Site Test Report

Contract No. – N-6166.1 CONSORTIIUM


New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:11.06.2012 Bay/Feeder : =E04 – Cable Feeder (E48 CIRCUIT-1) Page 1 of 3

High Voltage Switchgear Type 8DN8 72,5 kV and above


Current Transformers
Hochspannungsschaltanlagen 8D . . ab 72,5 kV
Stromwandler
Customer: Contract No.:
Kunde: TRANSCO Vertragsnr.: N-6166.1
Consultant: Bay/Feeder:
Berater: ENERGO CONSULT Abzweig: =E04
Substation: Serial No.:
Anlage: ADNEC Fabrik-Nr.: 31 259 838
Switchgear type: Rated voltage:
Schaltanlagentyp: 8DN8 Bemessungsspannung: 145 kV

Current transformer: item designation: Type: P2 in direction busbar


Stromwandler: Betriebsmittelkennz.: T2 Typ: AMT145/3 in Richtung SaS*/Feld*

Serial-No.:
Fabrik-Nr.: L1: 11/101 201 L2: 11/101 201 L3: 11/101 201

Core-No.
Kern-Nr. Core 1 Core 2 Core 3 Core 4
Core data Kern 1 Kern 2 Kern 3 Kern 4
Kerndaten
Nominal power VA 30-20 VA
Nennleistung
Nominal Ratio 1500-1000/1A 1500-1000/1A
Nennübersetzung
Class PX 0.5FS 5
Klasse
Magnetizing – U0 ≥600-400 V V
Magnetizing – I0 ≤50-80 mA mA
Resistance Rct ≤6-4 Ω ≤ 3.5 - 2.5 Ω
Earthed at 1S3 2S3
Geerdet an
Used for BUSBAR PRTN BCU
Verwendet für
Polarity check Error: Error: Error: Error: Error: Error: Error: Error: Error: Error: Error: Error:
Polaritätsprüfung Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer
Secondary circuits
checked up to: +S3 +S3
Sekundärverdrahtung
geprüft bis:

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHIL KUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO
Site Test Report
Contract No. – N-6166.1 CONSORTIIUM
New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:11.06.2012 Bay/Feeder : =E04 – Cable Feeder (E48 CIRCUIT-1) Page 2 of 3

INSULATION TEST (with 1000V insulation tester) Amb Temp:31.4 °C

TERMINAL WINDINGS R Y B
MARKING C.T + LEAD WIRE C.T + LEAD WIRE C.T + LEAD WIRE
UPTO TB UPTO TB UPTO TB

Core1-Earth 7.11 G Ω 5.14 G Ω 6.21 G Ω


T2 Core2-Earth 6.20 G Ω 4.93 G Ω 6.57 G Ω

Core 1-Core2 14.1 G Ω 10.5 G Ω 13.1 G Ω

RESISTANCE MEASUREMENT OF SECONDARY WINDINGS


Amb Temp:30.5 °C

CORE Resistance at Amb Temp in Ohms Resistance at 75˚C in Ohms


PHASE 1S1-1S2 1S1-1S3 2S1-2S2 2S1-2S3 1S1-1S2 1S1-1S3 2S1-2S2 2S1-2S3
R 2.884 4.456 1.479 2.327 3.368 5.203 1.727 2.717
Y 2.849 4.399 1.473 2.315 3.327 5.137 1.720 2.703
B 2.907 4.504 1.470 2.312 3.394 5.259 1.717 2.700

CT RATIO TEST

CURRENT CURRENT MEASURED ACROSS


% ERROR
INJECTED SECONDARY TERMINALS (mA)
CT RATIO
TERMINALS ACROSS
(A)
PRIMARY R-Phase Y-Phase B-Phase R-Phase Y-Phase B-Phase
(A)
1S1-1S2 1000/1A 600 599.2 599.2 599.3 -0.11 -0.11 -0.10
1S1-1S3 1500/1A 600 399.5 399.4 399.5 -0.11 -0.11 -0.10
2S1-2S2 1000/1A 600 599.4 601.1 601.13 -0.08 -0.22 -0.13
2S1-2S3 1500/1A 600 399.5 400.3 400.32 -0.09 -0.10 -0.11

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHIL KUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO
Site Test Report
Contract No. – N-6166.1 CONSORTIIUM
New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:11.06.2012 Bay/Feeder : =E04 – Cable Feeder (E48 CIRCUIT-1) Page 3 of 3

Used Instruments Stock no Calibration Certificate Certificate valid until


available
OMICRON CPC-100 JH808Q(VI) YES 09.05.2013
MEGGER MIT 510 3381 YES 08.05.2013

Remarks:
Bemerkungen: For Magnetizing Curve -See attached Printouts of CPC 100
For C.T Secondary Winding Resistance- See attached Printouts of CPC 100

For Polarity test done as per approved drawing - See attached Printouts of CPC 100

For Ratio Test- See attached Printouts of CPC 100

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHIL KUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO