Ref No: CRBC/LM/174/ 14 Date: July 16, 2014
We hereby inform you that, we have jointly with your material inspector taken
the aggregate from CRBC’s Bole Airport Quarry and nature sand, crushed
sand from CRBC’s Kality Batching Plant, and we have tried mix design for C-
35 concrete, we used Mugher cement for concrete mix design, after we
compared the try mix workability and test results. We want to choose as
follows:
Concrete Mix Cement Cement Water Agg. Sand P2 7 14 28
Class No. Type per/m3 (kg) (kg) (kg) (kg) days days days
C-35 Type Mugher 430 184 1002 732 4.3 33 41.8 45.0
1 MPa MPa MPa
So for C-35, we can use Type 1 try mix, which cement used 430kg/m3
with 1.0% P2 admixture.
Now we attached the proportion and 28-days test results with this letter.
Please check and give us approval.
Thanking you in advance for your cooperation, we remain.
Sincerely yours,
Wang yang
General Manage