You are on page 1of 10

Unit A&B JTVCF Bldg.

#46B Luzon St.corGen.Santos St.


Central Signal Village
Philippines
International Lift Services, Inc. Tel. No. (632)832-4103

TEST DATA REPORT

This certifies that Nanotech International Lift Services Inc., has conducted the following Testing of
One (1) unit Passenger Elevator 1 at TOWER 3 located at BAYVIEW PARANAQUE. That all
discrepancies in accomplishments of the work have been checked and adjustments thereof have been
made accordingly.

Test Report of Safety Gear


Rated speed 2.5 m/s
Diameter of wire ropes 10 mm
Sheave diameter 200 mm

CONTROL METHOD COLLECTIVE


TYPE OF TIMING VVVF
FLOOR 20
SPEED 2.5 M/S
POWER 20.4 KW

RATED READINGS
RATED ROTATE SPEED 197 RPM
RATED VOLTAGE 380 VOLTS
RATED CURRENT 42.9 A
RATED POWER 20.4 KW
RATED TORQUE 990 N.M
RATED HZ 52.5 HZ
MOTOR TYPE SYNCHRONIZE MOTOR

Page 1
ACTUAL READINGS

INPUT OUTPUT
L1 – GND = 133 V L1 – GND = 219 V
L2 – GND = 136 V L2 – GND = 232 V
L3 – GND = 136 V L3 – GND = 216 V
L1 – L2 = 231 V L1 – L2 = 383 V
L2 – L3 = 236 V L2 – L3 = 391 V
L3 – L1 = 232 V L3 – L1 = 385 V

SAFETY CIRCUIT CHECK

UP FINAL LIMIT OK
UP STOP LIMIT OK
UP SLOW DOWN LIMIT OK
DOWN FINAL LIMIT OK
DOWN STOP LIMIT OK
DOWN SLOW DOWN LIMIT OK
SAFETY GEAR SWITCH OK
CAR TOP EMERGENCY STOP OK
CAR COP STOP OK
PIT EMERGENCY STOP OK

We hereby certify that the products of has been passed the test and conforms to the technical
requirement of our company. It also conform that the unit is safe to operate.

This Certificate of Test Report is hereby issued for whatever purpose it may serve.

Issued this 27th day of August 2021.

Certified By:
Nanotech International Lift Services Inc.,

Prepared by:

Gerry Tamayo
Technical Supervisor

Noted By: Received By:

ENGR. BRYLLE JOSEPH M. DALIT _____________________


Service Manager Signed over printed Name
Building Representative

Date : _______________

Page 2
Unit A&B JTVCF Bldg.
#46B Luzon St.corGen.Santos St.
Central Signal Village
Philippines
International Lift Services, Inc. Tel. No. (632)832-4103

TEST DATA REPORT

This certifies that Nanotech International Lift Services Inc., has conducted the following Testing of
One (1) unit Passenger Elevator 2 at TOWER 3 located at BAYVIEW PARANAQUE. That all
discrepancies in accomplishments of the work have been checked and adjustments thereof have been
made accordingly.

Test Report of Safety Gear


Rated speed 2.5 m/s
Diameter of wire ropes 10 mm
Sheave diameter 200 mm

CONTROL METHOD COLLECTIVE


TYPE OF TIMING VVVF
FLOOR 23
SPEED 2.5 M/S
POWER 20.4 KW

RATED READINGS
RATED ROTATE SPEED 191 RPM
RATED VOLTAGE 380 VOLTS
RATED CURRENT 42.9 A
RATED POWER 20.4 KW
RATED TORQUE 990 N.M
RATED HZ 52.5 HZ
MOTOR TYPE SYNCHRONIZE MOTOR

Page 1
ACTUAL READINGS
INPUT OUTPUT
L1 – GND = 133 V L1 – GND = 215 V
L2 – GND = 136 V L2 – GND = 223 V
L3 – GND = 136 V L3 – GND = 231 V
L1 – L2 = 231 V L1 – L2 = 383 V
L2 – L3 = 236 V L2 – L3 = 391 V
L3 – L1 = 232 V L3 – L1 = 384 V

SAFETY CIRCUIT CHECK

UP FINAL LIMIT OK
UP STOP LIMIT OK
UP SLOW DOWN LIMIT OK
DOWN FINAL LIMIT OK
DOWN STOP LIMIT OK
DOWN SLOW DOWN LIMIT OK
SAFETY GEAR SWITCH OK
CAR TOP EMERGENCY STOP OK
CAR COP STOP OK
PIT EMERGENCY STOP OK

We hereby certify that the products of has been passed the test and conforms to the technical
requirement of our company. It also conform that the unit is safe to operate.

This Certificate of Test Report is hereby issued for whatever purpose it may serve.

Issued this 27th day of August 2021.

Certified By:
Nanotech International Lift Services Inc.,

Prepared by:

Gerry Tamayo
Technical Supervisor

Noted By: Received By:

ENGR. BRYLLE JOSEPH M. DALIT _____________________


Service Manager Signed over printed Name
Building Representative

Date : _______________

Page 2 Unit A&B JTVCF Bldg.


#46B Luzon St.corGen.Santos St.
Central Signal Village
Philippines
International Lift Services, Inc. Tel. No. (632)832-4103
TEST DATA REPORT

This certifies that Nanotech International Lift Services Inc., has conducted the following Testing of
One (1) unit Service Elevator at TOWER 3 located at BAYVIEW PARANAQUE. That all discrepancies in
accomplishments of the work have been checked and adjustments thereof have been made
accordingly.

Test Report of Safety Gear


Rated speed 1.750 m/s
Diameter of wire ropes 10 mm
Sheave diameter 200 mm

CONTROL METHOD COLLECTIVE


TYPE OF TIMING VVVF
FLOOR 23
SPEED 1.2 M/S
POWER 15.7 KW

RATED READINGS
RATED ROTATE SPEED 174 RPM
RATED VOLTAGE 380 VOLTS
RATED CURRENT 36.8 A
RATED POWER 15.7 KW
RATED TORQUE 860 N.M
RATED HZ 29.00 HZ
MOTOR TYPE SYNCHRONIZE MOTOR

Page 1
ACTUAL READINGS
INPUT OUTPUT
L1 – GND = 133 V L1 – GND = 223 V
L2 – GND = 136 V L2 – GND = 228 V
L3 – GND = 136 V L3 – GND = 228 V
L1 – L2 = 233 V L1 – L2 = 389 V
L2 – L3 = 237 V L2 – L3 = 397 V
L3 – L1 = 232 V L3 – L1 = 388 V

SAFETY CIRCUIT CHECK

UP FINAL LIMIT OK
UP STOP LIMIT OK
UP SLOW DOWN LIMIT OK
DOWN FINAL LIMIT OK
DOWN STOP LIMIT OK
DOWN SLOW DOWN LIMIT OK
SAFETY GEAR SWITCH OK
CAR TOP EMERGENCY STOP OK
CAR COP STOP OK
PIT EMERGENCY STOP OK

We hereby certify that the products of has been passed the test and conforms to the technical
requirement of our company. It also conform that the unit is safe to operate.

This Certificate of Test Report is hereby issued for whatever purpose it may serve.

Issued this 27th day of August 2021.

Certified By:
Nanotech International Lift Services Inc.,

Prepared by:

Gerry Tamayo
Technical Supervisor

Noted By: Received By:

ENGR. BRYLLE JOSEPH M. DALIT _____________________


Service Manager Signed over printed Name
Building Representative

Date : _______________

Page 2 Unit A&B JTVCF Bldg.


#46B Luzon St.corGen.Santos St.
Central Signal Village
Philippines
International Lift Services, Inc. Tel. No. (632)832-4103
TEST DATA REPORT

This certifies that Nanotech International Lift Services Inc., has conducted the following Testing of
One (1) unit Service Elevator at TOWER 2 located at BAYVIEW PARANAQUE. That all discrepancies in
accomplishments of the work have been checked and adjustments thereof have been made
accordingly.

Test Report of Safety Gear


Rated speed 1.750 m/s
Diameter of wire ropes 10 mm
Sheave diameter 200 mm

CONTROL METHOD COLLECTIVE


TYPE OF TIMING VVVF
FLOOR 23
SPEED 1.2 M/S
POWER 15.7 KW

RATED READINGS
RATED ROTATE SPEED 174 RPM
RATED VOLTAGE 380 VOLTS
RATED CURRENT 36.8 A
RATED POWER 15.7 KW
RATED TORQUE 860 N.M
RATED HZ 29.00 HZ
MOTOR TYPE SYNCHRONIZE MOTOR

Page 1

ACTUAL READINGS
INPUT OUTPUT
L1 – GND = 136 V L1 – GND = 227 V
L2 – GND = 136 V L2 – GND = 220 V
L3 – GND = 132 V L3 – GND = 218 V
L1 – L2 = 235 V L1 – L2 = 390 V
L2 – L3 = 230 V L2 – L3 = 382 V
L3 – L1 = 231 V L3 – L1 = 382 V

SAFETY CIRCUIT CHECK

UP FINAL LIMIT OK
UP STOP LIMIT OK
UP SLOW DOWN LIMIT OK
DOWN FINAL LIMIT OK
DOWN STOP LIMIT OK
DOWN SLOW DOWN LIMIT OK
SAFETY GEAR SWITCH OK
CAR TOP EMERGENCY STOP OK
CAR COP STOP OK
PIT EMERGENCY STOP OK

We hereby certify that the products of has been passed the test and conforms to the technical
requirement of our company. It also conform that the unit is safe to operate.

This Certificate of Test Report is hereby issued for whatever purpose it may serve.

Issued this 27th day of August 2021.

Certified By:
Nanotech International Lift Services Inc.,

Prepared by:

Gerry Tamayo
Technical Supervisor

Noted By: Received By:

ENGR. BRYLLE JOSEPH M. DALIT _____________________


Service Manager Signed over printed Name
Building Representative

Date : _______________

Page 2
Unit A&B JTVCF Bldg.
#46B Luzon St.corGen.Santos St.
Central Signal Village
Philippines
International Lift Services, Inc. Tel. No. (632)832-4103
TEST DATA REPORT

This certifies that Nanotech International Lift Services Inc., has conducted the following Testing of
One (1) unit Service Elevator at TOWER 1 located at BAYVIEW PARANAQUE. That all discrepancies in
accomplishments of the work have been checked and adjustments thereof have been made
accordingly.

Test Report of Safety Gear


Rated speed 1.750 m/s
Diameter of wire ropes 10 mm
Sheave diameter 200 mm

CONTROL METHOD COLLECTIVE


TYPE OF TIMING VVVF
FLOOR 23
SPEED 1.2 M/S
POWER 15.7 KW

RATED READINGS
RATED ROTATE SPEED 174 RPM
RATED VOLTAGE 380 VOLTS
RATED CURRENT 36.8 A
RATED POWER 15.7 KW
RATED TORQUE 860 N.M
RATED HZ 29.00 HZ
MOTOR TYPE SYNCHRONIZE MOTOR

Page 1

ACTUAL READINGS
INPUT OUTPUT
L1 – GND = 136 V L1 – GND = 228 V
L2 – GND = 133 V L2 – GND = 225 V
L3 – GND = 134 V L3 – GND = 220 V
L1 – L2 = 237 V L1 – L2 = 388 V
L2 – L3 = 231 V L2 – L3 = 383 V
L3 – L1 = 230 V L3 – L1 = 381 V

SAFETY CIRCUIT CHECK

UP FINAL LIMIT OK
UP STOP LIMIT OK
UP SLOW DOWN LIMIT OK
DOWN FINAL LIMIT OK
DOWN STOP LIMIT OK
DOWN SLOW DOWN LIMIT OK
SAFETY GEAR SWITCH OK
CAR TOP EMERGENCY STOP OK
CAR COP STOP OK
PIT EMERGENCY STOP OK

We hereby certify that the products of has been passed the test and conforms to the technical
requirement of our company. It also conform that the unit is safe to operate.

This Certificate of Test Report is hereby issued for whatever purpose it may serve.

Issued this 27th day of August 2021.

Certified By:
Nanotech International Lift Services Inc.,

Prepared by:

Gerry Tamayo
Technical Supervisor

Noted By: Received By:

ENGR. BRYLLE JOSEPH M. DALIT _____________________


Service Manager Signed over printed Name