LV GENSET & ATS CONTROLLER DSE8620


( Modify Submission ) Option B

ALLRIGHTSRESERVEDFORALLCOUNTRIES

SIZE DATE DRAWN UP CHECKED APPROVED STATUS

A4 SCA

CHRONOLOGICAL
PROJECT NUMBER ISSUER DISCIPLINE PROCESS DOC TYPE
NUMBER
VERSION REVISION

A19-0444-01 SUEZ PR 000 PH xxx A


DESIGN AND BUILD OF CALAWIS
WATER TREATMENT PLANT PROJECT Project N°: A19-0444-01

(CALAWIS WTP)

Doc N°: SUEZ-PR-000-PH-0001


LV GENSET & ATS CONTROLLER
DSE8620 ( Modify Submission ) for Rev.: B Doc Status: RFR
Option B Page 2 / 9 Date: 30/May/2023

Rev. Date Aim of revision Drawn up by Checked by Approved by


DESIGN AND BUILD OF CALAWIS
WATER TREATMENT PLANT PROJECT Project N°: A19-0444-01

(CALAWIS WTP)

Doc N°: SUEZ-PR-000-PH-0001


LV GENSET & ATS CONTROLLER
DSE8620 ( Modify Submission ) for Rev.: B Doc Status: RFR
Option B Page 3 / 9 Date: 30/May/2023

1. Requirement
- Keep the existing controller of Genset and MCC200
o DSE7410 control for Genset
o DSE8620 control incomer breakers & synchronize progress.
- Hard wire signal (DI/DO) require to coordinate DSE8620 & DSE7410
o Remote Start Genset
o Genset Ready Auto
o Generator Trip
o ATS Successful
o Fail To Transfer
o Sync Ok & Ready for Coupling
- Hard wire signal (DI/DO) require DSE8620 send to SCADA
o Fail To Transfer
- DSE8620 sends the signal to DSE7410 to start/stop Genset and sends the signal to control Incomer Breakers in MCC200.
- DSE8620 take to control Governor Controller and AVR controller to adjustable speed, voltage, and angle. ( Make sure Genset
supplier agrees with this proposal).
- Preparation to lay 1 cable at least 12 cores from MCC200 to Genset Control panel.
- Preparation to lay 3 cables 2 cores with shield from MCC200 to Governor, AVR Controller, and 1 for spare. (the case Genset
supplier agrees to DSE8620 control Governor and AVR)
- MCC200 additional 2 relays 24VDC (1KB9, 1KB10) for sends signal to DSE7410.
- Genset Panel additional 2 relays 24VDC (K5, K6) for sends signal to DSE8620.
- Modify DSE7410 program ( it should be managed by Genset supplier)
- Modify DSE8620 program follow Control Philosophy.
- Preparation to lay 1 cable 2 cores from MCC200 to CP200 ( fail to transfer sinal to SCADA) (check if the cable available, no
need to laying new)
DESIGN AND BUILD OF CALAWIS
WATER TREATMENT PLANT PROJECT Project N°: A19-0444-01

(CALAWIS WTP)

Doc N°: SUEZ-PR-000-PH-0001


LV GENSET & ATS CONTROLLER
DSE8620 ( Modify Submission ) for Rev.: B Doc Status: RFR
Option B Page 4 / 9 Date: 30/May/2023

2. Architecture
DESIGN AND BUILD OF CALAWIS
WATER TREATMENT PLANT PROJECT Project N°: A19-0444-01

(CALAWIS WTP)

Doc N°: SUEZ-PR-000-PH-0001


LV GENSET & ATS CONTROLLER
DSE8620 ( Modify Submission ) for Rev.: B Doc Status: RFR
Option B Page 5 / 9 Date: 30/May/2023

3. MCC200 - DSE8620 modify drawing


- Additional 2 relays 24VDC (1KB9, 1KB10) for sends the signal to DSE7410.
- GEN100-XA1 ( DI/DO cable 12 cores , using 9 5 cores)
- GEN100-XA2 (cable 2 cores with shield) for Governor.
- GEN100-XA3 (cable 2 cores with shield) for AVR.
- GEN100-XA4 (cable 2 cores with shield) for spare.
- Connect 1 sinal “fail to transfer” from 1KB8 to input %I32.6 to PLC200 (check if the cable available, no need to laying new)
DESIGN AND BUILD OF CALAWIS
WATER TREATMENT PLANT PROJECT Project N°: A19-0444-01

(CALAWIS WTP)

Doc N°: SUEZ-PR-000-PH-0001


LV GENSET & ATS CONTROLLER
DSE8620 ( Modify Submission ) for Rev.: B Doc Status: RFR
Option B Page 6 / 9 Date: 30/May/2023

4. CP200 modify drawing


- Additional 1 input sinal “ ATS200 fail to transfer” from DSE8620
DESIGN AND BUILD OF CALAWIS
WATER TREATMENT PLANT PROJECT Project N°: A19-0444-01

(CALAWIS WTP)

Doc N°: SUEZ-PR-000-PH-0001


LV GENSET & ATS CONTROLLER
DSE8620 ( Modify Submission ) for Rev.: B Doc Status: RFR
Option B Page 7 / 9 Date: 30/May/2023

5. Genset Panel modify drawing


- Additional 2 relays 24VDC (K5, K6) for sends the signal to DSE8620.
DESIGN AND BUILD OF CALAWIS
WATER TREATMENT PLANT PROJECT Project N°: A19-0444-01

(CALAWIS WTP)

Doc N°: SUEZ-PR-000-PH-0001


LV GENSET & ATS CONTROLLER
DSE8620 ( Modify Submission ) for Rev.: B Doc Status: RFR
Option B Page 8 / 9 Date: 30/May/2023
DESIGN AND BUILD OF CALAWIS
WATER TREATMENT PLANT PROJECT Project N°: A19-0444-01

(CALAWIS WTP)

Doc N°: SUEZ-PR-000-PH-0001


LV GENSET & ATS CONTROLLER
DSE8620 ( Modify Submission ) for Rev.: B Doc Status: RFR
Option B Page 9 / 9 Date: 30/May/2023

6. TOHO Govervor Controller modification


- Remove control from DSE7410 and replace control by DSE8620 (It shoud be agreed by Genset Supplier)