You are on page 1of 1

Notes:

1. All dimensions are in meters, unless otherwise specified.


2. Coordinates are in meters & are referred to Project coordinates system.
Project coordinates (E = 0.000, N = 0.000) correspond to Dubai Local Transverse Mercator (DLTM)
coordinates (E = 510500.000, N = 2735500.000)

3. Elevations are in meters and are referred to Dubai Municipality Datum (DMD).

4. This drawing shall be read in conjuntion with all relevant architectural & civil drawings and technical
specifications. In case of discrepancy between civil works and other drawings, the Contractor shall
refer to the Engineer to define the order of applicability.

11CFA05 11CFA06 5. Under Lean concrete, a 250 mm layer of structural fill compacted to 98% maximum dry density (ASTM
D-1557), according to Earthworks Specification and Soil Investigation Report, shall be placed.

11CFA04 6. Material properties shall comply with the requirements of Civilworks & Steel Stucture Specifications:
- Lean concrete
f'c = 20MPa (cylinder test at 28 days)
Cement type I (*)
Maximum aggregate size: 25mm
L

- Foundations and underground structures concrete:


f'c = 35MPa (cylinder test at 28 days)
Cement type IIIA (*), Portland cement + 36%-65% GGBS
Exposure: S3 / c
K
Maximum water/cement ratio: 0.37
Minimum cement content: 410 Kg/m3
Maximum aggregate size: 20mm

- Above ground structures concrete:


J
f'c = 30MPa (cylinder test at 28 days)
Cement type IIIA (*), Portland cement + 36%-65% GGBS
Maximum water/cement ratio: 0.40
Minimum cement content: 380 Kg/m3
I
Maximum aggregate size: 20mm

- Reinforcement steel:
Grade B500B, minimum yield strength of 500MPa, as per BS4449:2005

H (*) Cement type in accordance with BS8500-1:2006 and DM Circular 225

- Post installed chemical anchor bolt: Hilti HIT-V-5.8 stainless steel + HIT-HY 200-R (or similar)

- Nuts ASTM A563M Grade A, washer ASTM A36. Hot dip galvanized protection.
G

- Steel structures ASTM A572 Gr 50 (profiles and plates)

7. Erection tolerances shall be executed according to AISC 303-16.

F
8. All reinforced concrete structures shall comply with the Civilworks Technical Specification and ACI
18-14. Dimensional tolerances shall be in accordance with ACI-117 "Specifications for tolerances for
concrete construction and materials"
All steel works shall conform to the Steel Structure Technical Specification.
E
9. Structure protection shall be according to document: NE1-00-EM-EAI-TSP-YM_(M)-27700 Painting
Technical Specification

10. For connections to earthing network see drawing NE1-10-EM-EAI-DRW-BXE(E)-40100 Typical Erection
Details Earthing Network.
D

11. The outer surface of concrete foundations in contact with soil shall be protected with bituminous
coating, according to project specifications.

12. Perimeter edges of foundations shall be chamfered (45º angle and 25mm side).
C

13. A 100 mm layer of blinding concrete shall be placed beneath all foundations.

14. The minimum allowable ground bearing pressure shall be 0.15 MPa. Plate bearing tests shall be
performed on site to comply with the requirement.
B

15. Cover Reinforcement:


11CFA03 - Underground structure 75mm.
A
- Above ground structure and foundation
in contact with Lean concrete 50mm.

16. Concrete works cannot start until all embedded elements for anemometer tower base and sun sensor
foundation are on site (by Geonica).

Abbreviations:
11CFA01 11CFA02 FGL Finish Grade Level Stakeout point

TOC Top of Concrete Fixed connection

General plan view T&B Top and Bottom


Solar field layout just for reference
Scale 1:10000
References

NE1-00-EM-EAI-DRW-YC_(C)-00100 Civil General Notes, Symbols and Materials


Table 1. Stakeout data
NE1-00-EM-EAI-TSP-YC_(C)-00450 Civilworks Technical Specification
Anemometer Sun Sensor
KKS Type Location NE1-00-EM-EAI-TSP-YC_(C)-00600 Steel Structure Technical Specification
East North TOC Footing East North TOC Column TOC Footing BOC Footing Platform level
11CFA01 496.070 2821.152 137.85 496.070 2817.152 147.35 135.65 134.85 146.15 NE1-00-EM-EAI-TSP-YM_(M)-27700 Painting Technical Specification
Weather Station PT1 South West corner
11CFA02 Anemometer PT1 South center 2718.700 2821.152 141.80 N/A N/A N/A N/A N/A N/A NE1-10-EM-EAI-DRW-BXE(E)-40100 Typical Erection Details Earthing Network

11CFA03 Anemometer PT1 South East corner 4577.900 2821.152 148.45 N/A N/A N/A N/A N/A N/A NE1-03-EM-ABE-DRW-UZA(C)-00001 Typical stairs and ladders
11CFA04 Weather Station PT1 North West corner 503.070 4945.374 139.95 503.070 4941.374 149.45 137.75 136.95 148.25
NE1-03-EM-GEO-DRW-WNY(C)-00003 SEMS Civil Works Diagram
11CFA05 Anemometer PT1 North center 2718.700 4952.374 143.90 N/A N/A N/A N/A N/A N/A
NE1-03-EM-ABE-DRW-WC_(C)-00001 Meteo Station Arrangement in SF
11CFA06 Weather Station PT1 North East corner 4577.900 4952.374 150.55 4577.900 4948.374 160.05 148.35 147.55 158.85
Geotechnical parameters:
Based on the geotechnical report, "NE1-M-EM-SEC-ABE-00004-PT1 soil investigation report-final version",
the following data has been considerated in the design:

Allowable bearing pressure: 150 kpa


Friction coefficient soil-foundation: 0.4
Soil density: 16 kN/m3

A 2020/02/12 For construction IFC JASN FCG MRF DMRG


6.00

6.00
Anemometer tower base Anemometer tower base 05 2020/01/15 Moved 11CFA04 station IFC LMC FCG MRF DMRG
Stakeout point Stakeout point 04 2019/11/26 Foundation increase by SEC requeriments IFC ADSC FCG MRF MRF
(see table 1) (see table 1)
03 2019/11/13 Client comments IFC FCG LMC MRF MRF
02 2019/10/02 Client comments IFC FCG LMC MRF MRF
01 2019/08/22 First issue IFC LEVA LGC LMC MRF
12

12


6.0 6.0
0 0 0 0 Rev. Edition Description: Issue Signature Signature Signature Signature
6.0 6.0 No.: Date: for: Drawn: Checked: Reviewed: Approved:
Client: P. Engineer (if applicable):
120° 120°
Stamp: Signature: P.Eng.No:
4.00

EPC Contractor:
Anchor ring Anchor ring

Project: EPC Subcontractor:


NE1 - 700MW CSP + 250MW PV
Sun sensor Hybrid Project ABENGOA
Stakeout point
(See table 1) Scale: PT-1 Solar Field Area Drawing No.:

Title & Subtitles:


NE1-10-EM-ABE-DRW-UWT(C)-00024
Several Structure & Foundation for Solar Field Sheets: Sheet No.:
Weather Station layout Anemometer layout Weather Stations 05 01
Anemometer & Sun sensor arrangement detail Anemometer arrangement detail Size:
Scale 1:100 Scale 1:100
General Arrangement & Layout Int. Drawing No.
A1
This drawing and the design it covers are the property of Abengoa. They have been Project/Contract number:
merely loaned by express agreement of the borrower, who states that it cannot be
reproduced, copied, loaned, exhibited or used under any circumstances. As an Document status: X For approval. For information.
exception, it can be used in a limited and private way, as long as Abengoa gives
permission to the borrower for using it through a written consent. Critical: Yes X No