PROJECT INFORMATION

Building Analysis Data

Length of Building 12.52 m


Width of Building 12.00 m
Height of Building 10.35 m
Basic Wind Speed (V) 45.00 m/s
Topographic Location A from Section 5.4 0r Table 2 of CP 3: Chapter V Part 2
Ground Roughness 1.00 from Section 5.5.1 of CP 3: Chapter V Part 2
Cladding & Building Size Class A from Section 5.5.2 of CP 3: Chapter V Part 2
S3 - Multiplying Factor Relating to Life of Structure 1.00 from Figure 2 of CP 3: Chapter V Part 2
Cf 0.95 Force Coefficient from Table 10

Calculate and View Result

Table 2 or Section 5.4

Table 3

Section 5.5.1

Section 5.5.2

Tabe 10 force coefficient


of CP 3: Chapter V Part 2
Chapter V Part 2
Chapter V Part 2
WIND LOAD CALCULATION
Wind Analysis Data for CP3 Chapter V Part 2

Length of Building 12.5200 m


Width of Building 12.000 m
Height of Building 10.350 m
Basic Wind Speed (V) 45.00 m/s
Topographic Location A from Section 5.4 0r Table 2 of CP 3: Chapter V Part 2
Ground Roughness 1.00 from Section 5.5.1 of CP 3: Chapter V Part 2
Cladding & Building Size Class A from Section 5.5.2 of CP 3: Chapter V Part 2

Wind Pressure Calculation


Wk = 0.613 • Vs2 Characteristic Wind Pressure (N/m 2 )
Vs = V • S1 • S2 • S3 Design Wind Speed (m/s)
( from Section 4.3 of CP 3: Chapter V Part 2 )
S1 = 1.00 Multiplying Factor Relating to topology
( from Table 2 of CP 3: Chapter V Part 2 )
S2 = 1.03 Multiplying Factor Relating to Height above Ground & Wind Breaking
( from Table 3 of CP 3: Chapter V Part 2 )
S3 = 1.00 Multiplying Factor Relating to Life of Structure
( from Figure 2 of CP 3: Chapter V Part 2 )
Vs = 46.35 m/s
Wk = 1316.922 N/m2
Wk = 1.317 kN/m2

Wind Load Calculation


Cf = 0.950 Force Coefficient

Cf • Wk = 1.251 kN/m2

Design Wind Pressure Cf.Wk


Cf.Wk = 1.251 kN/m 2
WIND LOAD CALCULATION
Design Wind Pressure Cf.Wk
Cf.Wk = 1.251 kN/m 2

DIRECTION 1 +
Height Width Area Force Total Force Location
LOWER 0.2 12.52 2.504 3.133
STOREY 1 28.977 6.260 4
UPPER 1.65 12.52 20.658 25.845
LOWER 1.65 12.52 20.658 25.845
STOREY 2 43.420 5.449 3
UPPER 1.65 8.514 14.0481 17.575
LOWER 1.65 8.514 14.0481 17.575 2
STOREY 3 31.368 4.001
UPPER 1.5 7.35 11.025 13.793
LOWER 1.5 7.35 11.025 13.793 1
STOREY 4 16.092 3.675
UPPER 0.25 7.35 1.8375 2.299

DIRECTION 1 -
Height Width Area Force Total Force Location
LOWER 0.2 12.52 2.504 3.133
STOREY 1 28.977 6.260
UPPER 1.65 12.52 20.658 25.845 4
LOWER 1.65 12.52 20.658 25.845
STOREY 2 43.420 5.449
UPPER 1.65 8.514 14.0481 17.575 3
LOWER 1.65 8.514 14.0481 17.575
STOREY 3 31.368 4.001
UPPER 1.5 7.35 11.025 13.793 2
LOWER 1.5 7.35 11.025 13.793
STOREY 4 16.092 3.675 1
UPPER 0.25 7.35 1.8375 2.299

DIRECTION 2 +
Height Width Area Force Total Force Location
LOWER 0.2 12 2.4 3.003
STOREY 1 27.774 6.000
UPPER 1.65 12 19.8 24.771 4
LOWER 1.65 12 19.8 24.771
STOREY 2 49.543 6.000
UPPER 1.65 12 19.8 24.771 3
LOWER 1.65 12 19.8 24.771
STOREY 3 36.031 5.063 2
UPPER 1.5 6 9 11.260

STOREY 4
LOWER 1.5 6 9 11.260
13.136 3.000 1
UPPER 0.25 6 1.5 1.877

DIRECTION 2 -
Height Width Area Force Total Force Location
LOWER 0.2 12 2.4 3.003
STOREY 1 27.774 6.000
UPPER 1.65 12 19.8 24.771 4
LOWER 1.65 12 19.8 24.771
STOREY 2 49.543 6.000 3
UPPER 1.65 12 19.8 24.771
LOWER 1.65 12 19.8 24.771
STOREY 3 36.031 5.063 2
UPPER 1.5 6 9 11.260

STOREY 4
LOWER 1.5 6 9 11.260
13.136 3.000 1
UPPER 0.25 6 1.5 1.877

1&2 3 4
= + +
WIND LOAD CALCULATION
Wind Analysis Data for CP3 Chapter V Part 2

OPTION 1: CONCENTRATED LOAD ON BEAM-COLUMN JOINT

0.50 0.40
Dir1 Dir2

A or B A or B

2.125
4.563 m2 3.269 m2
1.258 m2 0.958 m2
5.821 m2 4.227 m2
A B

2.45
cf.wk x Area(A) cf.wk x Area(A)
7.300 kN 5.300 kN

1.375
C or D C or D
3.637 m2 2.606 m2 C D
0.000 m2 0.000 m2

0.15
3.637 m2 2.606 m2

4.600 kN 3.300 kN

OPTION 2: UNIFORMLY DISTRIBUTED LOAD ON COLUMN

0.50 0.40
Dir1 Dir2

A or B (Parapet) A or B (Parapet)
1.258 m2 0.958 m2

cf.wk x Area(A) cf.wk x Area(A)


1.600 kN 1.200 kN
A B

2.45
A or B A or B
2.645 m 1.895 m

cf.wk x width(A) cf.wk x width(A)


3.400 kN/m 2.400 kN/m

0.15

OPTION 3: CONCENTRATED LOAD ON THE CENTER OF BUILDING WIDTH PER FLOOR


0.50 0.40

Dir1 Dir2

A A
2.125

9.125 m2 6.538 m2
2.516 m2 1.916 m2
11.641 m2 8.454 m2 A
2.45

cf.wk x Area(A) cf.wk x Area(A)


14.600 kN 10.600 kN
1.375

B B
7.274 m2 5.211 m2 B
0.000 m2 0.000 m2
0.15

7.274 m2 5.211 m2

cf.wk x Area(A) cf.wk x Area(A)


9.200 kN 6.600 kN
Topography Factor
Topography Value of S1
a 1
b 1.1
c 0.9

Topographic Location
a All cases except those in b and c
b Very exposed hill slopes and crests where
acceleration of the wind is known to occur
c steep sided, enclosed valleys sheltered fromm all winds

GO TO DATA INPUTS
(2) Open Country with (3) Country with many windbreaks; (4) Surface with large and frequent
(1) Open Country with No Obstructions
Scattered Windbreaks Small towns; outskirts of large cities obstructions, e.g. city centes
Height A B C Height A B C Height A B C Height A B C

1 0.83 0.78 0.73 1 0.72 0.67 0.63 1 0.64 0.6 0.55 1 0.56 0.52 0.47
2 0.83 0.78 0.73 2 0.72 0.67 0.63 2 0.64 0.6 0.55 2 0.56 0.52 0.47
3 0.83 0.78 0.73 3 0.72 0.67 0.63 3 0.64 0.6 0.55 3 0.56 0.52 0.47
5 0.88 0.83 0.78 5 0.79 0.74 0.7 5 0.7 0.65 0.6 5 0.6 0.55 0.5
10 1 0.95 0.9 10 0.93 0.88 0.83 10 0.78 0.74 0.69 10 0.67 0.62 0.58
15 1.03 0.99 0.94 15 1 0.95 0.91 15 0.88 0.83 0.78 15 0.74 0.69 0.64
20 1.06 1.01 0.96 20 1.03 0.98 0.94 20 0.95 0.9 0.85 20 0.79 0.75 0.7
30 1.09 1.05 1 30 1.07 1.03 0.98 30 1.01 0.97 0.92 30 0.9 0.85 0.79
40 1.12 1.08 1.03 40 1.1 1.06 1.01 40 1.05 1.01 0.96 40 0.97 0.93 0.89
50 1.14 1.1 1.06 50 1.12 1.08 1.04 50 1.08 1.04 1 50 1.02 0.98 0.94
60 1.15 1.12 1.08 60 1.14 1.1 1.06 60 1.1 1.06 1.02 60 1.05 1.02 0.98
80 1.18 1.15 1.11 80 1.17 1.13 1.09 80 1.13 1.1 1.06 80 1.1 1.07 1.03
100 1.2 1.17 1.13 100 1.19 1.16 1.12 100 1.16 1.12 1.09 100 1.13 1.1 1.07
120 1.22 1.19 1.15 120 1.21 1.18 1.14 120 1.18 1.15 1.11 120 1.15 1.13 1.1
140 1.24 1.2 1.17 140 1.22 1.19 1.16 140 1.2 1.17 1.13 140 1.17 1.15 1.12
160 1.25 1.22 1.19 160 1.24 1.21 1,18 160 1.21 1.18 1.15 160 1.19 1.17 1.14
180 1.26 1.23 1.2 180 1.25 1.22 1.19 180 1.23 1.2 1.17 180 1.2 1.19 1.16
200 1.27 1.24 1.21 200 1.26 1.24 1.21 200 1.24 1.21 1.18 200 1.22 1.21 1.18

Ground Roughness
Height of Building = 10.35 1 1.03
Height of Building = 15 2 1
GO TO DATA INPUTS
Cladding & Building Size Class = A 3 0.88
Ground Roughness = 1.00 4 0.74

s2 = 1.03
GROUND ROUGHNESS CATEGORY

Ground Roughness 1 Long fetches of open, level or nearly level country with no shelter.
Examples are flat coastal fringes, fens, airfields and grasslands,
moorland or farmland without hedges or walls around the fields.

Ground Roughness 2 Flat or undulating country with obstructions such as hedges or walls
around fields, scattered windbreaks of tress and occasional buildings.
Examples are most farmland and country estates with the exception
of those parts that are well wooded.

Ground Roughness 3 Surfaces covered by numerous large obstructions.


Examples are well-wooded parkland and forest areas, towns and their
shrubs, and their suburbs, and the outskirts of large cities. The general
level of rooftops and obstructions is assumed at about 10m, but the
category will include built-up areas generaaly apart from those that
qualify for category 4.

Ground Roughness 4 Surfaces covered by numerous large obstructions with a general


roof height of about 25 m, or more. This category covers onty the
centres of large towns and cities where the buildings are not only
high, but are also bot too widely spaced,

GO TO DATA INPUTS
CLADDING AND BUILDING SIZE CATEGORY

CLASS A All units of cladding, glazing and roofing and their immediate
fixings and individual members of unclad structures

CLASS B All buildings and structures where neither the greatest horizontal
dimension nor the greatest vertical dimension exceeds 50 m (165ft).

CLASS C All buildings and structures whose greatest horizontal dimension


and greatest vertical dimension exceeds 50 m (165ft).

GO TO DATA INPUTS
h/b HEIGHT OVER BREADTH RATIO
L/W b/d cf FORCE COEFFICIENT
0.5 1 2 4 6 10 20
>4 1.2 1.3 1.4 1.5 1.6 1.6 1.6
4
<1/4 0.7 0.7 0.75 0.75 0.75 0.75 0.75
3 1.1 1.2 1.25 1.35 1.4 1.4 1.4
3
1/3 0.7 0.75 0.75 0.75 0.8 0.8 0.8
2 1 1.05 1.1 1.15 1.2 1.2 1.2
2
1/2 0.75 0.75 0.8 0.85 0.9 0.9 0.9
1.5 0.95 1 1.05 1.1 1.15 1.15 1.15
1.5
2/3 0.8 0.85 0.9 0.95 1 1 1
1 1 0.9 0.95 1 1.05 1.1 1.2 1.4

cf = 0.95

GO TO DATA INPUTS
PROJECT INFORMATION

Building Analysis Data

Length of Building 12.52 m


Width of Building 12.00 m
Height of Building 10.35 m
Basic Wind Speed (V) 45.00 m/s
Topographic Location A from Section 5.4 0r Table 2 of CP 3: Chapter V Part 2
Ground Roughness 1.00 from Section 5.5.1 of CP 3: Chapter V Part 2
Cladding & Building Size Class A from Section 5.5.2 of CP 3: Chapter V Part 2
S3 - Multiplying Factor Relating to Life of Structure 1.00 from Figure 2 of CP 3: Chapter V Part 2
Cf 0.95 Force Coefficient from Table 10

Calculate and View Result

Table 2 or Section 5.4

Table 3

Section 5.5.1

Section 5.5.2

Table 10 force coefficient