
shown in figure.
11
Note:
1. The sag direction is at an angle θ measure with respect to vertical called as slant sag. From
earlier expression and considering the total weight wt
𝑤𝑡 𝐿2
∴Slant sag, S=
8𝑇
12
3. And the vertical sag is cosine component of the slant sag[ as it is direction at an angle θ w.r.t.
vertical]
∴vertical sag = Scosθ
Factor of safety
Every conductor has certain ultimate strength to withstand beyond which mechanical failure of
conductor occurs. Thus while calculating sag and tension, a particular factor of safety is to be
considered.
Factor of safety is defined as the ratio of breaking stress (ultimate stress) to working stress (normal
stress) denoted by Sf.
Mathematically,
𝒃𝒓𝒆𝒂𝒌𝒊𝒏𝒈 𝒔𝒕𝒓𝒆𝒔𝒔
Sf =
𝒘𝒐𝒓𝒌𝒊𝒏𝒈 𝒔𝒕𝒓𝒆𝒔𝒔
𝒖𝒍𝒕𝒊𝒎𝒂𝒕𝒆 𝒔𝒕𝒓𝒆𝒏𝒈𝒕𝒉
=
𝒂𝒍𝒍𝒐𝒘𝒂𝒃𝒍𝒆 𝒘𝒐𝒓𝒌𝒊𝒏𝒈 𝒕𝒆𝒏𝒔𝒊𝒐𝒏 𝑻
[The stress is generally expressed in kg/m2 or kg/cm2 hence it must be multiplied by area of the
conductor to express it in kg]
13
Fig shows two wire transmission line a and b at distance ‘d’ m apart and of radius ‘r’ m each. The
flux linkages on anyone conductor say ‘a’ is due to
1. The internal flux linkages 𝜆𝑖𝑛𝑡 .
3. The flux linkages between the region (d-r) and (d+r) i.e., over the surface of the conductor b.
4. The flux linkages beyond (d+r). [ is zero as total current enclosed is zero]
Let H be the magnetic field intensity(amp-turns/metre) at any point distance 𝑥 (metres) from the centre
of the conductor.
14
∮ 𝑯𝒙 𝒅𝒔 = 𝑰𝒙
Where ∮ indictaes the integration around a closed path and
Hence, 2𝜋𝑥𝐻𝑥 = 𝐼𝑥 .
Assuming a uniform current density in the conductor,
𝝅𝒙𝟐
𝑰𝒙 = 𝑰
𝝅𝒓𝟐
𝑰 𝝅𝒙𝟐 𝒙
∴ 𝑯𝒙 = 𝟐𝝅𝒙
𝒙
=
𝝅𝒓𝟐 . 𝟐𝝅𝒙
𝑰=
𝟐𝝅𝒓𝟐
· 𝑰 𝑨𝑻/𝒎
If (µ = µ0 µ𝑟 ) is the permeability of the conductor, then flux density (𝐵𝑥) at a distance 𝑥 from the
centre of the conductor is given by
µ𝒙 𝑰
𝑩𝒙 = µ𝑯𝒙 = 𝒘𝒆𝒃𝒆𝒓/𝒎𝟐
𝟐𝝅𝒓𝟐
Now the flux enclosed in element thickness dx and per metre (axial) length of the conductor is given by
µ𝒙𝑰
𝒅𝝓 = 𝐝𝐱 . 𝟏 𝐰𝐞𝐛𝐞𝐫𝐬
𝟐𝝅𝒓𝟐
This flux links with current Ix so that flux linkages per metre length of the conductor is given by
𝝅𝒙𝟐 µ𝒙𝟑
𝒅𝝍 = 𝒅𝝓 = ( 𝑰𝐝𝐱) wb-turns
𝝅𝒓𝟐 𝟐𝝅𝒓𝟒
𝒓
µ𝒙𝟑 µ𝑰
∴ 𝝍𝒊𝒏𝒕 = ∫ 𝑰𝐝𝐱 = wb − turns
𝟐𝝅𝒓𝟒 𝟖𝝅
𝟎
𝜳𝒊𝒏𝒕 𝟏𝟎−𝟕
∴ 𝑳𝒊𝒏𝒕 = = ℎ𝑒𝑛𝑟𝑦/𝑚𝑒𝑡𝑟𝑒
𝑰 𝟐
15
Now consider the flux linkages of an isolated conductor due to that portion of flux that lies between
two points distant 𝐷1 𝑎𝑛𝑑 𝐷2 mts from centre of conductor 𝑃1 𝑎𝑛𝑑 𝑃2 .
The conductor shown in figure carries current I. the flux paths are concentric circles around the conductor
between 𝑃1 𝑎𝑛𝑑 𝑃2 . Consider a tubular element which 𝑥 mts from center of the conductor. The field intensity
at this point is 𝐻𝑥 . The m.m.f around the element is
𝟐𝝅 × 𝑯𝒙 = 𝑰
The flux density 𝐵𝑥 at this point is given by
µ𝑰
𝑩𝒙 = µ𝑯𝒙 = 𝒘𝒃/𝒎𝟐
𝟐𝝅𝒙
µ𝑰
∴ 𝒅𝝓 = 𝟐𝝅𝒙 𝒅𝒙
The flux linkages d𝜓/meter are equal to 𝑑𝜙 since flux external to the conductor links all the current
in the conductor. the total flux linkage between P1 and P2 are obtained by integrating 𝑑𝜓 from
𝐷1 𝑡𝑜 𝐷2.
𝑫𝟐
µ𝑰 µ𝑰 𝐷2 𝐝𝐱 µ𝑰
𝐷2
𝝍𝟏𝟐 = ∫ 𝒅𝒙 = ∫𝐷 = 𝒍𝒏 ( ‾ )and µ = µ𝟎 µ𝒓
𝟐𝝅𝒙 𝟐𝝅 1 𝒙 𝟐𝝅 𝐷1
𝑫𝟏
µ𝑰
𝑫𝟐 𝟒𝝅×𝟏𝟎−𝟕 𝑰
𝑫𝟐 𝑫𝟐
𝝍𝟏𝟐 = 𝟐𝝅
𝒍𝒏 ( ‾ )= 𝟐𝝅
𝒍𝒏 ( ‾ ) = 2 𝑿 𝟏𝟎−𝟕 𝑰 𝒍𝒏 ( ‾ )
𝑫𝟏 𝑫𝟏 𝑫𝟏
16
𝝍𝟏𝟐
𝑫𝟐
∴𝑳𝟏𝟐 = = 𝟐 𝑿 𝟏𝟎−𝟕 𝒍𝒏 ( ‾ )
𝑰
𝑫𝟏
Considered a single-phase line consisting of two conductors (phase and neutral) a and b of equal
radius r. They are situated at a distance D meters. The cross sections of conductors are shown in
the diagram below.
Let the current flow in the conductors are opposite in direction so that one becomes return path
for the other.
The flux linkages of conductor ‘a’ is given by the formula
𝟏 𝟏
𝝍𝒂= 𝟐 × 𝟏𝟎−𝟕 [𝑰𝒂 𝐥𝐧 + 𝑰𝒃 ]
𝑫𝒂𝒂 𝑫𝒂𝒃
Here,
𝑰𝒂 = +𝑰
𝑰𝒃 = −𝑰
𝑫𝒂𝒂 = 𝒓𝟏
𝑫𝒂𝒃 = 𝑫
17
𝟏 𝟏
𝝍𝒂= 𝟐 × 𝟏𝟎−𝟕 [𝑰𝒂 𝐥𝐧 𝟏
− 𝑰𝒃 ]
𝒓 𝐃
𝑫
= 𝟐 × 𝟏𝟎−𝟕 𝑰 𝒍𝒏
𝒓𝟏
Similarly, the flux linkage with the conductor ‘b’ will be
𝑫
𝝍𝒃 = 𝟐 × 𝟏𝟎−𝟕 𝑰 𝒍𝒏 𝒓𝟏
𝑫
Loop inductance = La + Lb = 2 × 𝟐 × 𝟏𝟎−𝟕 𝒍𝒏 𝑯/𝒎
𝒓𝟏
𝑫
= 4 × 𝟏𝟎−𝟕 𝒍𝒏 𝑯/𝒎
𝒓𝟏
The inductance of an individual conductor is one-half of the total inductance of a two- wire line.
Note: the radius 𝒓𝟏 is an imaginary or fictious conductor assumed to have no internal flux. The
quantity 𝜺−𝟏/𝟒 equals to 0.7788. ∴ 𝒓𝟏 = 𝟎. 𝟕𝟕𝟖𝟖𝒓
18
In symmetrical three-phase line, all the conductors are placed at the corners of the equilateral
triangle. Such an arrangement of conductors is also referred to as equilateral spacing. It is
shown in the diagram below
∴ 𝑰𝒂 = −(𝑰𝒃 + 𝑰𝑪 )
𝑫
= 𝟐 × 𝟏𝟎−𝟕 𝑰𝒂 𝐥𝐧 (𝒓𝟏 )
𝝍𝒂 𝑫
𝑳𝒂 = = 𝟐 × 𝟏𝟎−𝟕 𝐥𝐧 (𝒓𝟏 )
𝑰𝒂
Because of symmetry, conductors ‘b’ and ‘c’ will have same inductance as that of conductor ‘a’.
each phase consists of only one conductor. So, the above equation gives inductance/ phase of three
phase lines.
19
A three-phase line is said to be unsymmetrical when its conductors are situated at different
distances. Such arrangement of conductors is most common in practice because of their
cheapness and convenience in design and construction. Consider a three-phase
unsymmetrical line, having different spacing between their conductors where the radius of
each conductor is r. It is shown in the diagram below
𝟏 𝟏 𝟏
𝝍𝒂𝟏 = 𝟐 × 𝟏𝟎−𝟕 (𝑰𝒂 𝐥𝐧 𝒓𝟏 + 𝑰𝒃 𝐥𝐧 𝑫 + 𝑰𝒄 𝐥𝐧 𝑫 )
𝟏𝟐 𝟑𝟏
𝟏 𝟏 𝟏
𝝍𝒂𝟐 = 𝟐 × 𝟏𝟎−𝟕 (𝑰𝒂 𝐥𝐧 𝒓𝟏 + 𝑰𝒃 𝐥𝐧 𝑫 + 𝑰𝒄 𝐥𝐧 𝑫 )
𝟐𝟑 𝟏𝟐
𝟏
𝝍𝒂 = (𝝍 + 𝝍𝒂𝟐 + 𝝍𝒂𝟑 )
𝟑 𝒂𝟏
20
𝟐 𝟏 𝟏 𝟏
𝝍𝒂 = × 10−7 ( 𝟑𝑰𝒂 𝐥𝐧 𝟏 + 𝑰𝒃 𝐥𝐧 + 𝑰𝒄 𝐥𝐧 )
𝟑 𝒓 𝑫𝟏𝟐 𝑫𝟐𝟑 𝑫𝟑𝟏 𝑫𝟏𝟐 𝑫𝟐𝟑 𝑫𝟑𝟏
𝟐 𝟏 𝟏
𝝍𝒂 = × 10−7 ( 𝟑𝑰𝒂 𝐥𝐧 𝟏 + (𝑰𝒃 + 𝑰𝒄 ) 𝐥𝐧 )
𝟑 𝒓 𝑫𝟏𝟐 𝑫𝟐𝟑 𝑫𝟑𝟏
𝑰𝒂 + 𝑰𝒃 + 𝑰𝒄 = 𝟎
∴ (𝑰𝒃 + 𝑰𝑪 ) = −𝑰𝒂
𝟐 𝟏 𝟏
∴ 𝝍𝒂 = × 10−7 ( 𝟑𝑰𝒂 𝐥𝐧 𝟏 − 𝑰𝒂 𝐥𝐧 )
𝟑 𝒓 𝑫𝟏𝟐 𝑫𝟐𝟑 𝑫𝟑𝟏
𝟏
𝟑√𝑫𝟏𝟐 𝑫𝟐𝟑 𝑫𝟑𝟏 𝟏
∴ 𝝍𝒂 = 𝟐 × 𝟏𝟎−𝟕 𝑰𝒂 𝐥𝐧 ( ) ∵ 𝟐 𝐥𝐧𝒎 = 𝐥𝐧𝒎𝟐
𝒓𝟏
21