LETTER OF APPROVAL/COMMENTS FOR DRAWING / DOCUMENTS

Client: Rajkot Smart City Development Ltd. (RSCDL)


Project: 8MLD TTP at Raiyadhar, Rajkot.
Contractor: Gharpure Engg. & Const. Pvt. Ltd. (GECPL)
701,Rembrandt,Opp.Associated Petrol
Pump, C.G Road, Ellis bridge, Unit / Eqpt Name: 380kVA KOEL make DG set with AMF Panel
Ahmedabad-380006 Date: 15.09.2022
We here with convey our approval/comments on the documents listed below. Review of drawings/ documents in
accordance with contract Documents does not absolve Vendor/contractor from any responsibilities for their accuracy
of the design, performance and safety of the plant / works or any other obligations under the contract and Indian
Statutory laws nor does it limit the employer’s rights under the contract. Drawing / Document approval shall be read
in conjunction with this comments letter.
DRAWING / DOCUMENT REVIEW STATUS
A: Approved for construction / Manufacture. D: Not accepted Insufficient details. Return
without review.
B: Approved with comments. Construction/ E: Retained for Information only.
Manufacture may commence subject to
compliance of comments, Resubmit for review
and approval.
C: Resubmit for review after incorporating
comments.

Sr.
Rev.
No Drg. / Doc. Description
No.
.
380kVA Kirloskar Oil Engine Ltd. (KOEL) make DG Set Model: KGI-380WS with Engine R1
Make: Kirloskar Green, Model: DV8TAG2, & Alternator Make: Kirloskar Green, Frame:
1
KG472VS3 (DG set Qty.-1 No.) with Sound Canopy, Technical data sheet (TDS), Foundation
drg., etc. drg.
M/s Goel Power Engineers make AMF Panel for 380kVA DG set. GAD drg. No. R1
2
GPE/DG/W2223/30, Dtd.28/07/2022 & etc. drg.
3 QAP of Kirloskar Oil Engine Ltd. (KOEL) make 380kVA DG Set with AMF Panel R1
Comments on 380kVA DG set:
 This submission & approval shall be read in conjunction with comments compliance reply sheet dtd.nil
attached with this submission by contractor.
 Approval in Code ‘A’

Comments on AMF Panel (For 380kVA DG set) drg.:


Submitted Catalogue for Electronic AMF panel Logic relay is not clear for following functions. Pl.
clarify following function in submitted Catalogue for Electronic AMF panel Logic relay.
 Mains supply failure monitor
 Supply failure timer
 Restoration timer
 3 impulse Automatic engine Start / Stop attempts
 Failure to start indication
 Off / Manual / Auto / test Selectors
 Power On / Off Switch

Sr. Trip
Condition Indication Alarm
No. Annunciation
Provide R, Y, B Phase
A
Indicating lamp
Provide on, off, TRIP
B
indicating lamp
1 Mains on Yes ---
2 Generator on Yes ---
1|Page
LETTER OF APPROVAL/COMMENTS FOR DRAWING / DOCUMENTS

3 Load on Mains Yes ---


4 Load on generator Yes ---
5 Auto/ Manual Yes
6 Common Fault Yes
7 Over & Under Voltage Yes
8 Battery charger fault Yes
9 Low fuel oil level Yes
10 Over load Yes
11 Low Lub Oil Pressure Yes Yes
12 High water temperature Yes Yes
13 High Lub Oil temperature Yes
14 Set fails to start (with alarm) Yes Yes Yes
 AMF Panel: Approval in Code ‘C’

Comments on QAP of DG set with AMF Panel:


 Provided full load witness test for 10minutes is not acceptable. A full load witness test by Client / TPI
shall be carried out for 30minutes continuously by loading artificially as per tender.
 The overall efficiency of the DG Set at ¼ load, ½ load and full load shall be worked out.
 All necessary arrangements for testing under artificial load conditions such as cables, electrodes, load
and consumable like diesel, lubricating oil etc. shall be provided by the vender.
 Approval in Code ‘C’