Professional Documents
Culture Documents
Substation Interview Questions
Substation Interview Questions
Answer: Hybrid substation is a combination of both conventional air insulated substation (AIS) and Gas Insulated Substation
(GIS). Some of the bays in the substation are gas insulated (enclosed in modules filled with SF6 gas) and some of the bays
are air insulated type (open to atmosphere). The design of hybrid substation is based on the convenience, local conditions,
availability of the area and cost
Answer: In electrical substation in order to limit the step potential and touch potential to sufficiently safe values and to control
the influence of the short circuit currents on telecommunication installations. A Strong earthing network is provided. This is
provided to effectively earth the systems with high earth fault currents
Answer: Current transformers in substations are generally used for reducing or stepping down a.c currents from higher value
to lower value for the purpose of measuring, protection and control purposes. There are two classes of current transformers.
They are used for measuring purposes.They are used with ammeters, watt meters, KVA meters and kWh meters for
reducing line current to 1 ampere or 5 amperes
They are used with over-current protection, earth fault protection, differential protection, impedance protection
Answer: Power frequency spark-over voltage is the r.m.s value of the power frequency (50Hz or 60Hz) voltage applied
between the line and earth terminals of the arrester and earth which causes spark-over of the series gap
Answer: Follow current is the current which flows from the connected power source through lightning arrester following the
passage of discharge currents
Which is the basic busbar scheme employed in 220kV and 400kV substations?
Answer: In case of 220kV and 400kV substations double main busbar scheme or one-and-half breaker schemes are
generally employed
Isolators are disconnecting switches which are used for disconnecting of the circuit under no load conditions. Isolators are
placed in the substation such a way that any part of the circuit can be isolated from the live parts for maintenance purposes.
Isolators plays an important role during maintenance of the substation. Isolators should be always operated under no load
condition. Isolators should be open after opening the circuit breaker and closed before closing the circuit breaker contacts.
Earth Switches in substation are employed to connect the conductors to the earth thereby discharging any charging currents
due to capacitance. Earth switches are employed for the protection of operating personnel. Earth switches are operated
along with isolators. When isolators opens, earth switches immediately connects the conducting parts to ground
What are the different substation components
Answer: Circuit Breakers, Disconnecting switches, Grounding switches, Current Transformers,
Potential Transformers or Capacitor voltage Transformers, Line Traps, Lightning Arrestors,
Power Transformers, Shunt Reactors, Current limiting reactors, Station Buses and Insulators,
Grounding system, Series capacitors and shunt capacitors.
What are different types of busbar arrangement Schemes in Substations?
Answer: Different switching schemes or busbar arrangement scheme employed in switch-yard
are:
Single Bus Scheme
Double bus single breaker scheme
Main and Transfer busbar scheme
Double bus single breaker scheme
Breaker and half scheme
Ring main bus scheme
Which type of bus arrangement is costlier and more reliable?
Answer: One and half breaker scheme is most reliable and costlier scheme. In one and half
breaker scheme 3 circuit breakers are provided for 2 bus-bars. Hence the name is coined as
One and half breaker scheme
Step potential : It is the potential developed between the two feet on the ground of a man or
animal when short circuit occurs. This results in flow of current in the body leads to electrical
shock
Touch potential: It is the potential that is developed between the ground and the body of the
equipment when a person touches the body during fault condition. When operating personnel
touch an electrical equipment during short circuit condition, fault current flows through the
human body. This is defined as touch potential.
Gravel/Stones in the substation is provided to reduce the step potential and touch
potential when operators work on switch yard.
2. Power Transformers installed in the substations will have oil as cooling and insulating
medium. Oil leakage takes place during operation or when changing the oil in the
transformer. This oil spillage which can catch fire is dangerous to the switchyard
operation. So Stones/Gravel is provided to protect from fire when oil spillage takes
place.
3. Stones eliminate the growth of small weeds and plants inside the switch yard
4. Improves yard working condition
5. Provides protection from wild life and snakes.
Step potential and touch potentials are of concern during normal conditions and during ground
fault.Under normal conditions, unbalanced currents can rise the neutral to earth voltage. This is
not normally dangerous but it can cause shocks.
Step potential and Touch potentials during faults are more dangerous. Therefore it is important
to reduce the step potential and touch potential to be within limits during the substation design.
Step potentials and touch potentials can be reduced by employing one of the following methods:
Moisture content:
Moisture content in the soil is one of the major factors that determine the soil resistivity. The
dryer the soil the more is the resistivity of the soil, wet soil will have low soil resistivity. Change
in the moisture level of the soil through out the year during different seasons is the biggest
reason for change in the ground electrode resistance. With increase in the moisture content in
the soil, ground resistance or soil resistance decreases and about after 22% of moisture content
there will be very little change in the soil resistivity
Temperature:
Above the freezing point of the water, temperature does not impact the soil resistivity
significantly but the temperature below the freezing point of the water soil resistivity rises and
will have significant impact
Salts in Soil:
The presence of soluble salts in the soil will significantly impact the resistivity of the soil. One of
the option to reduce the electrode resistivity is by chemical treatment of soil near the electrode.
Bentonite backfilles or salt treatment such as sodium chloride or calcium chloride can
significantly reduce the soil resistivity. The only disadvantage is some chemicals enhance the
metal corrosion rate which can damage the grounding rod to corrode.
If the grounding rod sustains significant current, the current flowing through the grounding rod
may dry out the surrounding soil and that can increase the resistance of the electrode. When
high currents flowing through the grounding rod or earthing electrode, this may be due to
lightning or from faults the soil surrounding the electrode breaks resulting in the increase in the
resistance
The creepage distance for insulators is the shortest distance along the insulator surface
between the metal parts at each end of the insulator. Creepage distance can also be refer
as leakage distance for insulators.
Insulators in substation are provided to avoid any leakage current from live electrical conductors
to flow to the earth through supports. The atmospheric dust sticks to the insulator surface
forming a conducting layer. The leakage current flows from the live conductor to the earth
through such surface layers. The leakage properties (creepage properties) of an insulator s in
substation are characterized by the length of the leakage path. While designing the insulator
sheds, the leakage distance for insulators requirement should be satisfied. The requirement of
the leakage distance or creepage distance for insulators depends on the
Moderately
2 20 mm/kV
polluted areas
Heavily polluted
4 25 mm/kV
areas
Shunt capacitors and series capacitors in the power system generate the reactive power
to improve the power factor and voltage, thereby enhancing the power system capacity and
reducing the losses. In series capacitors reactive power generation is proportional to the square
of the load current (I2Xc), whereas in shunt capacitors reactive power generation is proportional
to the square of the voltage (V2/Xc).
The cost of installation of series capacitors is higher than that of the shunt capacitors.
This is because the protective equipment for the series capacitors is often complicated. In
addition to that, series capacitors are generally designed for higher power to cope up with the
future increase in the load
For the same voltage improvement, the rating of the shunt capacitors will be higher than
that of series capacitors. Series capacitors compensation may create certain disturbances:
ferro-resonance in transformers, sub-synchronous resonance during motor starting, shunting of
motors during normal operation and difficulty in protection of capacitors from system faults.
Series capacitors are more effective on distribution circuits with higher X/R ratio and for
load variations involving a higher reactive content.
Series capacitors are generally employed to improve the stability of the system and
shunt capacitors are generally employed to improve the power factor of the system
Some of the factors which influence the choice between the shunt and series capacitors are
tabulated below:
Series Shunt
Objective
Capacitors Capacitors
Reduce Voltage
Primary Not used
Fluctuations
Corona Ring:
This Metal Ring what we see in the substations and other transmission line network is "Corona Ring". At higher
voltages such as in EHV transmission networks corona discharge effect is prominent. Corona Ring distributes the
electrical potential gradient evenly and maintains the maximum value below the threshold limits of the corona effect.
Corona Rings are employed at high altitude electrical equipment where density of the air is less.
The main advantage of this Gas Insulated Substation is because of its compact size
due to high dielectric strength of the SF6 gas. And the availability and reliability of the
GIS substations are more compared to air insulated substations
(Faults occurring chances of Air insulated substation or conventional substations are
more. Hence GIS substations are provided where high reliability of electric power is
required such as nuclear plants and and other important facilities where un interruption
of power is more required.
Some of the places where Gas insulated substations are preferred are:
Large towns where space available is limited
Industrial complexes where un interruption of power is necessarily
Mountain regions and valleys
Underground substations
Off-shore (On sea or lake) substations
HVDC transmission system terminal substations
In large cities area for commissioning an ordinary Air insulated substation is difficult because of the lack of space
available. In such conditions GIS substations out rule the ordinary substation. However it is to be considered that GIS
substation requires high capital cost compared to ordinary substation.
Off shore and highly polluted areas where equipment present in the outdoor will be corroded due to the pollution and
saline environment. Under such case indoor GIS substation is very much helpful.
Pin insulators
Post insulators
Strain insulators
Suspension insulators
Hallow apparatus insulators
Dead-end insulators
Solid core insulators
What is creepage distance?
Answer: Creepage distance is the shortest distance between two conducting points along the
surface of the insulating material.
Answer: Basic Impulse Level (BIL) refer to the peak value of lightning impuse voltage withstand
capability of the equipment
It is necessary to earth a power system at a suitable point by a suitable method as it offers many advantages as
When the neutral of the power transformer and generator is directly connected to the earth, then the system is said to be
solidly earthed. The solidly earthing does not make a zero impedance circuit as generator or transformer would have its own
reactance in series with the neutral circuit. The direct earthing of a generator without external impedance causes earth fault
current from the generator to exceed the maximum 3-phase fault current if the impedance of the generator is too low. This
results in Stator winding damage as the short circuit current during fault will exceed the short circuit rating of the winding for
which it was designed. For this system of earthing, it is necessary that the earth fault current shall be in the range of 25% to
100% of the 3-phase fault current to prevent the development of high transit over voltages.
Resistance Earthing
In resistance earthing the neutral of the generator or transformer is connected to the earth trough a resistance in series.
1. It reduces the line voltage drop caused when earth fault occurs
2. It reduces electric shock hazards to the persons, caused by stray earth fault currents in the return path
The magnitude of the resistance to be used should be such that it should limit the earth fault current to a value which will
reduce minimum damage at the point of the fault.
Type Of Earth Resistance Methods
Reactance Earthing:
In reactance earthing a reactor is connected in between the neutral of the machine and earth. A low reactance is connected
in series with the neutral of the machine to limit the earth fault current through the generator. This current should not be
greater than the 3-phase fault current of the generator. The earth fault current of the earthed system should not be less than
25% of the 3-phase fault current in order to minimize the transient voltages
The Non linear lightning arrester basically consists of set of spark gaps in series with
the silicon carbide non linear resistor elements. Lightning arresters are connected
between the phase conductors and ground. During normal system operating voltage
conditions, the spark gaps are non conducting and isolate the high tension (HT)
conductors from the ground. However whenever an overvoltge of magnitude dangerous
to the insulation of the apparatus protected occurs ( these over voltages or over surges
may be caused due to lightning strikes on the conductors or due to Extra High Voltage
(EHV) switching) the spark gap breaks down and allows the high voltage surge current
to flow through the ground.
When the transformer is switched in, if the system voltage and transformer core magnetization
are not in synch, a magnetic transient may occurs. This transient may drive the core into
saturation and drives a large amount current into the transformer causing transformer core to
damage
A transformer that is designed to operate lower on the saturation curve draws less inrush
currents as there is more margin between the saturation point and the normal operating. The
extra flux during switching is less likely to push the core into saturation
Large transformers draw more inrush current. Large transformers will have smaller
saturation impedance
Higher source impedance relative to the transformer size limits the currents that the
transformer can pull from the system
the point where the circuit breaker close (position of flux wave in sine wave). The
worst case will be when the flux is at maximum (peak) and voltage is minimum (in
transformer the applied voltage lag behinds the flux by 90 deg).
Other factors have little significance. The load on the transformer does not significantly
change the inrush currents. While switching transients cause high inrush, other voltage
transients especially voltage transients with dc components can saturate the core of the
transformer and cause inrush currents
When the nearby fault was cleared and transformer voltage is recovering from
the voltage sag, the sudden rise in voltage can drive the transformer to saturation
Energizing a transformer can cause the nearby transformer to also draw inrush
currents. The inrush currents into the switched transformer has a significant dc
component that can cause the voltage drop. The dc component can push the other
transformer into saturation and draws inrush
A lightning flash near the transformer can drive the transformer core to saturation
Generally in power system mostly two winding transformers are employed. But three winding
transformers are employed because of some advantages:
The most common reason for having a three winding transformer is to provide a delta
connection tertiary winding
To limit the fault level on the low voltage system of the transformer by dividing the LV
infeed (in order to provide double secondary windings)
Providing tertiary winding helps to interconnect different power system operating at
different voltages (Three winding transformer helps provide power supply at two different
secondary voltages, 220kV/11kV/6.6kV transformer can able to provide power at two different
voltage levels (11kV and 6.6kV)
To regulate the voltage and reactive power of the system by providing synchronous
capacitor connected to one of the terminals of the transformer
Why Delta winding prefer:
It is always desirable to have one delta connection winding in the three phase transformer as
delta connected three phase winding will offer low impedance path for the three phase currents.
Also the presence of delta connected three phase winding allows to circulate the current around
the delta winding in the event of unbalance loading condition
Although power system designers aims to avoid use of star/star transformer in power system
but cases will arise when the phase shift between the star/delta and delta/star is not applicable
such as in the power station supplying power to auxiliary system. Therefore it is common
practice to have a star/star with delta tertiary three winding transformer supplying power to the
plant auxiliary system
B/H Curve of the magnetic material (core of the transformer) is not linear. Is a sinusoidal voltage
(flux) is applied across the primary winding, the magnetizing current obtained will not be
sinusoidal in nature and consists of fundamental component and several harmonics. Third
harmonic components predominate with several other higher harmonic components. If there is
no delta connected winding, or if the star connections of the transformers are not grounded, the
line to earth capacitance currents supply system lines supply the harmonic components. If the
harmonic components cannot flow in any one of these paths then, secondary voltage will be
distorted.
Noise In Transformer:
The basic cause for the noise in the transformer is due to magnetostriction of the
sheets in the magnetic circuit (core of the transformer). Variations in the magnetic
induction subjected to the sheets to periodic variations in the length, the amplitude
which is in the order of microns per meter length.
The fundamental frequency with which these vibrations occur is double that of
the system frequency, (for 60Hz frequency vibration frequency will be of the order of
120Hz) and also constitute numerous harmonics. Also various parts of the transformer,
starting with the magnetic circuit (core) are liable to vibrate due to magnetostricition
effect.
The noise generated due to magnetostricition effect transmitted from the
magnetic circuit to the tank of the transformer either through direct conduction to
supporting points or through the oil and insulating material used in transformer. The
transformer tank and the radiator radiate the acoustic noise or energy in to the ambient
atmosphere
Another source is due to the vibration of magnetic sheets perpendicular to the
surface either at the edge or at the core packets, or at the joints between the leg and
the yoke
The current carrying windings is also a source of noise, however the amplitude of
the noise is very less and is not detectable.
Cooling fans and pumps employed for cooling the transformer is also acts as
source of noise
Methods to reduce Transformer noise:
The main source of noise in the transformer is due to magnetostriction effect of
the magnetic circuit or core. In order to reduce the noise cold rolled grain-oriented plant,
with low magnetostriction and improved flatness is employed
Ensuring uniform flux distribution and reduction in the cross flux also reduces the
noise
Elimination of the clamp bolt holes, use of resin impregnated glass-fibre bands
instead of core bolts, gluing of core packets can reduce the noise
These above specified remedial methods not only reduces the noise level by 5 to 10 dB,
but also reduces the losses and no-load current
Faults in Transformers:
Some of the faults in the transformers are likely to be over-voltages which
resulting from the atmospheric phenomenon (lightning) transmitted by overhead lines.
Switching in the power system (especially high voltage switching more than
400kV) can produce over-voltages of less steep but longer duration surges stressing
both liquid and solid dielectrics (insulation). These over-voltages should be restricted in
amplitude to a value below the transformer insulation breakdown withstanding level.
Short circuits in the power system subject the transformer to currents of 10 to 20
times the rated currents (short circuit current level will be severe when fault occur close
to transformer). Power transformer is generally designed to withstand tens of short
circuits, lasting not more than 2 sec duration in its life time. If there are more short
circuits than the designed limit special construction is required. Short circuits should
eliminated (by isolating faulty power system by opening circuit breakers) as quickly as
possible to limit the short circuit intensity on transformer.
Ferroresonance:
Ferroresonance phenomenon can be triggered off through interaction of the system capacitance
with a non-linear inductance, when transformer is at no-load. This oscillatory phenomenon or
resonance phenomenon result in over-voltages which can damage the cable and the power
transformer. Series ferroresonance is dangerous to power transformer
Auto-transformer Advantages:
Auto-transformers in comparison with the double winding transformers are generally
advantageous of the voltage ratio is favorable from the point of view of the equivalent size
The reduction in the equivalent power in relation to the throughput, reduction in the
weight and size, reduction in the no load (iron losses) and on load losses (cooper losses), the
reduction in the no load current and the short circuit impedance
If P is the power of the transformer, linear dimensions of the auto transformer vary as
P0.25and the weight and volume vary as P0.75 thus reducing the losses and weight of the
transformer
The short circuit impedance of the auto-transformer goes down with equivalent rating
which is advantageous because of the lower voltage drop and better regulation.
For connections between the two systems at very high voltage, where the power is to be
transmitted in the order of GVA (Giga Volt-amperes), the use of auto transformer make it
possible for high power equipment and can be easily transportable. This will not be possible
with normal transformers
Auto-transformer Disadvantages:
An electrical connection between the primary and secondary is not always desirable,
particularly when the voltages levels on both the sides of transformer are quite different. If the
neutral point is not solidly earthed, the lower voltage side can be subjected to high potential in
the event of earth fault on high voltage side. In general practice, auto transformers are only
used on distribution systems where the neutral is connected to the earth
Auto-transformers are particularly sensitive to the atmospheric over-voltages. Therefore
the auto-transformer requires much highs standard of insulation compared to normal
transformer. Surge Arrester protection is required
As the short circuit impendace values of the auto-transformer are low, short circuit
currents can reach higher critical values.
Sources of Harmonics:
Several sources of harmonic currents that may be found on electrical power distribution
networks are listed below:
Dry type transformers are most suitable in locations where conventional oil filled transformers present a safety
hazard. Some of the locations where dry type transformers are best suited are: Oil refineries, Chemical plants, Marine
applications, Metro railways where there is significant safety is required against fire.
Why Isolation switches are provided along with the circuit breakers?
Answer: Isolation switches are provided for separating the disconnected element from
the live portion of the system for the purpose of safety.
For an Resistive Load and Inductive load considered for switching operation of
circuit breaker, Switching of which load is difficult and Why?
Answer: In case of switching resistive load, current and voltage will be in phase i.e,when
during current zero voltage also will be zero in case of resistive load. Hence the voltage
at the breaker terminals during arc extinction is zero or minimal. On the other hand, for
switching inductive load during current zero voltage across the breaker will be
maximum. This results in re-striking of arc once again. Therefore switching inductive
load will be difficult
What is meant by protective angle? Give its value for reliable operation?
Answer: Protective angle is the vertical angle through the ground wire axis and the line
passing from the ground wire axis to the outermost phase conductor. Its value for
reliable protection is taken equal to 20-30 degrees
What is the difference between the lightning arrester and surge absorber?
Answer: Lightning arrester limits the duration and amplitude of the follow current while a
surge absorber reduces the steepness of the wave front for a particular surge
Answer: Time Graded protection is a scheme of over current protection, in which the
discrimination is incorporated i.e, the time setting of the relays is so graded that in the event of
the fault, the smallest part of the system is disconnected
Answer: The main elements of the carrier current protection are: Transmitter, Receiver, Coupling
equipment and Line trap
Answer: Difficulties are experienced in balancing the secondaries of the CTs and this is why
Merz-Price protection is not employed beyond 33kV
What types of relays are suitable for the protection of radial feeders?
Answer: Induction type IDMT relays are more suitable for protection of the radial feeders
because the time current characteristics are similar in shape and in no case they cross each
other at any time
What is the purpose of Line trap and Coupling capacitors in carrier channels?
Answer: Line trap is an LC network inserted between the busbar and connection of
coupling capacitors to the line and tuned to resonance at the high frequency and are
used to confine the carrier currents to the protected section so as to avoid interference
with or from adjacent carrier current channel.
Coupling capacitors is used to connect the high frequency (carrier) equipment to one of
the line conductors and simultaneously serves to isolate the carrier equipment from high
power line voltage
What is the minimum time interval set for two adjacent circuit breakers to operate
in radial feeders?
Answer: It will be usually around 0.4 sec
Where Impedance relay, Reactance relay and Mho relays are employed?
Answer: The Impedance relay is suitable for the phase faults relaying for the lines of
moderate lengths Reactance type relays are employed for the ground faults while Mho
type of relays are best suited for the long transmission lines and particularly where
synchronizing power surge may occur
In a 3-phase system the alternators or generators may be star connected or delta connected.
Likewise 3-phase loads may be star connected or delta connected. Some of the advantages of
star and delta cconnected systems are listed below
Star Connection:
In a star connection, phase voltage Vph = VL/ (3)1/2. Since the induced emf in the primary
winding of an alternator is directly proportional to the number of turns, a star connected
alternator will require less number of turns than a delta connected alternator for the same
voltage.
For the same line voltage, a star connected alternator requires less insulation than a
delta connected alternator. Due to the above reasons three phase alternators are generally star
connected.
In star connection, we get 3-phase and 4-wire system. This permits the use of two
voltages (phase voltages as well as line voltages). Single phase loads can be connected
between any one lie and neutral wire while the 3-phase loads can be put across the three lines.
Such a flexibility is not available in delta connection
In star connection, the neutral point can be earthed. Such a measure offers many
advantages. For example, in case of line to earth fault (L-G fault), the insulators have to bear
1/31/2 (57.7%) times the line voltage. Earthing of neutral also permits the use of protective
devices (relays) to protect the system in the case of ground faults
Delta Connection:
Why Sine Wave is chosen rather than a simple curve such as a square or triangular wave.
Some of the reasons are given below:
Hysteresis Loss:
When a magnetic material is subjected to a cycle of magnetization (magnetized first in
one direction and later magnetized in opposite direction in a cyclic manner), an energy
loss takes place. This energy loss is due to molecular friction in the material. That is, the
domains (or molecular magnets) of the material being turned first in one direction and
then the other. Energy is thus expended in the material in overcoming this opposition.
This loss is in the form of heat and is called hysteresis loss.
Hysteresis loss is present in all electrical machines whose iron parts are subjected to
cycle of magnetization like transformers, induction motors and other machines operated
on ac supply. When an alternating supply is provided to the electrical machines the flux
in the iron of these machines change in both direction and value alternatively. During
this process energy is lost and this loss constitutes the core loss of the machine. The
obvious effect of hysteresis loss is the rise of temperature of the machine
Transformers and most electric machines operate on alternating current. In such
devices, the flux in the iron changes continuously, both in magnitude and in direction.
Hence hysteresis loss occurs in these machines
Hysteresis loss also occurs when iron parts rotates in constant magnetic field eg-
dc machines
When the core of the machine such as transformer, induction motors is magnetized
with the magnetizing force (H) by applying voltage, magnetic flux density (B) increases
as shown in the figure (dotted lines) and saturates (first quadrant). Saturation region in
one in which increase in the magnetization force (H) will not further appreciably increase
the magnetic flux density (B) in the material.
When the applied voltage reaches back to the zero position from the peak (first half
cycle), magnetizing force will also becomes zero. However the magnetic flux density in
the core will not reach zero but have some finite value. This property of magnetic
material to withhold some flux (B) when magnetizing strength becomes zero is
called Retentivity.
During the next half cycle all the domains in the magnetic core tries to align in opposite
direction as the applied voltage polarity changes and hence the magnetizing force
applied. With increase in the magnetizing force (H) a point is reached where the
magnetic flux density(B) becomes zero. This point is called coercivity. Beyond this point,
magnetic flux will be in opposite direction with increase in field strength and reaches
saturation as shown in figure (third quadrant).
Further applied magnetic field will starts decreasing from peak and reaches zero. This
decrease in the magnetic flux with decrease in field strength can be seen in figure (third
quadrant) and reaches back when the voltage polarity changes.
This forms the B-H loop of hysteresis loop of the magnetic material of the machines
A Computer network that spans relatively small area is called Local Area Network
(LAN). Most LANs are confined to small building or group of buildings. However one
LAN can be connected to other LANs over any distance via telephone lines and radio
waves. A system of LANs can be cconnected in this way is called Wide Area Network
(WAN)
Most LANs can connect workstations and personal computers. Each node (individual
computer) in a LAN has its own CPU with which it executes programs, but it is also can
able to access data and devices anywhere in the LAN. This means that many users can
able to share expensive devices, such as laser printers, as well as data. Users can also
use the LAN to communicate with each other, by sending e-mails or engaging in chat
sessions or can able to play games together
Metropolitan Area Network or MANs are large computer networks usually spanning a
campus or a city. They usually use wireless infrastructure or optical fiber
communications to their sites
For instance a university or college may have MAN that joins together many of the local
area networks (LANs) situated around site of a fraction of square kilometer. Then from
their MAN they could have several Wide Area Network (WAN) links to other universities
or the internet. Specially this type of MAN is known as campus area networks
1. What is the main reason for providing metallic sheath in underground cables?
Answer: The metallic sheath is provided around the insulation to protect it against the
ingress of moisture, gas and other damaging liquids (acid or alkalies) from the soil and
atmosphere
2. What are the main requirements of the insulation materials used for
underground cables?
Answer: Some the properties that insulation material require to possess are high
insulation resistivity, high dielectric strength, good mechanical properties, non-
hygroscopic, non inflammable, immune to attacks by acids and alkalies
5. What are different insulation materials used in cables for high voltage and
medium voltage?
Answer:
Medium Voltage:
Polyethylene (PE)
Cross linked polyethylene (XLPE)
Tree retardant cross linked polyethylene (TR-XLPE)
Ethylene-Propylene Elastomers (EPR)
PILC
High Voltage:
Cross linked polyethylene (XLPE)
Paper/Oil
Paper/Polypropylene
SF6 gas
NEUTRAL GROUNDING:
Generally on neutral grounding is provided at each voltage. There will be several
voltage levels between the generation of the power and distribution of the power in the
power system. Only one ground is provided for each voltage level of the power system
Grounding of the power system is provided at the source and not at the load end
Each of the major bus section in the system are grounded
For generator grounding, neutral of the generator is grounding through a
resistance which limits the stator fault current. The value of the resistor employed for the
grounding the generator decides the percentage of the generator windings left
unprotected
Synchronous motors and synchronous capacitors are provided with reactance
type of grounding. This reactance grounding provides additional reactance which
provides additional lagging currents which nullifies the capacitive grounding currents
When several generators are connected to a common neutral bus, the bus is
connected to the ground through a single grounding device. Disconnect switches
are used to ground the desired generators to the neutral bus
When several generators are operating in parallel, only one generator neutral is
earthed. This is to avoid the interference between the zero sequence currents
In generating stations there is a provision to ground neutral of at least two
generators, though one at a time. The other generator neutral is grounded when
the first generator is out of service
When there are one of the two supply sources, no switching equipment is used in
the grounding circuit.
For the protection purpose, the neutral point of the star side of the power
transformer is usually grounded
The star connected secondary sides of the protective CTs and PTs are grounded
at one point. This ensures stable neutral, proper measurement of the voltages
and currents, kWh and kVA on the secondary side measuring instruments and
controls
For the circuits between 3 kV and 33 kV resistance or reactance grounding is
used. But for low voltages less than 600V and high voltages above 33 kV solid or
effective grounding is used. Effective grounding limits the voltages of healthy
phases to line-to-neutral values in the events of ground faults and also eliminates
the arcing grounds. The effective grounding causes the ground fault currents of
very high magnitudes flow through the machine. But modern day protection
systems are very sensitive and fast operating so that faults are cleared in very
short time
Name the materials used for the contacts of vacuum circuit breakers?
Answer: Copper-Bismuth, Copper-lead, Copper-tellurium, Silver-bismuth, Silver-lead
and Silver-tellurium are some of the alloys employed as contact materials in the vacuum
circuit breakers
Rated Making Current = 1.8 x (2)1/2 rated short circuit breaking current
= 2.55 x rates short circuit breaking current
= 2.55 x symmetrical breaking capacity
BATTERY:
Valve Regulated Lead Acid (VRLA) Batteries are popularly termed as maintenance free lead
acid batteries. Each cell in VRLA battery will have a value (automating operating) to allow the
gas to escape if developed by the over charging the cells and to hinder the entrance of oxygen
from the air into the cell
These VRLA batteries are also called sealed lead acid batteries and also recombinant batteries.
Oxygen which evolve during discharging at the positive plate of the battery recombine with the
hydrogen which evolve at the negative plate of the cell to from water. This results in prevention
of the water loss and unlike flooded batteries water is not needed to be added periodically. The
valve present in VRLA cell acts as a safety valve which opens when the concentration of
hydrogen gas inside the battery increases dangerously high. Some of the advantages of VRLA
cell is listed below:
Advantages:
VRLA battery is maintenance free and no periodic water refilling is not required
Reduced demand on ventilation
The capacity range of VRLA battery is high (12000 Ah)
VRLA batteries will have longer life. Life span of this batteries will be around 10 years
Feasibility for float charge operation with the same voltage of the cells, to continue in
using existing charging equipment
VRLA batteries are economical
Battery Interview Question and Answers
What is primary cell and secondary cell?
Answer: Battery which can be discharged only once is called primary cell ex: Manganese Zinc and alkaline
Secondary cells are the battery which can be charged and discharged for a number of times ex: Lead acid and
Nickel cadmium
What factors that decide the VRLA battery to completely charged from fully discharged condition?
Answer: Some of the important factors that determine the duration of the discharged battery to charge are:
Duration of the discharge occurred
Temperature at which battery is operating
Size and efficiency of the charger
The secondary of the CT is almost short circuit, whereas the secondary of the PT is practically a open
circuit
The primary winding of the CT is connected in series with the load so that it carries the full line current,
but there is only a small voltage across it. However the primary winding of the PT has the full supply voltage
applied across it
In CT the excitation current I 0 and flux density vary over a wide range whereas in PT, they vary over a
limited range only,
Three phase system is widely used in generation, transmission and distribution. Single phase system is only
used to operate small electrical appliances at consumer ends where the power rating is very less. Some of the
advantages of three phase system or poly phase systems compared to single phase system is explained below
Advantages of three phase system:
The output of 3 phase machine is always greater than single phase machine of same size. The output
will be approximately 1.5 times than single phase machine. So for given size and voltage 3 phase alternator or
electrical machines occupy less space and less cost compared to single phase machine having same rating
For transmission of electrical power three phase supply requires less copper or less conducting
material than that of single phase system for given volt-amperes and voltage ratings. Hence 3 phase system is
more economical compared to single phase system
Single phase machines are not self starting machines. On the other hand three phase machines are
self starting due to rotating magnetic field. Therefore in order to start a single phase machine an auxiliary
device is required which not in the case of 3 phase machine.
Power factor of single phase machines is poor compared to three phase machines.
In single phase system the instantaneous power is function of time. Hence fluctuates with respect to
time. The fluctuating power will cause significant vibrations in the single phase machines. Hence performance
of single phase machines is poor. While instantaneous symmetrical three phase system is always constant
Three phase system gives steady output
Single phase system can be obtained from three phase supply system, vice-versa is not possible
For converting systems like rectifiers, the dc voltage waveform becomes more smoother with the
increase in the number of phases of the system. Hence three phase system is advantageous compared to
single phase system
3 phase motors will have uniform torque whereas single phase motors will have pulsating torque
Parallel operation of three phase generators will be simple compared to single phase generators
because of pulsating reaction in single phase generator
Consider a generator whose output power is 1000kVA, for different power factors 0.2,
0.5 and 0.8 and unity respectively the output power in kW will be 200, 500, 800 and
1000kW.
Class Y:
Maximum hot spot temperature for this type of insulator is 90 oC
Some of the materials used are cotton, silk, paper, wood without impregnated
Class A:
Maximum hot spot temperature for this type of insulator is 105 oC
Cotton, Silk, and Paper when suitably impregnated are the type of materials used
Class E:
Hot spot temperature is 120oC
Materials possessing degree of thermal stability allowing them to be operated at
a temperature 15oC above higher than Class A. Ex: wire, enamel etc
Class B:
Maximum hotspot temperature is 130oC
Mica, Glass fibre, asbestos, etc with suitable impregnation or coating substance
Class F:
Hot spot temperature is 155oC
Mica, glass, asbestos etc with suitable binding impregnation or coating
substances capable of withstanding 25oC higher than Class B
Class H:
Maximum hotspot temperature of 180oC
Combination of materials such as mica, glass fibre, asbestos suitably bonded
Class C:
Hotspot temperature above 180oC
Mica, porcelain, glass, quartz and asbestos with and without inorganic binder
Two alternators or synchronous generators which are to be operated in parallel should have same
output voltage rating
The rated speed of the machines which are operating in parallel should be such as to give the same
frequency (f is equal to (PxN)/120)
The alternators should be of the same type so as to generate voltages of the same waveform.
Generators operating can have different power rating (KVA rating)
The prime movers of the alternators should have same speed load characteristics, the nature of
characteristics should be drooping so that load on the generator is proportional to output rating of the
alternators
Without reactancce the alternators will not develop generating power and parallel operation would not
be possible. Hence the alternators should have reactances in armature circuits, otherwise they will not operate
in parallel
Why Reactive Power is Generated at Load
Reactive Power if possible should be generated close the load centers or close to the point of its consumption.
Some of the reasons why reactive power cannot be transmitted to long distances are:
It is inefficient during the high real power transfer and also requires higher voltage magnitude
gradients.
It causes high real and reactive power losses if reactive power is transmitted through long distances.
Real power losses should be kept minimum for economic point of view and reactive power should be reduced
to minimize the investment in reactive power devices such as shunt capacitors.
It can lead to damaging temporary over voltages following load rejections. When the receiving end
circuit breaker opens with transmission line still energized from sending end, then over voltages occurs as the
voltage magnitude depends upon the reactive power in the system. Over voltage will damage the insulation of
the conductor and wingdings.
If reactive power is to be transmitted through long distances in the power system It requires larger size
of the equipment (transformers and cables) in the power system.
Symmetrical Components:
Any unbalanced three phase system of currents, voltages or other sinusoidal quantities can be resolved in to
three balanced of phasors which are known as symmetrical components of the original unbalanced system.
This three balanced systems constitutes three sequence networks which are solved separately on single phase
basis.
The symmetrical components differ in phase sequence, i.e, the sequence in which the phasor quantities attains
the maximum value. Any unbalanced system quantities (current, voltage, other sinusoidal quantities) can be
represented in set of symmetrical quantities which constitutes positive sequence components, negative
sequence components and zero sequence components.
Since in symmetrical system as there is no interaction between the quantities of different sequences, currents
of any sequence is considered to flow in an independent network associated with that sequence only. In simple
words we will get different sequence networks for positive, negative and zero sequence components, for
example positive sequence current will flow in positive sequence network only. The single phase equivalent
circuit of any component consists of impedances associated with that circuit and it is called sequence network
for particular sequence component.
This helps in analyzing the system performance when there is unbalanced fault, interaction between the
quantities (voltage, current) of different sequences can be determined by interconnecting the sequence
networks (positive, negative and zero) at the fault location.
Main advantage of sequence components are isolating the quantities (voltage, current) in to components
(positive, negative, zero) which helps in better criteria for controlling factors for different applications
In Stability analysis investigations the synchronizing force between the machines is affected by the
positive sequence components.
Heating effect due to unbalanced currents depend on the negative sequence components. (when
heating is observed due to unbalanced currents that determines presence of negative sequence component
currents flowing the system. By reducing the unbalanced currents heating effect and negative sequence
components can be reduced.
When earth fault occurs zero sequence currents flows through the system. Hence all ground or earth
fault relay operates on determining the zero sequence components.
Where Star (wye) Delta transformer is used in Power
system
Generation side of the transformer (LV side) voltage applied is low and current flowing through the windings of
the transformer is high. At secondary side (LV side), delta connection (Δ) is employed because in delta
connection Iphase=ILine/√ 3 and Vphase=VLine.
Current carrying capacity of windings depends on the thickness of the conductor. Large current flowing through
the conductor means more copper utilised for the windings. Therefore in order to reduce the flow of huge
currents by above equation delta winding is employed in the LV side of the transformer.
On the other hand star type (Y) of connection is employed on the HV side of the transformer. In star connection
Vphase=VLine/√ 3 and Iphase=ILine.
Voltage withstand ability of conductor depends on the insulation strength of the conductor. Hence to reduce the
phase voltage Star (Y) connection is employed in the high voltage (HV side) of the transformer.
When load on transformer increases current flowing the transformer windings increases. Heat generated by the
rise in the current will be dissipated in to the transformer oil. Heated transformer oil becomes less denser
compared to the normal transformer oil and moves up in to the conservator. This heat will be dissipated in to
the atmosphere from hot transformer oil.
When load on transformer increases, transformer breather breathes air in. Air contains moisture when come in
contact with the oil will affect the purity of the transformer oil. Moisture and impurity level in the transformer oil
increases results in the damage of insulation property of the transformer oil.
To avoid entry of moisture air in to the transformer silica gel crystals are used. Silica gel will absorb the
moisture in the air and allows dry air in to the transformer. Silica gel will be blue when they are installed or dry.
When the crystals absorb the moisture they turn to pink color.
Thus silica gel protects the insulation strength of the transformer oil by absorbing the moist air entering in to the
transformer.
In Transformer design LV winding will be wound close to the core of the transformer because the insulation
provided between the LV winding and core of the transformer is quite less compared to the insulation provided
between the HV winding and the core of the transformer which results in less cost for insulation and reduction
in the size of the transformer for same MVA rating. Hence due to this reason LV winding is placed near to the
core of the transformer.
On the core of the transformer insulation is placed and LV winding is wound. Once again insulation is placed
between the LV winding and HV winding.
When current flowing in the same direction in the two adjacent conductors magnetic
filed will be produced in such a manner that they attract each other
On the other hand, when current flowing in opposite direction in two adjacent
conductors magnetic field will establish in such a manner such that both the conductors
repel each other
Stranded Conductors:
Stranded wire consists of sub conductors touch each other. It is costlier to manufacture compared to solid wire.
For the given current carrying capacity the size of the stranded conductor is large compared to solid wire.
Different elements of strands can be wound together to get the transmission line of desired property (eg: ACSR
conductor contains Aluminum and Steel stands wound together). Proximity and skin effect is reduced using
stranded conductors.
Bundled Conductors:
Bundled conductors are employed in Extra High Voltage (EHV) transmission as at higher voltages corona effect
is significant. In bundled conductors sub conductors are placed as certain distance throughout the transmission
lines. This reduces the corona discharge loss and interference with the communication lines nearby.
Bundled conductors per phase reduces the voltage gradient in the vicinity of the line. Thus reduces the
possibility of the corona discharge. (Corona effect will be observed when the air medium present between the
phases charged up and start to ionize and acts as a conducting medium. This is avoided by employing bundled
conductors)
Improvement in the transmission efficiency as loss due to corona effect is countered.
Bundled conductor lines will have higher capacitance to neutral in comparison with single lines. Thus
they will have higher charging currents which helps in improving the power factor.
Bundled conductor lines will have higher capacitance and lower inductance than ordinary lines they will
have higher Surge Impedance Loading (Z=(L/C)1/2). Higher Surge Impedance Loading (SIL) will have higher
maximum power transfer ability.
With increase in self GMD or GMR inductance per phase will be reduced compared to single
conductor line. This results in lesser reactance per phase compared to ordinary single line. Hence lesser loss
due to reactance drop.
Mobile Substation typically contains Trailer for unit, Distribution Transformer, Cooling system for
Transformers, Switchgear equipment (relays, circuit breakers, isolators etc..)
Advantages of Mobile Substation:
Mobility in service
Quick access for service
Less Maintenance cost
Minimum Clearance for utilization
Increase in Reliability
Maximum KVA with minimum height.
Application of Mobile Substations:
Mobile Substations are employed to provide emergency power supply during natural
disasters and during wars
It also used to supply power when ordinary conventional substation is under
maintenance or fault
It also employed for providing temporary load supply to industrial plants, remote
locations.
2. What are V and inverted V curves in Synchronous motor and their significance?
20. Why single phase induction motor is not self starting and methods to start single phase
induction motor?
What is a Signal
Anything which carries information is a signal. A signal is a real (or complex) valued function of one or more
real variable(s).When the function depends on a single variable, the signal is said to be one dimensional. A
speech signal, daily maximum temperature, annual rainfall at a place, is all examples of a one dimensional
signal. When the function depends on two or more variables, the signal is said to be multidimensional. An
image is representing the two dimensional signal, vertical and horizontal coordinates representing the two
dimensions A signal is a description of how one parameter is related to another parameter.
Types of Signal
For example, the most common type of signal in analog electronics is avoltage that
varies with time. Since both parameters can assume a continuous range of values, we
will call this a continuous signal. If this signal is passed through an analog-to-digital
converter force each of the two parameters to be quantized. Signals formed from
parameters that are quantized in this manner are said to be discrete signals. Discrete
signals are quantized in one dimension ( as discrete signal is obtained by sampling of a
continuous signal the signal obtained will be discrete with respect to time axis and
amplitude of the signal is continuous . Digital signals are those which obtained by
taking finite number of distinct values. Digital signals are discrete with respect to both
time and amplitude. Digital signals are quantized in both dimension ( X-axis and Y-axis
particular value exist; signal represented as just like a set of points in the plot depends
on the sampling rate)
Why Transformer rating is in KVA not kW
Rating of Electrical Transformer is in VA (Volt Amperes ) because:
Maximum current carrying capacity of the transformer is determined by the thickness of the conductor and
Maximum voltage supplied to the winding depends on the insulation strength of the conductor
Manufacturers of Transformers and alternators does not know at what power factor the consumer uses the
machine and the nature of the load (capacitive, resistive and inductive) connected to the machine. Hence they
rate the transformer depends on the maximum current carry and the voltage to be applied. This rating of the
transformer corresponds to apparent power of the machine (VA). Also iron losses in transformer depends on
the the voltage applied and copper losses depends on the current flowing through the winding. These losses
are independent of the power factor at which the transformer operates.
On the other hand induction motors are rated with real power (Watts) as the machine operating at defined
power factor at full load is pre determined.
Eg: Consider a transformer can carry maximum current of 50A and max voltage applied is 200V. Then
Power rating of the at full load (Unity power factor) = 50x200 = 10kW
Power rating of the at full load (0.5 power factor) = 50x200x0.5 = 5kW (This means load having 0.5 power
factor can connect maximum of 5kW to the transformer. 5kW is the full load of the transformer)
Reactive Power:
Reactive power is the power which will not do any useful work in the power system but helps the active power
to flow. Without Reactive Power active power will not able to flow in the system.
Answer: Some of the reasons or advantages why SCADA systems are implemented are:
Answer: Remote Terminal Units (RTUs) contain generally microprocessor having 16 bit or 32 bit
(eg: 68302 or 80386)
Answer: Remote Terminal Units (RTUs) are operated from 110V/240V + or - 10% and 50Hz or
12/24/48V + or - 10% DC Voltage
What are advantages of PLCs over RTUs?
Answer: Advantages of Programmable Logic Controllers (PLCs) are they can be used for general
purpose can easily set for verity of functions. Some of the advantages of PLCs over RTUs are: PLCs
are reliable, cheap, flexible compared to RTUs, sophisticated control and troubleshooting in PLC is
easier.
In simple words, Hence PLC acts as interface between the input and output devices at the process side of
the industries. It monitors the inputs receive from the input devices and takes necessary output control
functions by executing the programs stored in its memory.
The term Logic is used in Programmable Logic Controllers because all the program inside the PLC will be of
Logic programming (eg: Ladder diagrams ).
In industrial applications hard wired relay logics were replaced by Programmable Logic Controllers due to
its reliablity, simplicity, low cost, easier programming and many other functions
To reduce this effect to minimum the conductors are transposed. Transposition can be made either to the
power conductors or telephone (communication ) lines.In a transposed line each of the three conductors
occupies all the three positions relative to the other conductors for one third of the total length of the
transmission line. The purpose of transposition is due to balance the capacitance of the line so that electro-
statically induced voltages balances out in the transposed lines.
Under balanced condition the conductors magnetic field linking an telephone line is shifted by 120 o out of
phase. As the power lines are transposed, over the length of one complete transposition cycle ( three different
positions of the power conductor) of power line, the net voltage induced in the telephone line is zero. This is
because the sum of three induced voltages which are displaced by 120 o in phase combines zero.
Anwer: For a given conducting material insulation required depends on the voltage. Hence if
High Voltage (HV) winding is placed near to the transformer core, more insulation is required to
insulate between the transformer core and the High Voltage (HV) winding. This results in
increase in the cost of the insulation material and also size of the transformer increases
significantly. Thus Low Voltage (LV) winding is placed near the core which requires less
insulation between the core and LV winding
Routine tests:
These are carried out on every transformers before dispatch to ensure that it is in accordance
with the specifications.Some of the tests come under routine test include:
Type Tests:
Type tests are performed on the first transformer of one type and are intended to check the
design characteristics. It is presumed that every transformer would also comply with the type
test, since its design is identical.
Also the flux flowing through the iron core from primary winding to secondary winding not only
links the secondary winding but also primary winding. Due to this flux linkage self induced emf is
produced in the primary winding. This self induced emf in the primary winding will oppose the
applied voltage and hence it acts as back emf. This back emf limits the primary current flowing
through the primary winding in normal operating condition (similar like dc machine armature
current).
When a dc supply is provided to the transformer primary no self induced emf will be generated
(no back emf). Therefore heavy current will flow in the transformer primary winding which may
result in burning down the transformer primary winding.
When dc supply is given to transformer what happens? and which winding will
burn (primary or secondary)?
Smart Grid:
Smart Grid is an an intelligent, future electricity system that connects all the generating systems
(supply), grid and distribution systems ( consumer terminals) through an intelligent
communication system.Smart Grid is a family of network control systems and asset
management tools, empowered by sensors, communication pathways and information tools.
Simply smart grid is an secure integration of electrical and information infrastructures.
Major focus on the smart grid is on the distribution level or consumers. Demand is what drives
the supply, so better management at consumer level helps the overall system. Important
component of smart grid is 'smart metering'. Older meters connected to consumers just
indicated the units consumed by the consumer. Smart meters evolved in to advanced metering
system where the meter not only stores but also communicates loads and other power statistics
in real time and even advice the consumers for better and optimal load control for reduction in
prices. Smart grid explains and gives choice to the consumers to decide the timing and amount
of power consumption based on the price per unit at that instant. Thus smart grid provides many
wide features to the consumers for reducing the electricity bills and participating the consumers
in improving the performance of the grid.
Smart grid helps the Generation and Transmission companies in dealing effectively with the
power thefts and system losses through smart metering and advanced communication features.
This also reduce in the reduction in the CO2 emissions in to atmosphere.
Thus smart grid helps in reducing the losses, electricity bills and global warming and makes the
electrical grid stronger to disturbances.
Please find some more sources related to this and i hope this can become a good seminar topic
as it is the emerging technology and everybody talking about. Add some surveys, reports and
case studies while presenting the seminar topic which makes the subject more informative and
useful.
SCADA systems
SCADA systems:
SCADA systems consists of SCADA Master which is generally referred as SCADA Master Station which
includes SCADA hardware system and SCADA software system and Remote Terminal Unit (RTU). SCADA
master station job is to communicates with Remote Terminal Unit (RTU) for carrying out monitoring, control,
data storage and Human Machine Interface (HMI) operations. SCADA hardware consists of hardware
components such as very reliable PC ( work station ) and its peripherals present in the master station and able
to control the RTUs or PLCs (programmable Logic Controllers) through SCADA software. SCADA software
system was developed to communicate with the PLCs or RTUs for data acquisition and control operations.
Display the real time data received from PLCs, RTUs, and IEDs
Stores the received historical data received
Activates alarms when necessary
Displaces sequences of events during disturbance
Provide an Human or Operator Interface for supervisory control
Perform the communication control over the network
SCADA Hardware system:
Master station is a part of the WAN or LAN network. The hardware for the master station includes high end and
more reliable PC (workstation), its peripherals and its communication ports. Reliability of the hardware in
master station is important else entire SCADA system will tamper. Redundant workstations are provided to
improve the reliability of the system.
Data acquisition: Refers to receiving and analyzing and processing the data from the field.
Control: Controlling the remote units (RTUs) by commands initiated either by operator or automatic according
to predefined parameters.
Data Storage: Storing the historical data obtained from the field.
Human machine Interface: Includes input and output devices for interaction between the operator and software,
the way the data is displayed in graphs and the commands given to the system
SCADA application software is optional software to enhance the performance of the SCADA main software
Low voltage generation for particular power level (say 500MW) requires large
size of the stator conductors as huge currents flow through the stator because of low
voltage. ( Any current carrying conductor size is decided by the amount of current
flowing through the conductors). With larger the stator current flowing through the higher
the copper loss and the heat dissipated. Therefore requires better and larger heat
removing medium. Thereby increase in the cost and size of the machine. Low voltage
power generation also results in increase in the size of the generator and occupies
larger space.
On the other hand, increase of the machine voltage significantly beyond the
minimum necessary value results in requirement of more insulation for the generator
stator windings, thus increasing its size and cost. This increase in voltage for power
generation also increases the size of the machine.
Therefore an optimum value of Voltage and Current values are attained for designing
the generator considering the cost and size factors of the generator.
Example:
660 MW electrical generation plant usually operate at 23.5 kV with line currents of about
19,000 A at 0.85power factor.
3) The phenomenon in which the conductor surface carries more current compared to
core when alternative voltage is applied is
a) Corona
b) Skin Effect
c) Ferranti Effect
d) Lenz's Law
Answers:
a) ac
b) dc
c) pulsating
d) dc superimposed on ac
a) ac to dc
b) dc to ac
c) both a and b
a) Statically
b) Dynamically
c) magnetically
d) Electrostatically
b) Lenz's law
d) none of these
6.A Conductor is rotating within a magnetic field. At which position do the peak voltage occur:
d) Anywhere
a) dc generator
b) dc motor
c) alternator
d) Transformer
8.EMF induced in a coil rotating in a uniform magnetic field will be maximum when the:
Answers:
By increasing the spacing between the transmission line conductors. However the
spacing between the lines cannot be increased very much as this effects the size of the tower,
weight of the supporting structures and the land occupied by the tower.Hence the distance
between the conductors should be chosen optimum so that the critical breakdown voltage
increases.
Other factor on which the critical breakdown voltage is diameter of the conductor. By
increasing the diameter of the conductor breakdown voltage of the corona can be increased.
The increase in the conductor diameter results in reduction of the electric field intensity which
reduces the corona. Hence hollow conductors are employed for reducing the corona in EHV
lines.
By using the bundled conductors the diameter of the conductor increases
compared to diameter of the normal conductor for same power rating. Increase in
the conductor diameter reduces the electric field intensity. Hence corona loss can
be reduced.
In simple corona can be reduced by increasing the distance between the current
carrying conductors, increasing the diameter of the conductors (employing Hollow
conductors) and by using Bundled conductors corona loss can be reduced or
minimized.
The voltage gradient for breakdown of the air is proportional to its density. In stormy weather
(bad climate) the number of ions may be more than normal. As more number of ions present
between the conductors means reduction of insulating property of the medium. So corona can
occur at less voltage than critical breakdown voltage during bad climatic conditions than fair
weather conditions.
Conductor:
The corona is conserved to be affected by the Size(diameter), shape(stranded or
smooth) and surface condition (dirty or clean) of the conductor.
Corona decreases with the increase in the conductor diameter. This is due to the fact
that increase in the conductor diameter reduces the electric field intensity.
For Stranded conductor corona is more compared to solid conductor. As the potential
gradient of the stranded surface is more compared to the normal solid conductor for same power rating.
For dirty surfaced conductor the break down voltage required for corona formation is
less than clean surfaced conductor.
Spacing between Conductors:
With increase in the spacing between the conductors the electrostatic stresses reduces
results in reduced corona effect
Line Voltage:
At low line voltage there will be no corona. When the voltage applied increases
breakdown voltages then corona formation takes place