Site Test Report

Contract No. – N-6166.1


New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108116127
Contractor: CSE Equipment: 7SJ611 HV SBEF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F513
Substation: 132/11 kV SS at ADNEC Page: 1 of 4

Inspection, Testing and Secondary Injection of


SBEF Protection Relay 7SJ611
A - General Data:
Ordered MLFB: 7SJ6111-5EB90-1FA0 --0S Serial no.: BF1108116127

Built-in MLFB: 7SJ6111-5EB90-1FA0 --0S Firmware version: V4.81

Built-in rated auxiliary voltage (DC): 110 -250 VDC Feeder : =E05 - Transformer T202

Built-in rated voltage VN: NA Software used: Digsi 4 V4.84

Built-in rated current IN: 1A Frequency: 50 HZ

Relay Designation : -F513 HV SBEF Protection

B - General Inspection & Testing:

S NO General inspection & testing: Checked

1 Visual inspection of unit OK

2 Installation & wiring correct to relevant drawings OK

3 Relay case connected to local earth bar OK

4 Measured value check OK

5 Relay CT shorting contacts proved OK

6 Relay Binary inputs and outputs checked OK

7 Watch dog contact checked OK

8 Injection of current from terminal block with test plug OK

C - Configuration of protection function

Functions
Enabled Disabled
IEC No. Description
Description
50N/51N Earth fault Protection Enabled

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\641616921.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108116127
Contractor: CSE Equipment: 7SJ611 HV SBEF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F513
Substation: 132/11 kV SS at ADNEC Page: 2 of 4

D - Binary input function check

Bin. input Function Terminal Terminal Drawing Checked Remarks


(+)-X332:6
Relay Page No.
(-)-X332:23
BI 1 Spare F14-F16 -X332:52 /MAB4.2
BI 2 Spare F15-F16 -X332:53 /MAB4.3
BI 3 Test Mode F17-F18 -X332:54 /MAB4.3 Test plug inserted
BI 4 Spare R9-R7 -X332:55 /MAB4.4
BI 5 Spare R10-R7 -X332:56 /MAB4.4
BI 6 Spare R11-R13 -X332:58 /MAB4.5
BI 7 Spare R12-R13 -X332:59 /MAB4.6
BI 8 Spare R8-R7 -X332:57 /MAB4.5

E - Binary output check

Output Function Terminal Drawing Checked Remarks


Relay TB Page No.
BO1 EF Trip F6-F7 X513:2 NAB1.5 Trip to TC2
BO2 EF Trip F8-F9 X513:4-8 NEB1.4 Trip to MV2
BO3 EF Trip F10-F11 X513:6 MBB1.5 Start BF protection
BO4 EF Trip F12-F13 X513:10 NAB3.7 Trip to LOR 2
BO5 EF Trip R1-R3 X513:16 RC2.4 Signal to FMS
BO6 Spare R2-R3 - ZB4.3 -
BO7 EF Trip R4-R5 - RAB3.5 Cubicle alarm
BO8 Pick-up R6-R5 - ZB4.3 For testing only
Live Cont. F3-F4-F5 - RAB3.5 Cubicle alarm

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\641616921.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108116127
Contractor: CSE Equipment: 7SJ611 HV SBEF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F513
Substation: 132/11 kV SS at ADNEC Page: 3 of 4

F - LED function

S no Led no Function Checked Remarks


1 LED 1 Trip / relay trip
2 LED 2 Pickup / relay pickup
3 LED 3 SBEF IEp Trip / 51N
4 LED 4 SBEF IE>,IE>> Trip / 50N
5 LED 5 Spare / not used
6 LED 6 Spare / not used
7 LED 7 Summary Alarm / summary alarm event

1. MEASURED VALUE TEST:

Inject current in the relay as per the table below. Observe the reading on the relay display, in secondary values and in
Primary values. Inject Current through the test switch -X513

CT RATIO: 400/1 A

Primary Current read on relay Secondary Current read on relay


Current display In (A) Display in (A)
Phase
injected
injected
(Amps)
IR IY IB IN IR IY IB IN

N 1.0 399 1.00

2.1 Earth Fault function (DMT):50N-1


Pick up
Relay setting Drop off Operating time @2
Test phase Current Time setting (Sec)
IE > (A) Current (A) Times of Iset (Sec)
(A)
E/F 0.50 * * 1.0 *

* Note: Refer attached OMICRON Print out for Test results

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\641616921.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108116127
Contractor: CSE Equipment: 7SJ611 HV SBEF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F513
Substation: 132/11 kV SS at ADNEC Page: 4 of 4

2.2 Earth Fault function (DMT):50N-2


Pick up
Relay setting Drop off Operating time @2
Test phase Current Time setting (Sec)
IE >> (A) Current (A) Times of Iset (Sec)
(A)
E/F 1.0 * * 0.50 *
* Note: Refer attached OMICRON Print out for Test results

2.3 Earth Fault function (IDMT- Normal inverse curve ): 51N 0.14
T= .TP [s]
[(I/IP)0.02 - 1]

Operating time at current setting [Sec]


Test Relay Time
P/U D/O
element setting multiplier 2*IEP 5*IEP 10*IEP
[A] [A]
IEp [A] Tp
Act Cal Act Cal Act Cal

E/F 0.20 * * 0.50 * 5.015 * 2.140 * 1.485

* Note: Refer attached OMICRON Print out for Test results

Instruments Used

Equip. 1 Equip. 2 Equip. 3


Instrument: CMC256-6

Serial No.: JG697S

Calibration Date: 30.05.2012

Remark :
- Omicron print outs will be attached along with the test report for Pickup/Drop off & Characteristics

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO